CHAPTER 10 PROGRAMMING
(6) Program example
1.
Create the following program with GX Works2.
10
Input response time setting
(address: 0000H): 1.0ms (2H)
Output HOLD/CLEAR setting
(address: 0001H): CLEAR (0H)
Cyclic data update watch time setting
(address: 0002H): 200ms
Extension module identification code
(address: 0200H): 16 points output
module
Fast logic setting Y11 (0212H, 0213H):
Enable (8000H)
Fast logic setting Y12 (0214H, 0215H):
Enable (8000H)
Write the station-based parameter.
Write the extension module 1
parameter.
Write the extension module 1 fast
logic setting.
The station-based parameter writing
is normally completed.
The extension module 1 parameter
writing is normally completed.
The writing of extension module 1 fast
logic setting is normally completed.
Turn on Operation condition setting
request flag (RWw0.b9).
Turn off Operation condition setting
request flag (RWw0.b9).
Turn on Initial processing completion
flag (RWw0.b8).
Turn off Initial processing completion
flag (RWw0.b8).
229