Output On/Off Information Hold Function - Mitsubishi Electric NZ2GF2B1-16D User Manual

Cc-link ie field network remote i/o module
Table of Contents

Advertisement

9.9

Output ON/OFF Information Hold Function

This function checks if the output has been turned once on or off.
(1) Output ON information
Output ON information is stored in Output Y ON information Y (RWr8, RWr9, RWrA).
Whether the output has been turned on or not can be checked with Output Y ON information Y (RWr8, RWr9,
RWrA).
Output Y ON information Y (RWr8, RWr9, RWrA) can be cleared using Output Y ON information clear request
(RWw8, RWw9, RWwA).
For the on and off timing, refer to the following.
• Output Y ON information Y (RWr8, RWr9, RWrA) ( Page 264, Appendix 2 (6))
(2) Output OFF information
Output OFF information is stored in Output Y OFF information Y (RWrC, RWrD, RWrE).
Whether the output has been turned off or not can be checked with Output Y OFF information Y (RWrC, RWrD,
RWrE).
Output Y OFF information Y (RWrC, RWrD, RWrE) can be cleared using Output Y OFF information clear
request (RWwC, RWwD, RWwE).
For the on and off timing, refer to the following.
• Output Y OFF information Y (RWrC, RWrD, RWrE) ( Page 265, Appendix 2 (7))
(3) Applicable module and software package
The output on/off information hold function cannot be used depending on the combination of the I/O module and
software package used. For details, refer to the following.
Module
NZ2GF2B1-16D
NZ2GF2B1-16T
NZ2GF2B1-16TE
NZ2GFCE3-16D
NZ2GFCE3-16DE
NZ2GFCM1-16D
NZ2GFCM1-16DE
NZ2GFCE3-16T
NZ2GFCE3-16TE
NZ2GFCM1-16T
NZ2GFCM1-16TE
NZ2GF2B1N-16D
NZ2GF2B1N-16T
NZ2GF2B1N-16TE
188
Serial number (first five digits)
"15102" or later
"16042" or later
"16111" or later
Version of GX Works2
Version 1.501X or later
Version 1.513K or later
Version 1.501X or later
Version of GX Works3
Version 1.000A or later

Advertisement

Table of Contents
loading

Table of Contents