Cc-Link Ie Field Network Communication Function; Cyclic Transmission - Mitsubishi Electric CC-Link IE Field NZ2GF12A-60IOLH8 User Manual

Network waterproof remote io-link module
Table of Contents

Advertisement

7.6
CC-Link IE Field Network Communication
Function

Cyclic transmission

This function periodically exchanges data among stations on the network using link devices.
An IO-Link module operates as an intelligent device station on the CC-Link IE Field Network.
The status of the master station link devices (RY, RWw) is output to the IO-Link module external devices, and the status of
input from the IO-Link module external devices are stored in the master station link devices (RX, RWr).
The following table lists applications of link devices used for the IO-Link module.
Link device
RX, RY
RWw, RWr
For details on the CC-Link IE Field Network cyclic transmission, refer to the following.
 User's manual for the master/local module used
7 FUNCTIONS
82

7.6 CC-Link IE Field Network Communication Function

Application
Configures the settings such as the input and output values in IO-Link mode and SIO
mode.
Sets the initial processing, reads error codes, reads/writes IO-Link module process
data.
Reference
Page 129 Remote I/O Signals
Page 138 Remote Registers