Mitsubishi Electric NZ2GF2B1-16D User Manual page 60

Cc-link ie field network remote i/o module
Table of Contents

Advertisement

Item
Availability of connecting extension module
Voltage
Module power supply
Current
Weight
*1
For how to calculate the processing time of the remote device station (output), refer to the point in the following.
( Page 54, Section 4.2.2 (1))
*2
Using bar solderless terminals is recommended for wiring.
*3
Only one wire can be connected to a wire insertion opening. Multiple wires cannot be connected to a terminal.
Connecting two or more wires may cause a poor contact.
*4
For how to calculate the current consumption when an extension module is connected, refer to "Calculating Current
Consumption". ( Page 92, Section 4.4)
Connector for module
*5
power supply and FG
Pin
UNIT POWER
No.
CABLE
1
1
2
2
3
Module power
3
supply
Terminal block
*5
for output
Load
1
2
3
4
5
6
7
8
9
10
11
12
13
External power supply
for the output part
14
15
Load
16
17
18
Load power
supply
Load
17
18
*5
Only one wire can be connected to a wire insertion opening. Multiple wires cannot be connected to a terminal.
Connecting two or more wires may cause a poor contact.
58
Connectable (Max. one module)
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
190mA or less (24VDC, all points ON)
0.31kg
External connection
Signal name
Non-insulated
+24V
24G
FG
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
YA
YB
YC
YD
YE
YF
CTL+
COM-
Constant-voltage
circuit
External power supply for the output part
and load power supply (common)
CTL+
COM-
NZ2GF2S1-16T
*4
Terminal block mounting screw
Terminal block mounting screw
Terminal block
Pin number
1
3
5
7
Signal name
Y0
Y2
Y4
Y6
Pin number
2
4
6
8
Signal name
Y1
Y3
Y5
Y7
9
11
13
15
17
Y8
YA
YC
YE
CTL+
10
12
14
16
18
Y9
YB
YD
YF
COM-

Advertisement