Pressure transmitter with wireless enabled hart solutions (13 pages)
Summary of Contents for Emerson Rosemount 3051S
Page 1
Reference Manual 00809-0100-4804, Rev AA January 2011 Rosemount 3051S Electronic Remote Sensors www.rosemount.com...
Page 3
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Rosemount 3051S Electronic Remote Sensors NOTICE Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table of Contents Using This Manual ........1-1 SECTION 1 Models Covered .
Page 6
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 TOC-2...
Product Recycling/Disposal ..... . . page 1-2 The sections in this manual provide information on installing, operating, and USING THIS MANUAL ™ ® maintaining a Rosemount 3051S ERS System with HART protocol. The sections are organized as follows: •...
To expedite the return process outside of the United States, contact the SERVICE SUPPORT nearest Rosemount representative. Within the United States, call the Emerson Process Management Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
• Use only bolts supplied or sold by Emerson Process Management as spare parts. Improper assembly of manifolds to traditional flange can damage the device: •...
Page 11
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 For dimensional drawing information, refer to Appendix A: Specifications and Mechanical Reference Data on page A-11. For steam service or for applications with process temperatures greater than the limits of each ERS sensor, do not blow down impulse piping through either sensor.
Page 12
As a result, ERS cannot be used in applications with floating electrical grounds greater than 50 Vdc (such as Cathodic Protection). Consult an Emerson Process Management sales representative for additional information or considerations on use in similar applications.
Page 13
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 2-2. 3051S ERS Installation Flowchart START HERE Bench Commissioning Field Installation Identify P Verify ERS Sensors Run “Basic Setup” Wizard Mount Each ERS Device Tagging Review ERS Sensor...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 INSTALLATION PROCEDURES A complete ERS system contains two pressure sensors. One is mounted on Identify ERS Sensors the high-pressure (P ) process connection, and the other is mounted on the low-pressure (P ) process connection.
Page 15
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Mount the P and P sensors at the correct process connections for the Mount Each ERS Sensor application. Common ERS installations are shown in Figure 2-4. Vertical Installation In a vertical installation such as on a vessel or distillation column, the P sensor should be installed at the bottom process connection.
Page 16
Carbon steel bolts do not require lubrication. No additional lubricant should be applied when installing either type of bolt. Bolts supplied by Emerson Process Management are identified by their head markings: Carbon Steel (CS) Head Markings...
Page 17
Rosemount 3051S ERS System January 2011 Bolt Installation Only use bolts supplied with the ERS sensor or sold by Emerson Process Management as spare parts. Use the following bolt installation procedure: Finger-tighten the bolts. Torque the bolts to the initial torque value using a crossing pattern.
Page 18
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 The process connection size on a 3051S ERS Sensor flange is -18 NPT. Process Connections Flange adapters with a -18 NPT to -14 NPT connection are available with the D2 option. Use a plant-approved lubricant or sealant when making the process connections.
Page 19
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Impulse Piping The piping between the process and each ERS sensor must accurately transfer the pressure to obtain accurate measurements. There are many possible sources of error: pressure transfer, leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and plugged impulse lines.
Page 20
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 2-7. Housing Rotation PlantWeb Housing Junction Box Housing Housing Rotation Set Screw (3/32 inch) LCD display Rotation In addition to rotating the housing, the optional LCD display on the primary ERS sensor can be rotated in 90°...
Page 21
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Switch Configuration Procedure To reposition the hardware switches, follow the procedure below: Do not remove the housing covers in explosive atmospheres when the circuit is live. If the ERS system is live, set the loop to manual and remove power.
Page 22
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 ERS System with Optional Remote Display and Interface (Figure 2-10 and Figure 2-11) Remove the housing cover labeled “Field Terminals” on both ERS sensors and the remote housing. Using the ERS Madison Cable (if ordered) or an equivalent 4-wire...
Page 23
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Optional Transient Protection Terminal Block The transient protection terminal block can be ordered as an installed option (Option Code T1) or as a spare part to retrofit an existing 3051S ERS System in the field.
Page 24
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 2-9. Wiring Diagram for Typical ERS System 2-16...
Page 25
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 2-10. Wiring Diagram for ERS System with Remote Display in “Tree” Configuration 2-17...
Page 26
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 2-11. Wiring Diagram for ERS System with Remote Display in “Daisy-Chain” Configuration 2-18...
