Emerson Rosemount 3051S Series Reference Manual

Emerson Rosemount 3051S Series Reference Manual

Pressure transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051S Series:
Table of Contents

Advertisement

Quick Links

Reference Manual
00809-0200-4801, Rev DA
October 2016
Rosemount
3051S Series Pressure Transmitter
with F
Fieldbus Protocol
OUNDATION

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 3051S Series

  • Page 1 Reference Manual 00809-0200-4801, Rev DA October 2016 ™ Rosemount 3051S Series Pressure Transmitter ™ with F Fieldbus Protocol OUNDATION...
  • Page 3: Table Of Contents

    Reference Manual Contents 00809-0200-4801, Rev DA October 2016 1Section 1: Introduction Overview ............... . . 1 Using this manual .
  • Page 4 Reference Manual Contents 00809-0200-4801, Rev DA October 2016 3Section 3: Configuration Overview ............... . 25 Safety messages.
  • Page 5 Reference Manual Contents 00809-0200-4801, Rev DA October 2016 4Section 4: Operation and Maintenance Overview ............... . 51 Safety messages.
  • Page 6 Reference Manual Contents 00809-0200-4801, Rev DA October 2016 6.3.6 PlantWeb alert ............. 77 6.3.7 Trending statistical values in control system.
  • Page 7 Reference Manual Contents 00809-0200-4801, Rev DA October 2016 A.2.2 Minimum span limits ............108 A.2.3 Overpressure limits .
  • Page 8 Reference Manual Contents 00809-0200-4801, Rev DA October 2016 B.15.1 Factory Mutual (FM) ............167 B.15.2 Canadian Standards Association (CSA) .
  • Page 9 Customer Central Technical support, quoting, and order-related questions. 1-800-999-9307 (7:00 am to 7:00 pm CST) North American Response Center Equipment service needs. 1-800-654-7768 (24 hours—includes Canada) Outside of the United States, contact your local Emerson representative. Title Page...
  • Page 10 Do not attempt to loosen or remove flange bolts while the transmitter is in service.  Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
  • Page 11: Overview

    , see Rosemount Reference Manual. Using this manual The sections in this manual provide information on configuring, troubleshooting, operating and maintaining Rosemount 3051S Series Pressure Transmitters specifically for F Fieldbus OUNDATION Protocol. The sections in this manual are organized as follows:...
  • Page 12 Reference Manual Introduction 00809-0200-4801, Rev DA October 2016 Introduction...
  • Page 13: Overview

    Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Section 2 Installation Overview ..............page 3 Safety messages .
  • Page 14: Considerations

    Use only bolts supplied or sold by Emerson as spare parts.  ™ Improper assembly of manifolds to traditional flange can damage SuperModule Platform.
  • Page 15: General

    Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Figure 2-1. Commissioning Tag COMMISSIONING LABEL DEVICE ID: 00115113051032003161928-030016245 PD TAG: 007138842 REVISION: 23.3 REVISION: 23.3 S/N UNIT #: 0071358842 DEVICE ID: 00115113051032003161928-030016245 PD TAG: 007138842 A. Device ID B. Device tag to denote physical location Transmitter tag If permanent tag is ordered: Transmitter is tagged in accordance with customer requirements...
  • Page 16: Draft Range

    Reference Manual Installation 00809-0200-4801, Rev DA October 2016 2.3.5 Draft range Installation For the Rosemount 3051S_CD0 Draft Range Pressure Transmitter, it is best to mount the transmitter with the isolators parallel to the ground. Installing the transmitter in this way reduces oil mounting effect and provides for optimal temperature performance.
  • Page 17: Mount The Transmitter

    Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Cover installation Always ensure a proper seal by installing the electronics housing cover(s) so that metal contacts metal. Use Rosemount O-rings. Cover jam screw For transmitter housings shipped with a cover jam screw, as shown in Figure 2-2, the screw should be properly installed once the transmitter has been wired and powered up.
  • Page 18 Alloy 400 Head Marking Bolt installation Only use bolts supplied with the Rosemount 3051S or sold by Emerson as spare parts. When installing the transmitter to one of the optional mounting brackets, torque the bolts to 125 in-lb. (0,9 N-m). Use the following bolt installation procedure: 1.
  • Page 19 Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Figure 2-3. Transmitter Bolts and Vents Differential transmitter Gage/absolute transmitter 1.50 (38) x 2 1.75 (44) x 4 1.50 (38) x 4 1.75 (44) x 4 Transmitter with flange adapters Transmitter with flange bolts and flange/ adapter bolts 1.75 (44) x 4 2.88 (73) x 4...
  • Page 20 Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Table 2-2. Bolt Specifications Description Size (in. [mm]) Differential Pressure Flange bolts 1.75 (44) Adapter bolts 1.50 (38) Flange/adapter bolts 2.88 (73) Gage/Absolute Pressure Flange bolts 1.75 (44) Adapter bolts 1.50 (38) Flange/adapter bolts 2.88(73) DIN-compliant traditional flange requires 1.75 in.
  • Page 21 Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Liquid flow measurement Place taps to the side of the line to prevent sediment deposits on the process isolators.  Mount the transmitter beside or below the taps so gases vent into the process line. ...
  • Page 22: Process Connections

