Mitsubishi Electric NZ2GF2B1-16D User Manual page 278

Cc-link ie field network remote i/o module
Table of Contents

Advertisement

(11)Extension module identification code (address: 0200H)
Set the identification code to specify the extension module type.
This remote buffer memory is provided only for extension modules.
Extension module not connected
Extension input module
Extension output module
Extension module not connected
16 points
(a) Enabling the setting
Turn on and off Operation condition setting request flag (RWw0.b9) to enable the setting.
(b) Default value
The default value is Extension module not connected (0000H).
If the set module type differs from the extension module actually connected, an error code (0501H) is stored in Error code
(RWr1), Error status flag (RWr0.b10) turns on, and the ERR. LED turns on. Then the main I/O module and extension I/O
module stop the I/O operation.
(12)Fast logic enable status (address: 0602H, 0603H, 0702H)
The fast logic enable or disable status for each signal is stored.
0602H, 0603H
0702H
(Address: 0602H)
(Address: 0603H)
(Address: 0702H)
276
b15 b14 b13 b12 b11 b10 b9 b8
Module type
Module type
Points
Address
b15 b14 b13 b12 b11 b10 b9 b8
0
0
0
0
Data for b8 to b15 are fixed to 0.
b15 b14 b13 b12 b11 b10 b9 b8
0
0
0
0
Data for b8 to b15 are fixed to 0.
b15 b14 b13 b12 b11 b10 b9 b8
0
0
0
0
Data for b8 to b15 are fixed to 0.
b7 b6 b5 b4 b3
Point
00H
01H
02H
00H
01H
Main module
Extension module
b7 b6 b5 b4
0
0
0
0
Y7
Y6
Y5
b7 b6 b5 b4 b3 b2
0
0
0
0
Y17
Y16
Y15
b7 b6 b5 b4
0
0
0
0
Yn7
Yn6
Yn5
b2 b1
b0
Setting value
Setting value
Module type
b3 b2 b1
b0
Y4
Y3
Y2
Y1
Y0
0: Disable
1: Enable
b1
b0
Y14
Y13
Y12
Y11
Y10
0: Disable
1: Enable
b3 b2 b1
b0
Yn4
Yn3
Yn2
Yn1
Yn0
0: Disable
1: Enable

Advertisement

Table of Contents
loading