Page 27
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Grounding Loop Wiring Grounding Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment. Ground the shield of the signal wiring at any one point on the signal loop.
Page 28
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Shield Grounding Connect the shield from the Madison Cable assembly to each housing case for the applicable wiring configuration as shown in Figure 2-13. Figure 2-13. Shield Grounding Cable Shield...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Transmitter Case Always ground the transmitter case in accordance with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance (< 1 ohm).
Page 30
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 2-16. Rosemount 306 In-Line Manifold 306 IN-LINE To install a 305 Integral Manifold to a 3051S ERS sensor: Rosemount 305 Manifold Installation Procedure Inspect the PTFE sensor module o-rings. If the o-rings are undamaged, reusing them is recommended.
Page 31
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 To install a 306 In-Line Manifold to a 3051S ERS sensor: Rosemount 306 Manifold Installation Procedure Place the 3051S ERS sensor into holding fixture. Apply appropriate thread paste or tape to the threaded instrument end of the manifold.
Page 32
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Two-Valve Manifold The two-valve configuration is available on the Rosemount 304, 305, and 306 Manifolds for use with gage and absolute pressure transmitters. A block valve provides instrument isolation, and a drain/vent valve allows for venting, draining, or calibration.
• Use only bolts supplied or sold by Emerson Process Management as spare parts. Improper assembly of manifolds to traditional flange can damage the device: •...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 It is recommended that the following items are verified and configured to BASIC SETUP ensure the proper functionality of the ERS system. Device Tagging 2, 1, 1, 1 Fast Keys An 8 character free-form text field that can be used to uniquely identify the device.
Page 36
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Select which ERS parameters to assign to each HART variable. Variable Mapping 2, 1, 1, 3 Fast Keys Primary Variable The parameter assigned to the HART Primary Variable controls the 4-20 mA Analog Output.
Page 37
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 3-1. Zero and Span Buttons Zero Span The 3051S ERS system automatically and continuously performs Alarm and Saturation self-diagnostic routines. If a self-diagnostic routine detects a failure, the ERS...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 The following items are considered optional and may be configured as ADDITIONAL needed. Refer to Appendix B: for the full Field Communicator menu tree. CONFIGURATION A local display is available as an orderable option on the ERS Primary Local Display Transmitter.
Page 39
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Burst Variable Slot Definition If either “Device vars w/ status” or “Device Variables” is selected as the Burst Option, you will need to configure which variables are communicated in Burst Mode.
Page 40
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Enabling Multidrop Configuration To configure an ERS system to be part of a multidrop network: 1. Assign a unique address to the ERS system. For a HART 5 system, the valid address range is 1-15.
Page 41
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 3-3. Scaled Variable - Level Example Scaled Variable Configuration 1. Scaled Units FEET METER 2. DP (Minimum DP) 0 (in. H 0 (mmH 3. Scaled (Level at Min. DP) 1.5 (feet)
Page 42
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 NOTE: The values entered for each successive DP and Scaled Variable pair must be greater than or equal to the previous pair. 5. The ERS system will not be able to calculate mass or volume if the process is below the P pressure tap.
Page 43
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Tank Formula Method The tank formula method for configuring Scaled Variable can be used if the ERS system is installed on one of the types of tanks shown in Figure 3-5. The steps for using the Tank Formula method are described below: 1.
Page 44
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Strapping Table Method Scaled Variable can also be configured by inputting a traditional “level vs. volume” strapping table. The steps for using the Strapping Table method are described below: 1.
Page 45
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 3-6. Example of How to Change the P and P Module Assignments Sensor Serial Number 11223344 DP = P Sensor Serial Number 44332211 Process alerts allow for the configuration of the ERS system to output a HART...
Page 46
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Disabling Process Alerts 1. Select a parameter for which the process alert will be disabled. 2. Set the Alert Mode to “disabled.” 3-14...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Section 4 Operation and Maintenance Overview ........page 4-1 Safety Messages .
Page 48
• Use only bolts supplied or sold by Emerson Process Management as spare parts. Improper assembly of manifolds to traditional flange can damage the device: •...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 CALIBRATION Calibrating a 3051S ERS System involves the following tasks: Calibration Overview 1. Configure process variables See “Basic Setup” on page 3-3 for additional details: • Units of measure •...
Page 50
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 1. Vent the P sensor to atmosphere. 2. Wait for the P pressure measurement to stabilize. 3. Using AMS or a field communicator, perform the zero trim function on the sensor.
