Mitsubishi Electric NZ2GF2B1-16D User Manual page 97

Cc-link ie field network remote i/o module
Table of Contents

Advertisement

Item
This function performs I/O operations with a
synchronization cycle of the master station
CC-Link IE Field
that supports the CC-Link IE Field Network
Network synchronous
synchronous communication function. This
communication function
enables the I/O module to operate at the
same timing of other slave stations on the
same network.
The output module has the overload
Protection function
protection function and the overheat
protection function.
This function allows the presence or absence
CC-Link IE Field
of a network error to be checked by
Network diagnostic
accessing the engineering tool connected to
function
the CPU module.
This function sets the output timing (ON/OFF
timing) of the output module that operates
Synchronous output
synchronously using CC-Link IE Field
timing setting function
Network synchronous communication
function. The timing is set in increments of
0.1s.
This function acquires the input timing
(ON/OFF timing) of the input module that
Synchronous input
operates synchronously using CC-Link IE
timing acquisition
Field Network synchronous communication
function
function. The timing is acquired in increments
of 0.1s.
*1
In a combination of a main module and an extension module, one must be an input module, and the other must be an
output module.
*2
Available only when the extension module is connected to a main module that supports the CC-Link IE Field Network
synchronous communication function.
*3
Available only when the extension module is connected to a main module that supports the output ON/OFF information
hold function.
*4
The function cannot be used with the NZ2GFCE3-32T.
*5
The function cannot be used with the NZ2GFCE3-32D.
Main
Description
input
module
*5
CHAPTER 4 SPECIFICATIONS
Availability
Main
Main I/O
Extension
output
combined
input
module
module
module
*2
*4
Extension
Reference
Digital
Output
Module
Page 198,
*2
Section
9.13
Page 202,
Section
4
9.14
Page 203,
Section
9.15
Page 206,
Section
9.16
Page 209,
Section
9.17
95