Configuration
October 2016
pressure transmitter. If a function block is scheduled in the Rosemount 3051S that links a process
variable from another device on the segment, that process variable can be shown on the LCD display.
Display Parameter 1
Block Type #1
Block Tag #1
Param Index #1
Custome Tag #1
Units Type #1
Custom Units #1
DISPLAY_PARAM_SEL
The DISPLAY_PARAM_SEL parameter specifies how many process variables will be displayed. Select up to
four display parameters.
BLK_TAG_#
Enter the Block Tag of the function block that contains the parameter to be displayed.
BLK_TYPE_#
Enter the Block Type of the function block that contains the parameter to be displayed. This parameter is
generally selected via a drop-down menu with a list of possible function block types. (e.g. Transducer,
PID, AI, etc.)
PARAM_INDEX_#
The PARAM_INDEX_# parameter is generally selected via a drop-down menu with a list of possible
parameter names based upon what is available in the function block type selected. Choose the
parameter to be displayed.
CUSTOM_TAG_#
The CUSTOM_TAG_# is an optional user-specified tag identifier that can be configured to be displayed
with the parameter in place of the block tag. Enter a tag of up to five characters.
UNITS_TYPE_#
The UNITS_TYPE_# parameter is generally selected via a drop-down menu with three options: AUTO,
CUSTOM, or NONE. Select AUTO only when the parameter to be displayed is pressure, temperature, or
percent. For other parameters, select CUSTOM and be sure to configure the CUSTOM_UNITS_#
parameter. Select NONE if the parameter is to be displayed without associated units.
CUSTOM_UNITS_#
Specify custom units to be displayed with the parameter. Enter up to six characters. To display Custom
Units the UNITS_TYPE_# must be set to CUSTOM.
1,
_# represents the specified parameter number.
42
AI Block
FFAI_RMT3
OUT
Auto
(1)
(1)
(1)
(1)
(1)