Page 51
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 The DP calibration function can be used to adjust the calculated DP DP Calibration measurement of the ERS system. For example, a DP zero trim can be 3, 4, 2, 1...
Page 52
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 To perform a two-point DP trim, follow the procedure below: 1. Launch the “Lower DP Trim” function using AMS or a Field Communicator. 2. Physically apply the desired low DP value to the entire ERS system. This may require the use of two separate reference pressure devices.
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 The Loop Test command verifies the output of the 3051S ERS system, the FUNCTIONAL TESTS integrity of the 4-20 mA loop, and the operations of any recorders or similar...
• Whenever the process flange or flange adapters are removed, visually inspect the PTFE o-rings. Emerson Process Management recommends reusing o-rings if possible. If the o-rings show any signs of damage, such as nicks or cuts, they should be replaced.
Page 55
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 4-2. Terminal Blocks 3051S ERS Primary 3051S ERS Secondary PWR/ COMM TEST WIRE TO SECONDARY WIRE TO ERS PRIMARY To remove the electronics featureboard from a 3051S ERS Primary device:...
Page 56
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure 4-4. Location of Housing Rotation Set Screw PlantWeb Housing Junction Box Housing Housing Rotation Set Screw (3/32 in.) Attaching the IMPORTANT The V-Seal must be installed at the bottom of the housing.
Page 57
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 3051S ERS Secondary (Junction Box) 1. Apply a light coat of low temperature silicon grease to the SuperModule connector. 2. Insert the SuperModule connector into the top of the SuperModule.
Page 58
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table 4-1. Bolt Installation Torque Values Bolt Material Initial Torque Value Final Torque Value CS-ASTM-A445 Standard 300 in-lb. (34 N-m) 650 in-lb. (73 N-m) 316 SST - Option L4 150 in-lb.
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Section 5 Troubleshooting Overview ........page 5-1 Device Overview .
Page 60
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table 5-1. Diagnostic Message Troubleshooting LCD display Message Host Diagnostic Message Possible Problems Recommended Actions CURR mA Output Saturated The primary variable has exceeded the Verify the process conditions and modify the range points defined for the 4-20 mA Analog Range Values if necessary.
Page 61
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 LCD display Message Host Diagnostic Message Possible Problems Recommended Actions SNSR No P Module Neither of the modules in the ERS Verify that both sensors are connected and CONFIG...
Page 62
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table 5-2. 3051S ERS System Troubleshooting Symptom Corrective Actions The mA output of the 3051S ERS System is • Verify power is applied to “+” and “-” PWR / COMM terminals on the ERS primary unit zero •...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 The 3051S ERS System is compliant with the HART Revision 6 Standard. MEASUREMENT One of the most noticeable enhancements available with the HART 6 QUALITY STATUS standard is that each variable has a measurement quality status. These statuses can be viewed in AMS, with a Field Communicator, or with any HART 6 compatible host system.
Page 64
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Appendix A Specifications and Reference Data Performance Specifications ..... . . page A-1 Functional Specifications .
Page 66
1-year limited warranty (1) Warranty details can be found in Emerson Process Management Terms & Conditions of Sale, Document 63445, Rev G (10/06). (2) Rosemount Ultra sensors in an ERS configuration have a limited warranty of twelve (12) years from date of shipment. All other provisions of Emerson Process Management standard limited warranty remain the same.
Page 67
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Dynamic Performance • Total Time Response at 75 °F (24 °C), Includes Dead Time: 360 ms • Dead Time (nominal): 220 ms • Update Rate: 11 updates per second (1) Consult Instrument Toolkit for 3051S ERS configurations that include remote seals.
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Vibration Effect Less than ±0.1% of URL when tested per the requirements of IEC60770-1 field or pipeline with high vibration level (10-60 Hz 0.21 mm displacement peak amplitude / 60-2000 Hz 3g).
Page 69
DP Span Considerations It is recommended that the DP rangedown (Operating Pressure / DP Span) not exceed 100:1. Consult with your Emerson Process Management sales representative or Instrument Toolkit when considering a 3051S ERS System for use on applications beyond 100:1 rangedown.
Page 70
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Power Supply External power supply required (16 – 42.4 Vdc with no load) Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply: •...
Page 71
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Storage • -50 to 185 °F (-46 to 85 °C) • With LCD display: -40 to 185 °F (-40 to 85 °C) At 70 °F (21 °C) ambient temperature and atmospheric pressure or above...
