Quick Start Guide
00825-0100-4805, Rev FD
March 2018
Rosemount
3051S Series Pressure Transmitter
and Rosemount 3051SF Series Flow Meter
with F
Fieldbus Protocol
OUNDATION

Advertisement

loading

Summary of Contents for Emerson Rosemount 3051S FOUNDATION Series

  • Page 1 Quick Start Guide 00825-0100-4805, Rev FD March 2018 ™ Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flow Meter ™ with F Fieldbus Protocol OUNDATION...
  • Page 2: Table Of Contents

    Refer to the Rosemount 3051S F Fieldbus Reference Manual for more OUNDATION instruction. This document is also available electronically on Emerson.com/Rosemount. Explosions can result in death or serious injury.  Do not remove the transmitter covers in explosive environments when the circuit is live. ...
  • Page 3: Mount The Transmitter

    Quick Start Guide March 2018 Mount the transmitter Liquid flow applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the Flow drain/vent valves are oriented upward. Gas flow applications 1.
  • Page 4 March 2018 Quick Start Guide Figure 1. Panel and Pipe Mounting Panel mount Pipe mount Coplanar flange Traditional flange In-line Housings ™ Plantweb Junction box Remote mount display...
  • Page 5 Use only ™ bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 2 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 6 March 2018 Quick Start Guide Table 1. Torque Values for the Flange and Flange Adaptor Bolts Bolt material Head markings Initial torque Final torque Carbon Steel (CS) 300 in-lb 650 in-lb Stainless Steel 150 in-lb 300 in-lb (SST) O-rings with flange adaptors Failure to install proper flange adaptor O-rings may cause process leaks, which can result in death or serious injury.
  • Page 7: Tagging

    0011513051010001440-121698091725 PD Tag: PD Tag: PT- 101 PT- 101 Revision: 24 Revision: 23 Support files available at Support files available at Emerson.com/Rosemount Emerson.com/Rosemount Tear Here Tear Here Revision: 24 Revision: 23 Support files available at Support files available at Emerson.com/Rosemount Emerson.com/Rosemount...
  • Page 8: Consider Housing Rotation

    Note The device description loaded in the host system must be at the same revision as this device. The device description can be downloaded from Emerson.com/Rosemount Fieldbus.org. Consider housing rotation To improve field access to wiring or to better view the optional LCD display: 1.
  • Page 9 The enclosed pipe plug must be installed in unused conduit opening with a minimum of five thread engagement to comply with explosion-proof requirements. Refer to the Rosemount 3051S Fieldbus Reference Manual for more information. This manual is also available OUNDATION electronically on Emerson.com/Rosemount.
  • Page 10: Verify Configuration

    March 2018 Quick Start Guide Verify configuration Use the following block examples to do basic configuration to the transmitter. For more advanced configurations see the Rosemount 3051S F OUNDATION Fieldbus Reference Manual. Note ™ DeltaV users should use DeltaV Explorer for the resource and transducer blocks and Control Studio for the function blocks.
  • Page 11: To Display Level Or Flow, Use Ai Block Out

