CHAPTER 10
This chapter describes the programming of the I/O module.
10.1

Precautions for Programming

This section describes precautions to create CC-Link IE Field Network programs.
(1) Cyclic transmission program
For a cyclic transmission program, interlock with the following link special relay (SB) and link special register
(SW).
• Own station data link status (master station) (SB0049)
• Data link status (each station) (SW00B0 to SW00B7)
For details on the link special relay (SB) and link special register (SW), refer to the user's manual for the
master/local module used.
Interlock example
Ex.
(2) Transient transmission program
For a transient transmission program, interlock with the following link special relay (SB) and link special register
(SW).
• Own station baton pass status (master station) (SB0047)
• Baton pass status (each station) (SW00A0 to SW00A7)
For details on the link special relay (SB) and link special register (SW), refer to the user's manual for the
master/local module used.
Interlock example
Ex.
Start contact
212
PROGRAMMING
Communication program with station No. 1
Communication program with station No. 2
Dedicated instruction to station No. 1