(1) Module status area (RWr0)
(a) Initial processing request flag (RWr0.b8)
The operations of Initial processing request flag (RWr0.b8) and Initial processing completion flag (RWw0.b8)
vary depending on the setting value of Initial operation setting (address: 0004H).
• When With initial processing (0) is set
After the module is powered on, Initial processing request flag (RWr0.b8) turns on. Create a program
where initial processing is executed by using Initial processing request flag (RWr0.b8) and Initial
processing completion flag (RWw0.b8). When Initial processing completion flag (RWw0.b8) is turned on,
Remote READY (RWr0.b11) turns on. Also when Initial processing completion flag (RWw0.b8) is turned
on, Initial processing request flag (RWr0.b8) turns off.
When setting parameters using Initial processing request flag (RWr0.b8) as an interlock as shown in the program example,
set Initial operation setting (address: 0004H) to With initial processing (0). After that, perform initial processing and check
that Remote READY (RWr0.b11) is on.
For program examples of initial processing, refer to the following.
• Initial processing ( Page 222, Section 10.3 (6) (a))
*1
Module power supply
Initial processing request flag
(RWr0.b8)
Initial processing completion flag
(RWw0.b8)
Parameter area
Remote READY
(RWr0.b11)
*2
External input signal X0
RX0
*1
When data link starts at the same time of when the module is powered on
*2
When an external input device connected to X0 is on
258
Controlled by the I/O module
Controlled by the program
ON
OFF
ON
OFF
ON
OFF
Parameter settings are
read from the internal
nonvolatile memory.
OFF
OFF
OFF
OFF
OFF
(Setting value A)
The operation is started
with the setting value A.
ON
ON