M800V/M80V Series PLC Programming Manual (1/2)
4 Explanation of Devices
4.4 Detailed Explanation of Devices

4.4.7 Timer T

The 100 ms timer and 10 ms timer are available for this count-up type timer.
The 100 ms timer and 10 ms timer are differentiated by the instructions used. Refer to "7.3 Output Instructions" for details.
100 ms timer T
 When the input conditions are set, the count starts. When the set value is counted, that timer contact will turn ON.
 If the input conditions are turned OFF, the 100 ms timer count value will be set to 0, and the contact will turn OFF.
X5
Input
conditions
 The value is set with a decimal, and can be designated from 1 to 32767 (0.1 to 3276.7 (s)). The data register D or file
register R data can be used as the setting value.
10 ms timer T
 When the input conditions are set, the count starts. When the set value is counted, that timer contact will turn ON.
 If the input conditions are turned OFF, the 10 ms timer count value will be set to 0, and the contact will turn OFF
X5
Input
conditions
 The value is set with a decimal, and can be designated from 1 to 32767 (0.01 to 327.67 (s)). The data register D or file
register R data can be used as the setting value.
With the device T, the contact/coil is handled as bit device, and the current value is handled as word device.
In the function instructions described after, the word device T indicates the current value even if there is no description about
it.
IB-1501667-B
X5
K50
T193
T193 coil
T193 contact
100 ms timer
Display for 10ms timer instruction
X5
H K500
T1
T1 coil
T1 contact
10 ms timer
ON
OFF
ON
OFF
5 seconds
OFF
ON
ON
OFF
OFF
ON
5 seconds
OFF
ON
40