Page 72
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure A-1. Thermal Optimizer with Silicone 704 Fill Fluid Temperature Limits Humidity Limits 0-100% relative humidity Turn-On Time The 3051S ERS System will be within specifications within six seconds from when power is applied to the system.
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 PHYSICAL SPECIFICATIONS -14 NPT, G , and M20 x 1.5 conduit. HART interface connections fixed to Electrical Connections terminal block of ERS Primary Unit. Process Connections Coplanar Gage / Absolute Sensor (3051SAM_ _G, 3051SAL _ _A)
Page 74
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Drain / Vent Valves 316 SST, Alloy C-276, or Alloy 400/K-500 material (drain / vent seat: Alloy 400, drain / vent stem: Alloy K-500) Process Flanges and Adapters •...
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 DIMENSIONAL DRAWINGS Figure A-2. 3051S ERS Coplanar Sensor and Flange PlantWeb Housing Junction Box Housing Front View Front View 4.20 (107) 4.20 (107) 8.53 8.53 (217) (217) 9.63 9.63...
Page 76
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure A-3. 3051S ERS Coplanar Sensor with Traditional Flange PlantWeb Housing Junction Box Housing Front View Front View 9.26 9.26 (235) (235) 1.10 1.10 3.40 3.40 (86) (28) (86)
Page 77
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure A-4. 3051S ERS In-Line Sensor PlantWeb Housing Junction Box Housing Front View Front View 4.20 (107) 4.20 (107) 8.22 8.22 (209) (209) Side View Side View 5.21 (132) 4.55 (116)
Page 78
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure A-5. Coplanar Mounting Configurations (B4 Bracket) Pipe Mount Panel Mount Front View Front View Front View 4.55 (116) 2.58 (66) 6.15 (156) 2.81 (71) 4.70 (120) 3.54 (90) 6.25 (159)
Page 79
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Figure A-7. In-Line Mounting Configurations (B4 Bracket) Pipe Mount Panel Mount Front View Side View 2.58 4.55 (116) (66) 6.15 2.81 (156) 6.15 (71) 6.25 3.08 (159) (78) 4.72 (120) 6.90 (175)
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 ORDERING INFORMATION Rosemount 3051SAM Transmitter for ERS Applications • Coplanar and In-Line sensor module platforms • Variety of process connections including threaded NPT, flanges, manifolds, and 1199 remote seals •...
Page 82
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table A-5. 3051SAM Scalable Advanced Measurement Transmitter for ERS Applications Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
Page 83
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table A-5. 3051SAM Scalable Advanced Measurement Transmitter for ERS Applications Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
Page 84
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table A-5. 3051SAM Scalable Advanced Measurement Transmitter for ERS Applications Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
Page 85
(4) Tantalum diaphragm material is only available with Pressure Sensor / Module code G. (5) “Assemble to” items are specified separately and require a completed model number. (6) Consult an Emerson Process Management representative for performance specifications. (7) Not available with Configuration Type code S.
Page 86
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Rosemount 3051SAL Level Transmitter for ERS Applications • Integrated transmitter and remote seal in a single model number • Variety of process connections including flanged, threaded, and hygienic remote seals •...
Page 87
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table A-6. 3051SAL Scalable Advanced Level Transmitter for ERS Applications Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
Page 88
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Continue specifying a completed model number by choosing a remote seal type below: page A-26 FF Flush Flanged Seal Process Connections: 2 in. / DN 50 3 in. / DN 80 4 in.
Page 89
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 FM Intrinsically Safe, Division 2 ★ ★ FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★ CSA Explosion-proof, Dust Ignition-proof, Division 2 CSA Intrinsically Safe ★ CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★...
Page 90
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 DIRECT MOUNT SEALS FOR 3051SAL ORDERING INFORMATION Flush Flanged (FF) Seal • Most common seal • Good for use in general applications • Easy installation on flanged connections ranging from 2-in. (DN 50) to 4-in. (DN 100) Table A-7.
Page 91
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table A-7. Flush Flanged (FF) Seal Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 92
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Extended Flanged (EF) Seal • Good for use in viscous applications with plugging issues • Seal diaphragm installed flush with inner tank wall to prevent process plugging • Easy installation on 3-in. (DN 80) and 4-in. (DN 100) flanged connections Table A-8.
