Mitsubishi Electric NZ2GF2B1-16D User Manual page 189

Cc-link ie field network remote i/o module
Table of Contents

Advertisement

(2) Checking and clearing the number of ON times
The number of ON times can be checked and cleared on the program.
Item
Number of ON times integration value Y
(address: 0610H to 064FH, 0710H to 072FH)
Number of ON times integration value clear
command Y (address: 1100H, 1102H,
1200H)
Number of ON times integration value clear
completed Y (address: 1101H, 1103H,
1201H)
● When the ON time and the OFF time of the target output signal are less than 10ms, the output module cannot recognize
the output change and the number of ON times may not be counted.
● When the number of ON times integration value exceeds 2147483647, the count stops. To integrate the number of ON
times continuously, clear the integration value by using Number of ON times integration value clear command Y
(address: 1100H, 1102H, 1200H).
● The number of ON times is counted also when the fast logic function is enabled.
Description
Stores the integration value of the number of ON times integration
function.
When the corresponding bit of output is turned on, the integration
value for the output with the number of ON times integration function
is cleared to zero.
After the integration value is cleared to zero using Number of ON
times integration value clear command Y (address: 1100H, 1102H,
1200H), the bit of the output which is cleared to zero turns on.
CHAPTER 9 FUNCTIONS
Reference
Program Example
• Page 214, Section 10.3
Details of Remote Buffer Memory
Addresses
• Page 277, Appendix 3 (13)
Program example
• Page 224, Section 10.4.2
Details of Remote Buffer Memory
Addresses
• Page 283, Appendix 3 (22)
Program example
• Page 224, Section 10.4.2
Details of Remote Buffer Memory
Addresses
• Page 285, Appendix 3 (23)