Mitsubishi Electric NZ2GF2B1-16D User Manual page 289

Cc-link ie field network remote i/o module
Table of Contents

Advertisement

(b) Immunity requirements
Specifications
Test item
EN61000-4-2
Electrostatic discharge
*1
immunity
EN61000-4-3
Radiated, radio-
frequency,
electromagnetic field
*1
immunity
EN61000-4-4
Electrical fast
transient/burst
*1
immunity
EN61131-2: 2007
EN61000-4-5
Surge immunity
EN61000-4-6
Immunity to conducted
disturbances, induced by
radio-frequency fields
EN61000-4-8
Power-frequency
magnetic field immunity
EN61000-4-11
Voltage dips and
interruption immunity
*1
The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a
conductive control panel. The tests were conducted with the module installed in a control panel.
The accuracy of an analog-digital converter module may temporarily vary within 10%.
*2
Test details
Immunity test in which electrostatic
is applied to the cabinet of the
equipment.
Immunity test in which electric fields
are irradiated to the product.
Immunity test in which burst noise is
applied to the power line and signal
line.
Immunity test in which lightning
surge is applied to the power line
*1
and signal line.
Immunity test in which high
frequency noise is applied to the
power line and signal line
*1
Immunity test in which the product
is installed in inductive magnetic
*1
field
Immunity test in which power
supply voltage is momentarily
*1
interrupted
Standard value
• 8kV Air discharge
• 4kV Contact discharge
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
• AC/DC main power, I/O power, AC I/O (unshielded): 2kV
• DC I/O, analog, communication: 1kV
• AC power line, AC I/O power, AC I/O (unshielded): 2kV CM,
1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
*2
• DC I/O, AC I/O (shielded), analog
0.15M-80MHz,
80% AM modulation @1kHz, 10Vrms
50Hz/60Hz, 30A/m
• Apply at 0%, 0.5 cycles and zero-cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
APPENDICES
A
, communication: 1kV CM
287