Specifications and Reference Data
October 2016
A.1.3 Transmitter total performance
Total performance is based on combined errors of reference accuracy, ambient temperature effect, and line pressure effect.
Models
Rosemount
Ranges 2-3
3051S_CD
Rosemount
Ranges 2-5
3051S_CG
Rosemount
Ranges 2-4
3051S_CA
Rosemount
Ranges 2-4
3051S_T
Rosemount
DP Ranges 2-3
(2)
3051SMV
Rosemount
3051SAL
1.
Ultra for Flow is only available for Rosemount 3051S_CD Ranges 2-3 and Rosemount 3051SMV DP Ranges 2-3.
2.
For Rosemount 3051SMV, Transmitter Total Performance specification applies to differential pressure measurement only.
A.1.4 Multivariable flow performance
Mass, Energy, Actual Volumetric, and Totalized Flow Reference Accuracy
Models
(3)
Rosemount 3051SMV
DP Ranges 2-3 ±0.65% of Flow Rate over a 14:1 flow range
DP Range 1 Not available
Annubar Flowmeter (Rosemount 3051SFA)
Ranges 2-3 ±0.85% of flow rate at 8:1 flow turndown
Compact Conditioning Orifice Flowmeter (Rosemount 3051SFC_C)
Ranges 2-3
 = 0.4 ±0.60% of flow rate at 8:1 flow turndown
 = 0.65 ±1.05% of flow rate at 8:1 flow turndown
Compact Orifice Flowmeter
Ranges 2-3
 = 0.4 ±1.30% of flow rate at 8:1 flow turndown
 = 0.65 ±1.30% of flow rate at 8:1 flow turndown
Integral Orifice Flowmeter (Rosemount 3051SFP)
Ranges 2-3
 < 0.1 ±2.55% of flow rate at 8:1 flow turndown
0.1 <  < 0.2 ±1.35% of flow rate at 8:1 flow turndown
0.2 <  < 0.6 ±0.85% of flow rate at 8:1 flow turndown
0.6 <  < 0.8 ±1.55% of flow rate at 8:1 flow turndown
1.
Flow performance specifications assume device is configured for full compensation of static pressure, process temperature, density, viscosity, gas expansion, discharge
coefficient, and thermal correction variances over a specified operating range.
2.
Energy, actual volumetric, and totalized flow not available with transmitter output code F.
3.
Uncalibrated differential producer (0.2 < beta < 0.6 Orifice) installed per ASME MFC 3M or ISO 5167-1. Uncertainties for discharge coefficient, producer bore, tube
diameter, and gas expansion factor as defined in ASME MFC 3M or ISO 5167-1. Reference accuracy does not include RTD sensor accuracy.
4.
For smaller line sizes, see the Rosemount DP Flowmeter
Specifications and Reference Data
Ultra
±0.1% of span; for ±50°F (28°C)
temperature changes; 0-100%
relative humidity, up to 740 psi
(51 bar) line pressure (DP only),
from 1:1 to 5:1 rangedown
Use Instrument Toolkit
under operating conditions.
(1)
Ultra for Flow
(200:1 DP range)
(4)
(Rosemount 3051SFC_P)
Product Data
Classic and Classic MV
±0.15% of span; for ±50°F (28°C)
temperature changes; 0-100%
relative humidity, up to 740 psi
(51 bar) line pressure (DP only),
from 1:1 to 5:1 rangedown
or the QZ Option to quantify the total performance of a remote seal assembly
(2)
Sheet.
Reference Manual
00809-0200-4801, Rev DA
Ultra for Flow
±0.15% of reading; for ±50°F
(28°C) temperature changes;
0-100% relative humidity, up to
740 psi
(51 bar) line pressure, over 8:1 DP
turndown from URL
Classic MV
±0.70% of Flow Rate over 8:1 flow range
(64:1 DP range)
±0.90% of Flow Rate over 8:1 flow range
(64:1 DP range)
±0.80% of flow rate at 14:1 flow turndown
±0.55% of flow rate at 14:1 flow turndown
±1.00% of flow rate at 14:1 flow turndown
±1.25% of flow rate at 14:1 flow turndown
±1.25% of flow rate at 14:1 flow turndown
±2.50% of flow rate at 14:1 flow turndown
±1.30% of flow rate at 14:1 flow turndown
±0.80% of flow rate at 14:1 flow turndown
±1.50% of flow rate at 14:1 flow turndown
(1)
101