Table C-5. ADB Parameters
Parameter
Index
PLINE_ON
80
PLINE_
81
RELEARN
PLINE_
82
SENSITIVITY
PLINE_AFFECT
83
_PV_STATUS
PLINE_
84
HISTORY_
STATUS
PLINE_
85
HISTORY_
TIMESTAMP
PLINE_LEARN_
86
LENGTH
PLINE_DETECT
87
_LENGTH
PLINE_AUTO_
88
RELEARN
PLINE_
89
RELEARN_
THRESHOLD
PLINE_
90
1. Insufficient Dynamics Check
LEARNING_
SENSITIVITY
5. 3*Stdev Mean Change Check
6. 6*Stdev Mean Change Check
PLINE_DETECT
91
_SENSITIVITY
PLINE_SINGLE
92
_DETECT_
SENSITIVITY
218
Valid range
0 = FALSE
0xff = TRUE
1. Run
2. Relearn
1. Low
2. Medium
3. High
0 = FALSE
0xff = TRUE
1. Lines Plugged
2. No History
All Times and Dates
1 to 45
1 to 45
0 = Disabled
0xff = Enabled
0 to 50
2. 10% StdevChange Check
3. 20% Stdev Change Check
4. 30% Stdev Change Check
7. 2% Mean Change Check
0 to 100
0 to 10000
F
OUNDATION
Initial value Units Other Description
FALSE
N/A
1
N/A
Medium
N/A
FALSE
N/A
3
N/A
Read
Only
0
Read
Only
5
Min.
1
Min.
Enabled
0.0
%URL
0x55
0.0
%
0.0
%
Fieldbus Block Information
October 2016
Turns algorithm On/Off
Resets the algorithm and reinitiates
learning
Detection Sensitivity
Determines whether the quality of the
pressure measurement will be affected or
unaffected when a plugged impulse line
is detected
Last plugged Line determination status
Timestamp of last plugged impulse line
detection
Length of Learning and Verification
Cycles in Minutes
Length of Detection Cycle Status Update
in Minutes
Enables/Disables Auto Relearn on Process
Mean Changes
Threshold for Relearning in % Primary
Value URL of Sensor
Learning Sensitivity Check Options. Only
one of bits 2, 3 and 4 is allowed and only
one of bits 5 and 6 is allowed.
Overrides IL Plugging Sensitivity if a
non-zero value is entered. Value
corresponds to a percentage decrease in
standard deviation.
Overrides IL Plugging Sensitivity if a
non-zero value is entered. Value
corresponds to a percentage increase in
standard deviation. (Used by DP
transmitters only)