    Installation Reference Manual 00809-0200-4801, Rev DA October 2016 Figure 2-5. In-Line Installation Examples Gas or liquid service Gas service Liquid or steam service 2.4.2 Process connections Rosemount 3051S Transmitter flange process connection size is –18 NPT. Flange adapters with –14 NPT connections are available as the D2 option.
  • Page 23: Consider Housing Rotation

    Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Failure to install proper flange adapter O-rings can cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring that is designed for its specific flange adapter, as shown below.
  • Page 24: Configure Security

    Installation Reference Manual 00809-0200-4801, Rev DA October 2016 Note If LCD display pins are inadvertently removed from the interface board, carefully re-insert the pins before snapping the LCD display back into place. 2.4.4 Configure security The Rosemount 3051S F Fieldbus Transmitter has a hierarchy of security. The SECURITY switch OUNDATION located on the electronics provides the highest level of security.
  • Page 25: Transmitter Grounding

    Reference Manual Installation 00809-0200-4801, Rev DA October 2016 below. The terminals are not polarity sensitive. The transmitter requires 9-32 Vdc to operate. Type A Fieldbus wiring 18 awg twisted shielded pair is recommended. OUNDATION Note Avoid running instrument cable next to power cables in cable trays or near heavy electrical equipment. It is important that the instrument cable shield be: - trimmed close and insulated from touching the transmitter housing - continuously connected throughout the segment...
  • Page 26: Rotating The Lcd Display

    Installation Reference Manual 00809-0200-4801, Rev DA October 2016 The most effective transmitter case grounding method is a direct connection to earth ground with minimal (< 1 ) impedance.  Note Grounding the transmitter case using the threaded conduit connection may not provide a sufficient ground.
  • Page 27: Zeroing Transmitter

    Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Zeroing transmitter Before operating the transmitter, perform a Zero Trim and set the Damping. Refer to “Calibration” on page 53 for zeroing procedures. 2.7.1 Damping The damping parameter in the Transducer Block may be used to filter measurement noise. By increasing the damping time, the transmitter will have a slower response time, but will decrease the amount of process noise that is translated to the Transducer Block Primary Value.
  • Page 28: Rosemount 306 In-Line Manifold Installation Procedure

    Installation Reference Manual 00809-0200-4801, Rev DA October 2016 Note Always perform a zero trim on the transmitter/manifold assembly after installation to eliminate mounting effects. See “Zero trim method” on page 2.8.2 Rosemount 306 In-line Manifold installation procedure The Rosemount 306 is for use only with a Rosemount 3051S In-line Transmitter. Assemble the Rosemount 306 to the Rosemount 3051S with a thread sealant.
  • Page 29: Rosemount 305 And 304 Manifold Styles

    Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Figure 2-10. Bolt Tightening Pattern 2.8.4 Rosemount 305 and 304 Manifold styles The Rosemount 305 Integral Manifold is available in two styles: coplanar and traditional. The traditional Rosemount 305 can be mounted to most primary elements with mounting adapters. Figure 2-11.
  • Page 30 Reference Manual Installation 00809-0200-4801, Rev DA October 2016 Coplanar transmitters 3-valve and 5-valve manifolds Performing zero trim at static line pressure In normal operation the two isolate (block) valves between the process ports and transmitter will be open and the equalize valve will be closed. Drain/Vent Drain/Vent valve...
  • Page 31 Reference Manual Installation 00809-0200-4801, Rev DA October 2016 5-valve natural gas manifold Performing zero trim at static line pressure 5-valve natural gas configurations shown: In normal operation, the two isolate (block) valves between the process ports and transmitter will be open, and the equalize valves will be closed.
  • Page 32 Reference Manual Installation 00809-0200-4801, Rev DA October 2016 4. After performing a zero trim on the transmitter, close the equalize valve on the low pressure (downstream) side of the transmitter. (Plugged) (Plugged) Equalize Equalize (open) (closed) Isolate Isolate (open) (closed) Process Drain vent Process...
  • Page 33 Reference Manual Installation 00809-0200-4801, Rev DA October 2016 In-line transmitters 2-valve and block and bleed style manifolds Isolating the transmitter In normal operation the isolate (block) valve between the process Transmitter port and transmitter will be open and the test/vent valve will be closed.
  • Page 34 Installation Reference Manual 00809-0200-4801, Rev DA October 2016 4. Open the Isolate (block) valve to return the transmitter to Transmitter service. Vent (closed) Isolate Process (open) Adjusting valve packing Over time, the packing material inside a Rosemount manifold may require adjustment in order to continue to provide proper pressure retention.
  • Page 35: Overview

