LCD Display Transducer Block

Table C-4. LCD Display Transducer Block Parameters
Parameter
Index Valid range
ST_REV
1
TAG_DESC
2
STRATEGY
3
ALERT_KEY
4
MODE_BLK
5
BLOCK_ERR
6
UPDATE_EVT
7
BLOCK_ALM
8
TRANSDUCER_
9
DIRCTORY
TRANSDUCER_
10
TYPE
XD_ERROR
11
COLLECTION_
12
DIRECTORY
DISPLAY_
13
PARAM_SEL
BLK_TYPE_1
14
BLK_TAG_1
15
PARAM_INDEX
16
_1
CUSTOM_TAG_
17
1
UNITS_TYPE_1
18
CUSTOM_
19
UNITS_1
BLK_TYPE_2
20
BLK_TAG_2
21
F
Fieldbus Block Information
OUNDATION
Initial value Units Other Description
0-255
spaces
0
1-255
0
O/S
100
Bit 0 – Bit 4
Bit 0 – DP1
See Table 33
0x8001
"TRANSDUCER"
14
spaces
1: Auto
1
2: Custom
3: None
spaces
See Table 33
0
spaces
The revision level of the static data associated with the
function block.
N/A
The user description of the intended application of the
block.
N/A
The strategy field can be used to identify grouping of
blocks.
N/A
The identification number of the plant unit.
N/A
The actual, target, permitted, and normal modes of the
block.
E
Read
This parameter reflects the error status associated with
the hardware or software components associated with a
Only
block. it is a bit string, so that multiple errors may be
shown.
N/A
Read
This alert is generated by any change to the staic data.
Only
N/A
The BLOCK_ALM is used for all configuration, hardware,
connection failure or system problems in the block. The
cause of the alert is entered in the subcode field. The first
alert to become active will set the Active status in the
Status attribute. As soon as the Unreported status is
cleared by the alert reporting task, another block alert
may be reported without clearing the Active status, if the
subcode has changed.
N/A
Read
A directory that specifies the number and starting indicies
of the transducers in the transducer block.
Only
E
Read
Identifies the transducer that follows.
Only
E
Read
Provides additional error codes related to transducer
blocks.
Only
N/A
Read
A directory that specifies the number, starting indicies,
and DD Item ID's of the data collections in each transducer
Only
block.
E
This will determine which Display Parameters are active.
Bit 0 = DP1
Bit 1 = DP2
Bit 2 = DP3
Bit 3 = DP4
Bit 4 = Bar Graph enable
E
The enumerated block type for DP1's block.
N/A
The tag of the block containing DP1.
N/A
The relative index of DP1 within its block. See Table 34
N/A
The block description that is displayed for DP1.
E
This parameter determines where the units for the display
parameter come from.
N/A
This is the user entered units that are displayed when
UNITS_TYPE_1=Custom.
E
The enumerated block type for DP2's block.
N/A
The tag of the block containing DP2.
Reference Manual
00809-0200-4801, Rev DA
211