Mitsubishi Electric NZ2GF2B1-16D User Manual page 201

Cc-link ie field network remote i/o module
Table of Contents

Advertisement

(2) Restrictions
This section describes restrictions to use the CC-Link IE Field Network synchronous communication function.
(a) Restrictions to use this function with other functions
Function name
Input OFF delay function
Fast logic function
Cyclic data update watch function
*1
If any of these function is enabled in the synchronous communication mode, Synchronous communication mode setting
error (error code: 0107H) occurs.
(b) Restrictions on the network parameter settings (RWw/RWr)
Set the network parameters (RWw/RWr) so that RWw13/RWr13 are assigned to use the synchronous
communication function.
(3) Operation using the CC-Link IE Field Network synchronous communication
function
The following figure shows the operation when the CC-Link IE Field Network synchronous communication
function is used.
(a) Operation of an input module
For the main input module or extension input module, input signals are imported in every synchronization cycle
of the master station.
Synchronization cycle of
the master station
External input (Xn terminal)
readout processing
External input signal X
(RX0 to RXF, RX10 to RX1F)
(b) Operation of an output module
For the main output module or extension output module, signals are output in every synchronization cycle of
the master station.
Synchronization cycle of
the master station
External output signal Y
(RY0 to RYF, RY10 to RY1F)
External output Y
(a status of the Yn terminal)
The input OFF delay function cannot be used.
The fast logic function cannot be used.
The setting of Cyclic data update watch time setting (address: 0002H) will be ignored.
Controlled by the I/O module
1)
2)
Readout
Readout
processing
processing
External input
status of 1)
Controlled by the I/O module
1)
2)
Output of 1)
CHAPTER 9 FUNCTIONS
Restrictions
*1
*1
3)
4)
Readout
Readout
processing
processing
External input
External input
status of 2)
status of 3)
3)
4)
Output of 2)
Output of 3)
9
5)
Readout
processing
External input
status of 4)
5)
Output of 4)
199

Advertisement

Table of Contents
loading

Table of Contents