A.1.11 Mounting position effects
Models
Rosemount 3051S_CD or CG
Rosemount 3051SMV_ _ 3 or 4
Rosemount 3051SF_3, 4, 7, or D
Rosemount 3051S_CA
Rosemount 3051S_T
DP Sensor: Zero shifts up to ±1.25 inH
Rosemount
3051SMV_ _ 1 or 2
Rosemount
3051SF_1, 2, 5, or 6
Sensor:
Rosemount 3051SAL
A.1.12 Vibration effect
Less than ±0.1% of URL when tested per the requirements of
IEC60770-1 field or pipeline with high vibration level (10-60 Hz
0.21mm displacement peak amplitude / 60-2000 Hz 3g).
For Housing Style codes 1J, 1K, 1L, 2J, and 2M:
Less than ±0.1% of URL when tested per the requirements of
IEC60770-1 field with general application or pipeline with low
vibration level (10-60 Hz 0.15mm displacement peak amplitude/
60-500 Hz 2g).
A.1.13 Electromagnetic Compatibility (EMC)
Meets all industrial environment requirements of EN61326 and
NAMUR NE-21. Maximum deviation < 1% Span during EMC
(1)(2)
disturbance.
1.
During surge event device may exceed maximum EMC deviation limit or
reset; however, device will self-recover and return to normal operation
within specified start-up time.
2.
Rosemount 3051SMV and 3051SF_1, 3, 5, 7 require shielded cable for the
process temperature connection.
A.1.14 Transient protection (Option T1)
Meets IEEE C62.41.2-2002, Location Category B
6 kV crest (0.5 s - 100 kHz)
3 kA crest (8 × 20 microseconds)
6 kV crest (1.2 × 50 microseconds)
Meets IEEE C37.90.1-2002 Surge Withstand Capability
SWC 2.5 kV crest, 1.0 MHz wave form
106
Ultra, Ultra for Flow, Classic, and Classic MV
Zero shifts up to ±1.25 inH
Span: no effect
Zero shifts to ±2.5 inH
Span: no effect
Span: no effect
GP/AP
Zero shifts to ±2.5 inH
Span: no effect
With liquid level diaphragm in vertical plane, zero shift of up to ±1 inH
diaphragm in vertical plane, zero shift of up to ±5 inH
extended units. All zero shifts can be zeroed.
Span: no effect.
O (3,11 mbar), which can be zeroed
2
O (6,22 mbar), which can be zeroed
2
O (3,11 mbar), which can be zeroed
2
O (6,22 mbar), which can be zeroed
2
Specifications and Reference Data
O (2,5 mbar). With
2
O (12,5 mbar) plus extension length on
2
Specifications and Reference Data
October 2016