Page 93
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Remote Flanged (RF) Seal • Designed to improve performance on smaller process connections • Easy installation on flanged connections ranging from 1-in. to 1.5-in. (DN 50 – DN 40) •...
Page 94
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table A-9. Remote Flanged (RF) Seal Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 95
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Remote Threaded (RT) Seal • For use with threaded process connections ( -18 to 1-11.5 NPT) • Rated for use in high-pressure applications (up to 2500 PSI) • Optional flushing connections available Table A-10.
Page 96
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table A-10. RT Threaded Seal Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 97
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Hygienic Tri-Clamp (SC) Seal • Good for use in hygienic applications • Easy installation on Tri-Clover style Tri-Clamp connections (1.5-in. to 3-in.) • Conforms to 3-A standard 74-03 Table A-11. SC Hygienic Tri-Clover Style Tri-Clamp Seal Ordering Information ★...
Page 98
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Hygienic Tank Spud (SS) Seal • Commonly used in hygienic level applications • Seal diaphragm installed flush with inner tank wall • Conforms to 3-A standard 74-03 Table A-12. SS Hygienic Tank Spud Seal Ordering Information ★...
Page 99
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Rosemount 300 ERS Transmitter Housing Kit • Housing kit for Rosemount 3051SAM and 3051SAL ERS transmitters • Upgrade an existing 3051S transmitter to an ERS configuration Table A-13. Rosemount 300 ERS Transmitter Housing Kit Ordering Information ★...
Page 100
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Table A-13. Rosemount 300 ERS Transmitter Housing Kit Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 SPARE PARTS Sensor Modules See Rosemount 3051S_T, and 3051SAL Liquid Level ordering tables in the 3051S Product Data Sheet (00813-0100-4801) for ordering spare 3051S sensor modules. Use housing code style 00 in the model number.
Page 102
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Cast C-276 Adapters 03031-1300-0013 Cast Alloy 400 Adapters 03031-1300-0014 Ni Plated CS Adapters 03031-1300-0015 CS Bolts, Graphite PTFE O-Rings SST Adapters 03031-1300-0102 Cast C-276 Adapters 03031-1300-0103 Cast Alloy 400 Adapters...
Page 103
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Coplanar Flange/Adapter Bolt Kit {73 mm (2.88 in.)} Carbon Steel (set of 4) 03151-9281-0001 316 SST (set of 4) 03151-9281-0002 ANSI/ASTM-A-193-B7M (set of 4) 03151-9281-0003 Alloy K-500 (set of 4) 03151-9281-0004 Manifold/Coplanar Flange Bolt Kit {57 mm (2.25 in.)}...
Page 104
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 A-40...
Page 105
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Appendix B HART Menu Tree Home 1 Overview Overview 2 Configure 1 Device Status 3 Service Tools 2 Communications Communications Variable Mapping 3 Device Information 1 Variable Mapping 4 Analog Output...
Page 106
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Home 1 Overview Configure 2 Configure 1 Guided Setup Guided Setup 3 Service Tools Basic Setup 1 Basic Setup 2 Manual Setup Device Tagging 1 Device Tagging 3 Alert Setup...
Page 107
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 Home 1 Overview 2 Configure Configure 3 Service Tools 1 Guided Setup 2 Manual Setup Manual Setup 3 Alert Setup 1 Process Variables 2 Analog Output 3 Scaled Variable...
Page 108
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011...
CERTIFICATION FOR FM testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA). European Directive Consult your Emerson Process Management sales representative for more information about the EC declaration of conformity. Information Hazardous Locations North American Certifications...
Page 110
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 ATEX Dust Certificate No.: BAS01ATEX1374X II 1 D Ex tD A20 IP66 T105 °C (-20 °C T 85 °C) = 42.4 V max IP66 1180 Special Conditions for safe use (X): Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
Page 111
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011 IECEx Flameproof and Dust (each listed separately) IECEx Flameproof Certificate No.: IECExKEM08.0010X Ex d IIC T6 (-50 °C T 65 °C) Ex d IIC T5 (-50 °C T ...
Page 112
Reference Manual 00809-0100-4804, Rev AA Rosemount 3051S ERS System January 2011...
Page 114
PlantWeb is a mark of one of the Emerson Process Management companies. HART is a registered trademark of the HART Communications Foundation. ASP Diagnostics Suite is a trademark of one of the Emerson Process Management companies. Syltherm and D.C. are registered trademarks of Dow Corning Co.