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Section 3 Configuration Overview ............... . page 25 Safety messages .
  • Page 36: Device Description

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Device description Before configuring the device, ensure the host has the appropriate Device Description file revision for this device. The device descriptor can be found on FieldCommGroup.org. The initial release of the Rosemount 3051S with F Fieldbus Protocol is device revision 20.
  • Page 37: General Block Information

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Block execution times Analog Input = 20 ms PID = 25 ms Arithmetic = 20 ms Input Selection = 20 ms Signal Characterizer = 20 ms Integrator = 20 ms Analog Output = 20 ms Output Splitter = 20 ms Multiple Analog Input = 20 ms Control Selector = 20 ms...
  • Page 38: Block Instantiation

    Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 Other types of modes Other types of modes are Cas, RCas, ROut, IMan and LO. Some of these may be supported by different function blocks in the Rosemount 3051S. For more information, see the F Fieldbus Block OUNDATION Reference...
  • Page 39 Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 FEATURES_SEL is used to turn on any supported features found in the FEATURES parameter. The default setting of the Rosemount 3051S does not select any of these features. Choose one or more of the supported features if any.
  • Page 40: Max_Notify

    Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 3.6.2 MAX_NOTIFY The MAX_NOTIFY parameter value is the maximum number of alert reports the resource can have sent without getting a confirmation, corresponding to the amount of buffer space available for alert messages.
  • Page 41 Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 FAILED_ALM Alarm indicating a failure within a device which makes the device non-operational. MAINT_ALARMS A maintenance alarm indicates the device or some part of the device needs maintenance soon. If the condition is ignored, the device will eventually fail. There are five parameters associated with MAINT_ALARMS, they are described below.
  • Page 42: Analog Input (Ai) Function Block

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 4. Defer NV Memory Write Detected 5. Mass Flow Transducer Block Reverse Flow 6. Mass Flow Transducer Block Sensor Out of Range 7. Mass Flow Transducer Block Out of Range 8. Process Anomaly Detected (SPM) ADVISE_MASK The ADVISE_MASK parameter will mask any of the failed conditions listed in ADVISE_ENABLED.
  • Page 43 Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Table 3-1. I/O Channel Definitions Channel number Channel description differential pressure in AI.XD_SCALE units sensor temperature in AI.XD_SCALE units mean differential pressure absolute pressure (AO.OUT) process temperature (AO.OUT) mass flow absolute pressure (AO.CAS_IN shadow) process temperature (AO.CAS_IN shadow) All MAI channels (12-19 below) SPM1 mean (ADB)
  • Page 44: Configuration Examples

    Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 L_TYPE is direct When the desired output is the measured variable, set the XD_SCALE to the Primary_Value_Range. This is found in the Sensor Transducer Block. Set OUT_SCALE to match XD_SCALE. L_TYPE is indirect When an inferred measurement is made based on the sensor measurement, set the XD_SCALE to represent the operating range that the sensor will see in the process.
  • Page 45 Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Solution Table 3-2 lists the appropriate Analog Input function block configuration for a typical pressure transmitter. Table 3-2. Configuration Values Parameter Configured values L_TYPE Direct XD_SCALE Primary_Value_Range OUT_SCALE Primary_Value_Range Channel 1 - pressure Pressure transmitter used to measure level in an open tank Situation #2 The level of an open tank is to be measured using a pressure tap at the bottom of the tank.
  • Page 46 Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 Output calculation for Situation #2 When the L_Type is configured as Indirect, the OUT parameter is calculated as: OUT = PV – XD_SCALE_0%* (OUT_SCALE_100% – OUT_SCALE_0%) + OUT_SCALE_0% XD_SCALE_100% – XD_SCALE_0% In this example, when PV is 5 psi, then the OUT parameter will be calculated as follows: OUT = 5 psi –...
  • Page 47: Differential Pressure Transmitter To Measure Flow