    Quick Start Guide March 2018 Pressure example Parameters Enter data Channel L_Type Direct XD_Scale See list of supported engineering units. Out_Scale Set values outside operating range. DP Flow example Parameters Enter data Channel L_Type Square root XD_Scale 0–100 inH O @ 68 °F Out_Scale 0–20 GPM DP Level example...
  • Page 12 March 2018 Quick Start Guide Trim the transmitter Note Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit). Zero trim A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects.
  • Page 13: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Ordinary Location Certification As standard, the transmitter has been examined and tested to determine that...
  • Page 14 March 2018 Quick Start Guide IE FM FISCO Certificate: FM16US0089X Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 2005, NEMA 250 – 2003 Markings: IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ T ≤...
  • Page 15 Quick Start Guide March 2018 Europe E1 ATEX Flameproof Certificate: KEMA 00ATEX2143X Standards: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-26:2015 II 1/2 G Ex d IIC T6…T4 Ga/Gb, T6(–60 °C ≤ T ≤ +70 °C), Markings: T5/T4(–60 °C ≤ T ≤ +80 °C) Temperature class Process temperature –60 °C to +70 °C...
  • Page 16 March 2018 Quick Start Guide 3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area. IA ATEX FISCO Certificate: BAS01ATEX1303X Standards: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012...
  • Page 17 Quick Start Guide March 2018 International E7 IECEx Flameproof and Dust Certificate: IECEx KEM 08.0010X (Flameproof) Standards: IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-26:2014 Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ T ≤ +70 °C), T5/T4(–60 °C ≤ T ≤...
  • Page 18 March 2018 Quick Start Guide Model 33 μH 3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 3051SAL…M7, M8, or M9 93 μH 30 V 300 mA 1.0 W 12 nF 3051SAM…M7, M8, or M9 RTD Option for 3051SF 500 mA 0.63 W Special Conditions for Safe Use (X):...
  • Page 19 Quick Start Guide March 2018 Parameter FISCO Voltage U 17.5 V Current I 380 mA Power P 5.32 W Capacitance C Inductance L Special Conditions for Safe Use (X): 1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500V test as defined in Clause 6.3.13 of EN 60079-11:2012.
  • Page 20 March 2018 Quick Start Guide Brazil E2 INMETRO Flameproof Certificate: UL-BR15.0393X Standards: ABNT NBR IEC 60079-0:2008 + Corrigendum 1:2011, ABNT NBR IEC 60079-1:2009 + Corrigendum 1:2011, ABNT NBR IEC 60079-26:2008 + Corrigendum 1:2008 Markings: Ex d IIC T* Ga/Gb, T6(–60 °C ≤ T ≤...
  • Page 21 Quick Start Guide March 2018 Standards: 3051S: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2013, GB12476.5-2013 3051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2013, GB 12476.5-2013 Markings: 3051S: Ex d IIC T6…T4; Ex tD A20 T 105 °C T 95 °C; IP66 3051SFx: Ex d IIC T5/T6 Ga/Gb; DIP A20 T 105 °C;...
  • Page 22 March 2018 Quick Start Guide I3 China Intrinsic Safety Certificate: 3051S: GYJ16.1250X [Mfg USA, China, Singapore] 3051SFx: GYJ11.1707X [Mfg USA, China, Singapore] 3051S-ERS: GYJ16.1248X [Mfg USA, China, Singapore] Standards: 3051S: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 3051SFx: GB3836.1/4-2010, GB3836.20-2010, GB12476.1-2013, GB12476.5-2013 3051S-ERS: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 Markings: 3051S, 3051SFx: Ex ia IIC T4 Ga 3051S-ERS: Ex ia IIC T4...
  • Page 23 Quick Start Guide March 2018 GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)” GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”...
  • Page 24 March 2018 Quick Start Guide 7.13 Combinations K1 Combination of E1, I1, N1, and ND K2 Combination of E2 and I2 K5 Combination of E5 and I5 K6 Combination of E6 and I6 K7 Combination of E7, I7, and N7 KA Combination of E1, I1, E6, and I6 KB Combination of E5, I5, E6, and I6 KC Combination of E1, I1, E5, and I5...
  • Page 25 Quick Start Guide March 2018 Figure 7. Rosemount 3051S Declaration of Conformity EU Declaration of Conformity No: RMD 1044 Rev. AA Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 declare under our sole responsibility that the product, Rosemount 3051S Series Pressure Transmitters Rosmeount 3051SFx Series Flowmeter Transmitters Rosemount 300S Housings manufactured by,...
  • Page 26 March 2018 Quick Start Guide EU Declaration of Conformity No: RMD 1044 Rev. AA EMC Directive (2014/30/EU) Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013 PED Directive (2014/68/EU) Rosemount 3051S Series Pressure Transmitters Rosemount 3051S_CA4; 3051S_CD2, 3, 4, 5 (also with P0 & P9 option) Pressure Transmitters QS Certificate of Assessment –...
  • Page 27 Quick Start Guide March 2018 EU Declaration of Conformity No: RMD 1044 Rev. AA ATEX Directive (2014/34/EU) BAS01ATEX1303X – Intrinsic Safety Certificate Equipment Group II, Category 1 G Ex ia IIC T4 Ga Harmonized Standards Used: EN 60079-0:2012+A11:2013, EN 60079-11:2012 BAS01ATEX3304X –...
  • Page 28 March 2018 Quick Start Guide EU Declaration of Conformity No: RMD 1044 Rev. AA PED Notified Body Rsoemount 3051S Series Pressure Transmitters DNV GL AS [Notified Body Number: 0575] Veritasveien 1, N-1322 Hovik, Norway ATEX Notified Bodies for EU Type Examination Certificate DEKRA Certification B.V.
  • Page 29 Quick Start Guide March 2018 Rosemount 3051S China RoHS List of Rosemount 3051S Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6) (PBB) (PBDE) Electronics...
  • Page 30 March 2018 Quick Start Guide...
  • Page 31 Quick Start Guide March 2018...
  • Page 32 Dubai, United Arab Emirates Electric Co. +971 4 8118100 Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners. +971 4 8865465 © 2018 Emerson. All rights reserved.