D/A Conversion Enable/Disable Setting Function; D/A Output Enable/Disable Setting Function - Mitsubishi Electric MELSEC iQ-R Series User Manual

High speed digital-analog converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

1.3

D/A Conversion Enable/Disable Setting Function

Common
Set whether to enable or disable the D/A conversion for each channel.
Disabling the D/A conversion for unused channels reduces the D/A conversion cycles.
The conversion cycle of the D/A converter module is the Conversion speed  Number of D/A conversion enabled channels.
Setting method
Set "D/A conversion enable/disable setting" to "D/A conversion enable" or "D/A conversion disable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [D/A conversion
enable/disable function]
1.4

D/A Output Enable/Disable Setting Function

Common
Specify whether to output the D/A conversion value or the offset value for each channel.
The conversion cycle is a constant, regardless of the D/A output enable/disable state.
Setting method
Set to enable or disable the D/A output for each channel with 'CH1 Output enable/disable flag' (Y1).
'CH1 Output enable/disable flag' (Y1)
Enable (ON)
Disable (OFF)
1 FUNCTIONS
22
1.3 D/A Conversion Enable/Disable Setting Function
Analog output
The D/A conversion value is output.
The offset value is output.