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 3.7.3 Differential pressure transmitter to measure flow Situation #4 The liquid flow in a line is to be measured using the differential pressure across an orifice plate in the line. Based on the orifice specification sheet, the differential pressure transmitter was calibrated for 0 to 20 0 for a flow of 0 to 800 gal/min.
  • Page 48: Low Cutoff

    Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 Note The AI Block has it's own filtering parameter called PV_FTIME. For simplicity, it is better to do filtering in the Transducer Block as damping will be applied to primary value on every sensor update. If filtering is done in AI block, damping will be applied to output every macrocycle.
  • Page 49: Status Options

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 3.7.8 Status options Status Options (STATUS_OPTS) supported by the AI Block are shown below. Propagate fault forward If the status from the sensor is Bad, Device failure or Bad, Sensor failure, propagate it to OUT without generating an alarm.
  • Page 50: Multiple Analog Input (Mai) Function Block

    Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 Multiple Analog Input (MAI) function block OUT_1 OUT_2 OUT_3 OUT_4 OUT_5 OUT_6 OUT_7 OUT_8 Out1 = The block output value and status for the first channel. The MAI function block has the ability to process up to eight field device measurements and make them available to other function blocks.
  • Page 51: Lcd Transducer Block

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Modes The MAI Function Block supports three modes of operation as defined by the MODE_BLK parameter: Manual (Man) The block output (OUT) may be set manually. Automatic (Auto) OUT_1 to OUT_8 reflects the analog input measurement or the simulated value when simulation is enabled.
  • Page 52 Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 pressure transmitter. If a function block is scheduled in the Rosemount 3051S that links a process variable from another device on the segment, that process variable can be shown on the LCD display. Display Parameter 1 AI Block Block Type #1...
  • Page 53: Display Bar Graph

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Displaying a variable from another device on the segment (example) Input Selector Any Function block on Segment IN_5 IN_6 Parameter X IN_7 IN_8 Any variable from a device on the network can be displayed on the Rosemount 3051S LCD display but the variable must be on a regularly scheduled communications cycle and the variable must be linked to a block within the Rosemount 3051S.
  • Page 54: Engineering Assistant Software

    Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 The second part is configuring the Mass Flow Block to accept pressure and temperature inputs from other transmitters. The differential pressure is passed to the Mass Flow Block through a channel. The pressure and temperature inputs can be linked through any F Fieldbus configurator.
  • Page 55: Create And Send Mass Flow Configuration

    Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Figure 3-6. Device View A. Device tag name(s) on segment B. Scan fieldbus segment C. Selected device status D. Communication status (ONLINE or OFFLINE) 3.11.3 Create and send mass flow configuration A mass flow configuration file can be created in either OFFLINE or ONLINE mode using Rosemount 3051S EA for F Fieldbus.
  • Page 56 Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 Figure 3-7. Open EA Wizard A. Scan button B. Select device tag name C. Open EA Wizard D. Mass flow configuration file name E. Start EA Wizard F. Browse and open existing file 3.
  • Page 57 Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Note Upon completing a mass flow configuration using the EA Wizard, the file can be saved to disk. The file must be saved for review or to edit the mass flow configuration file in the future. F Fieldbus OUNDATION mass flow configuration files cannot be uploaded from the Mass Flow Transducer Block.
  • Page 58 Configuration Reference Manual 00809-0200-4801, Rev DA October 2016 Table 3-7. Mass Flow Block Device - Specific Parameter Values Data type/ Initial Index Parameter structure Store Size Valid range value Units Mode Description DIFFERENTIAL DS-65 Differential pressure status and value _PRESSURE 68°F DIFFERENTIAL 10: DP Sensor...
  • Page 59 Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Figure 3-10. Field Communicator Menu Tree Home Overview Overview Status Active Alerts Overview Status Active Alerts "Alert 1 Name" Configure Primary Purpose Variable Return all to Service Service Tools Shortcuts Put all Out of Service Advanced Primary Purpose Variable Pressure...
  • Page 60 Reference Manual Configuration 00809-0200-4801, Rev DA October 2016 Configuration...
  • Page 61: Overview

    Reference Manual Operation and Maintenance 00809-0200-4801, Rev DA October 2016 Section 4 Operation and Maintenance Overview ............... . page 51 Safety messages .
  • Page 62: Status

    Operation and Maintenance Reference Manual 00809-0200-4801, Rev DA October 2016 Status Along with the measured or calculated PV value, every F Fieldbus block passes an additional OUNDATION parameter called STATUS. The PV and STATUS are passed from the Transducer Block to the Analog Input Block.
  • Page 63: Calibration

    Reference Manual Operation and Maintenance 00809-0200-4801, Rev DA October 2016 Manual mode To change only the OUT_VALUE and not the OUT_STATUS of the AI Block: 1. Place the TARGET MODE of the block to MANUAL. 2. Change the OUT_VALUE to the desired value. Simulate 1.
  • Page 64: Zero Trim Method

    Operation and Maintenance Reference Manual 00809-0200-4801, Rev DA October 2016 8. Set SENSOR_CAL_WHO to the person responsible for the calibration. 9. Set SENSOR _CAL_LOC to the calibration location. 10.Set SENSOR_CAL_METHOD to User Trim. 11.Set MODE_BLK.TARGET to AUTO. 4.5.2 Zero trim method In order to zero the transmitter, run the Zero Trim Method.
  • Page 65: Overview

    Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 Section 5 Troubleshooting Overview ............... . page 55 Safety messages .
  • Page 66: Service Support

    00809-0200-4801, Rev DA October 2016 Service support ™ To expedite the return process outside of the United States, contact the nearest Emerson representa- tive. Within the United States, call the Rosemount National Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
  • Page 67: Flowcharts

    Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 Flowcharts Figure 5-1. Rosemount 3051S Troubleshooting Problems with communications Device does not appear Device does not on segment. stay on segment. 1. Check wiring to device. 2. Recycle power to device. 3. Electronic failure. Refer to Device does not show up on Table 5-1...
  • Page 68 Troubleshooting Reference Manual 00809-0200-4801, Rev DA October 2016 Figure 5-2. Problems with Communications Communications established but have “Block_err” or an “Alarm” Condition “PlantWeb™ Alerts” on page 65 Problem Identified? Perform Recommended Action, see Table 5-1 Read the following parameters in the Resource Block to determine the recommended action.
  • Page 69: Resource Block

    Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 Table 5-1. Troubleshooting Guide Symptom Cause Recommended actions Unknown Recycle power to device 1. Ensure the device is connected to the segment. 2. Check voltage at terminals. There should be 9–32Vdc. No power to device 3.
  • Page 70: Sensor Transducer Block

    Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 Table 5-3. Resource Block SUMMARY_STATUS Messages Condition name Uninitilized No repair needed Repairable Call Service Center Table 5-4. Resource Block DETAILED_STATUS Messages Condition name Recommended action 1. Restart processor. 2. Check display connection. LOI Transducer block error 3.
  • Page 71: Diagnostics

    Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 5.6.1 Diagnostics Table 5-7 lists the potential errors and the possible corrective actions for the given values. The corrective actions are in order of increasing system level compromises. The first step should always be to reset the transmitter and then if the error persists, try the steps in Table 5-7.
  • Page 72: Analog Input (Ai) Function Block

    Troubleshooting Reference Manual 00809-0200-4801, Rev DA October 2016 Analog Input (AI) Function Block This section describes error conditions that are supported by the AI Block. Read Table 5-9 to determine the appropriate corrective action. Table 5-8. AI BLOCK_ERR Conditions Condition number Condition name and description Other...
  • Page 73: Mai Block

    Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 MAI Block Symptom Possible causes Corrective action Target mode not set Set target mode to something other than OOS. BLOCK_ERR will show the configuration error bit set. Before the block is Configuration error allowed out of OOS, the CHANNEL must be set to 11 for “All ADB-SPM Outputs”.
  • Page 74: Advanced Diagnostics Transducer Block (Adb)

    Troubleshooting Reference Manual 00809-0200-4801, Rev DA October 2016 Symptom Possible causes Recommended action See XXXX (Self Test). If some Some LCD display segments have gone of the segment is bad, replace the LCD display. The display is hard to read. Device exceeds temperature limit for Check ambient temperature the LCD display.
  • Page 75: Plantweb ™ Alerts

    Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 ™ 5.11 PlantWeb Alerts Table 5-12. Failure Alerts Default configuration What alert is Recommended 0 = Disabled, Alert detecting Effect on instrument action Help 1 = Enabled 1. Check interface cable between sensor check interface Primary Pressure updates from...
  • Page 76 Troubleshooting Reference Manual 00809-0200-4801, Rev DA October 2016 Table 5-13. Maintenance Alerts Default configuration What alert is Effect on Recommended 0 = Disabled, Alert detecting instrument action Help 1 = Enabled 1. Confirm process pressure is within the Instrument pressure operating range of transmitter.
  • Page 77 Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 Default configuration What alert is Effect on Recommended 0 = Disabled, Alert detecting instrument action Help 1 = Enabled Mass Flow DP value is negative (and Check DP sensor Licensed Mass Flow PV Transducer beyond a threshold) configuration...
  • Page 78 Reference Manual Troubleshooting 00809-0200-4801, Rev DA October 2016 Troubleshooting...
  • Page 79: Oundation

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 Section 6 Advanced Pressure Diagnostics for ™ Fieldbus OUNDATION Overview ............... . page 69 SPM technology .
  • Page 80: Pil Diagnostics

    Link Master device if this is a concern. SPM technology ™ SPM is a unique technology developed by Emerson that provides a means for early detection of abnormal situations in a process environment. The technology is based on the premise that virtually all dynamic processes have a unique noise or variation signature when operating normally.
  • Page 81: Spm Functionality

    The mean (or average) is calculated on the unfiltered pressure signal, the standard deviation calculated from the filtered pressure signal. These statistical values are available via handheld communication devices like the Emerson 375 Field Communicator or asset management software like ™...
  • Page 82 Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 Figure 6-3. Rosemount 3051S FF Statistical Process Monitoring SPM also contains a learning module that establishes the baseline values for the process. Baseline values are established under user control at conditions considered normal for the process and installation. These baseline values are made available to a decision module that compares the baseline values to the most current values of the mean and standard deviation.
  • Page 83: Spm Configuration And Operation

    Therefore, Emerson cannot absolutely warrant or guarantee that SPM will accurately detect each specific condition under all circumstances.
  • Page 84: Configuration For Monitoring Other Process Variables

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 SPM_Active = Enabled with 1st-order HP Filter After SPM is enabled, it will spend the first five (whatever the SPM_Monitoring_Cycle is set to) minutes in the learning phase, and then another five minutes in the verification phase. If a steady process is detected at the end of the verification phase, the SPM will move into the monitoring phase.
  • Page 85 Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 appropriate. The allowable range is 1 to 1440 minutes (for software revisions 2.0.x or earlier, the minimum SPM Monitoring Cycle is 5 minutes). Figure 6-5 illustrates the effect of the SPM Monitoring Cycle on the Statistical Calculations. Notice how with a shorter sampling window there is more variation (e.g.
  • Page 86: Alert Configuration

    Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 6.3.4 Alert configuration To have SPM generate a PlantWeb alert, the alert limits must be configured on the mean and/or standard deviation. The three alert limits available are: SPM#_Mean_Lim Upper and lower limits for detecting a Mean Change SPM#_High_Variation_Lim Upper limit on standard deviation for detecting a High Variation condition SPM#_Low_Dynamics_Lim...
  • Page 87: Plantweb Alert

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 SPM#_Mean_Change Percent change between the baseline mean and the current mean SPM#_Baseline_StDev Baseline standard deviation of the process variable, determined during the Learning/Verification process, and representing the normal operating condition SPM#_StDev Current Standard Deviation of the process variable SPM#_StDev_Change...
  • Page 88: Trending Statistical Values In Control System

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 6.3.7 Trending statistical values in control system SPM mean and standard deviation values may be viewed and/or trended in a Fieldbus host system through the AI or MAI function blocks. An Analog Input (AI) Block may be used to read either the mean or the standard deviation from any one of the SPM Blocks.
  • Page 89: Spm Configuration With Eddl

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 6.3.8 SPM configuration with EDDL For host systems that support Electronic Device Description Language (EDDL), using SPM is made easier with step-by-step configuration guidance and graphical displays. This section of the manual uses AMS Device Manager version 10.5 for illustrations, although other EDDL hosts could be used as well.
  • Page 90: Example Configuration Of Spm Using Function Block

    Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 6.3.9 Example configuration of SPM using Function Block The following is an example of configuring SPM using one of the Function Blocks within the transmitter. Figure 6-9 illustrates an example from DeltaV Control Studio of the PID Function Block (highlighted) within the Rosemount 3051S Pressure Transmitter being used for control in the field.
  • Page 91: Eddl Trending Of Mean And Standard Deviation

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 Figure 6-10. Example Configuration of SPM Using a Function Block Set the High Variation Limit (or other limits) as desired, and set the user command to Learn in order to begin the learning process for this SPM Block.
  • Page 92: Trending Spm Data In Deltav

    Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 Note that data shown on the EDDL trends are not stored in a process historian or other database. When this screen is closed, all past data in the trends plots are lost. See “Trending SPM data in DeltaV”...
  • Page 93 Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 Figure 6-13. Adding History Recorder from DeltaV Control Studio Follow through the Add History Collection dialog (Figure 6-14), to add the parameter to the DeltaV Historian with the desired sampling period, compression, etc. By default the sampling period is 60 seconds, as shown in Figure 6-14.
  • Page 94: Pil Detection Technology

    Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 Figure 6-15. Trend of Standard Deviation in DeltaV Process History View Finally, when the SPM data is trended in DeltaV, it is possible to configure HI and/or LO alarms on the mean or standard deviation via the AI Block.
  • Page 95: Pil Physics

    October 2016 Figure 6-16. PIL Basics Testing at Emerson and other sites indicates that SPM technology can detect plugged impulse lines. Plugging effectively disconnects the transmitter from the process, changing the noise pattern received by the transmitter. As the diagnostic detects changes in noise patterns, and there are multiple sources of noise in a given process, many factors can come into play.
  • Page 96 Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 common mode cancellation no longer occurs. Therefore there is an increase in the noise of the DP signal. Figure 6-18. Figure 6-17. Differential Pressure Signals under Different Plugging Conditions Figure 6-18. Differential Pressure (DP) Signals under Different Plugged Conditions However, there is a combination of factors that may affect the output of the DP transmitter under single plugged line conditions.
  • Page 97: Plugged Line Detection Factors

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 6.4.3 Plugged line detection factors The factors that may play a significant role in a successful or unsuccessful detection of a plugged impulse line can be separated into positive factors and negative factors, with the former increasing the chances of success and the latter decreasing the chances of success.
  • Page 98 Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 plugging occurs, the resonant generated noise is still present, and the transmitter does not detect a significant change in noise level, and the plugged condition is undetected. The formula that describes the resonant frequency is: fn = (2n-1)*C/4L (2) where:...
  • Page 99: Pil Functionality

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 6.4.4 PIL functionality The Advanced Diagnostics Suite provides the PIL diagnostic, as an easy way to apply SPM technology specifically for detecting plugging in pressure measurement impulse lines. Similar to SPM, PIL also calculates the mean and standard deviation of the pressure measurement and generates an alert when the standard deviation exceeds an upper or lower limit.
  • Page 100 Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 2. Sufficient variation? During the Learning and the Verify modes, the PIL checks that the noise level (e.g. the standard deviation) is high enough for reliable detection of plugged impulse lines. If the noise level is too low, the status goes to “Insufficient Dynamics”, and the PIL stops.
  • Page 101: Configuration Of Pil Detection

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 Figure 6-20. Plugged Impulse Line Diagnostics Flow Configuration of PIL detection This section describes the configuration of the plugged impulse line diagnostic. 6.5.1 Basic configuration For some impulse line plugging applications there will be a very significant (> 80%) decrease in standard deviation.
  • Page 102: Configuration Of Detection Sensitivity

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 By default, the value of PLINE_Affect_PV_Status is “False”, meaning the quality of the pressure measurement will not be changed if PIL detects a plugged impulse line. Setting this parameter to True will cause the status quality to change to “Uncertain”...
  • Page 103 Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 Figure 6-21. PIL Basic Detection Sensitivities Detection sensitivities are specified as a percent change in the standard deviation from the baseline value. Note from Figure 6-21 that a higher detection limit (% change) actually corresponds to a lower sensitivity, because a greater change in the process dynamics is required to trigger a plugged impulse line alert.
  • Page 104: Determining Detection Sensitivity

    Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 PLINE_Single_Detect_Sensitivity Adjusts the Upper detection limit. If this value is 0 (default), the Upper limit is determined by PLINE_Sen- sitivity. If this value is greater than 0, then it overrides the basic sensitivity value. This value can be set in the range 0 –...
  • Page 105: Advanced Pil Configuration

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 A good “rule of thumb” is to set the detection limit to half of the observed change in standard deviation, but no less than 20 percent. 6.5.4 Advanced PIL configuration PIL provides the ability for advanced users to fine-tune some of the algorithm settings.
  • Page 106: Pil Operation

    Advanced Pressure Diagnostics Reference Manual 00809-0200-4801, Rev DA October 2016 PLINE_Learn_Sensitivity The PLINE_Learn_Sensitivity parameters provide very specific adjustments to the sensitivity during the learning phase. Most of the time, it is sufficient to use these default values: Insufficient Dynamics Check: Ignores the insufficient dynamic check if not selected. Use only when ...
  • Page 107: Viewing The Indication Of A Pil

    Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 Table 6-4. Corresponding EDDL Labels Fieldbus parameter name EDDL label(s) PLINE_ON Plugged Line PLINE_Learn_Length Learning Cycle PLINE_Sensitivity Sensitivity Detection Detection Sensitivity PLINE_Affect_PV_Status Affect PV Status PLINE_Relearn User Command PLINE_Auto_Relearn Auto Relearn PLINE_Relearn_Threshold Relearn Threshold (% of URL) PLINE_Learn_Sensitivity...
  • Page 108 Reference Manual Advanced Pressure Diagnostics 00809-0200-4801, Rev DA October 2016 Advanced Pressure Diagnostics...
  • Page 109: Performance Specifications

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Appendix A Specifications and Reference Data Performance specifications ............page 99 Functional specifications .
  • Page 110 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Transmitter with In-Line Sensor Module Absolute Pressure (Rosemount 3051S_TA), Gage Pressure (Rosemount 3051S_TG) Ultra Classic ±0.025% of span ±0.035% of span Ranges 1 - 4 For spans less than 10:1, For spans less than 10:1, ±(0.004 [URL/Span])% of span ±(0.0065 [URL/Span])% of span...
  • Page 111: Transmitter Total Performance

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA A.1.3 Transmitter total performance Total performance is based on combined errors of reference accuracy, ambient temperature effect, and line pressure effect. Models Ultra Classic and Classic MV Ultra for Flow Rosemount Ranges 2-3 3051S_CD...
  • Page 112: Uncompensated Flow Performance

    Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA A.1.5 Uncompensated flow performance Flow performance specifications assume the device only uses DP readings without pressure and temperature compensation. Models Ultra Classic Ultra for Flow Annubar Flowmeter (Rosemount 3051SFA) Ranges 2-3 ±0.85% of flow rate at 8:1 flow ±0.9% of flow rate at 8:1 flow ±0.80% of flow rate at 14:1 flow...
  • Page 113: Warranty

    Warranty details can be found in Emerson Process Management Terms and Conditions of Sale, Document 63445, Rev G (10/06). Rosemount Ultra and Ultra for Flow transmitters have a limited warranty of 15 years from date of shipment. All other provisions of Emerson Process Management standard limited warranty remain the same.
  • Page 114: Ambient Temperature Effect

    Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA A.1.9 Ambient temperature effect Transmitter with Coplanar Sensor Module (Single Variable) Differential Pressure: (Rosemount 3051S_CD, 3051SMV_ _3 or 4) Gage Pressure: (Rosemount 3051S_CG) Ultra Classic Ultra for Flow per 50 °F (28 °C) per 50 °F (28 °C) -40 to 185 °F (-40 to 85 °C) Ranges 2 - 5...
  • Page 115: Line Pressure Effect

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Transmitter with Multivariable Sensor Module Differential Pressure and Static Pressure (Rosemount 3051SMV_ _1 or 2) Models Classic MV Ultra for Flow Per 50 °F (28 °C) -40 to 185 °F (-40 to 85 °C) DP Ranges 2-3 ±(0.0125% URL + 0.0625% span) ±0.13 reading up to 8:1 DP turndown from URL;...
  • Page 116: Mounting Position Effects

    Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA A.1.11 Mounting position effects Models Ultra, Ultra for Flow, Classic, and Classic MV Rosemount 3051S_CD or CG Zero shifts up to ±1.25 inH O (3,11 mbar), which can be zeroed Rosemount 3051SMV_ _ 3 or 4 Span: no effect Rosemount 3051SF_3, 4, 7, or D...
  • Page 117: Functional Specifications

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA A.2 Functional specifications A.2.1 Range and sensor limits Transmitter with Coplanar Sensor Module (Single Variable) DP Sensor GP Sensor AP Sensor (Rosemount 3051S_CD, Rosemount (Rosemount 3051S_CG, Rosemount (Rosemount 3051S_CA, 3051SMV_ _3, 4, or D Rosemount 3051SF_3, 3051SAL_G) Rosemount 3051SAL_A)
  • Page 118: Minimum Span Limits

    Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Static Pressure Sensor (GP/AP) Range Lower (LRL) Upper (URL) : -14.2 psig (0,98 bar) GP: 800 psig (55,16 bar) AP: 0.5 psia (34,5 mbar) AP: 800 psia (55,16 bar) : -14.2 psig (0,98 bar) GP: 3626 psig (250 bar) AP: 0.5 psia (34,5 mbar)
  • Page 119 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Transmitter with Multivariable Sensor Module (Rosemount 3051SMV_ _1 or 2, Rosemount 3051SF_1, 2, 5, or 6) DP Sensor Range Ultra for Flow Classic MV 0.5 inH O (1,24 mbar) 0.5 inH O (1,24 mbar) 1.3 inH...
  • Page 120: Overpressure Limits

    Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Provides pre-defined application-based equations including The integral Statistical Process Monitoring (SPM) technology flow with partial density compensation, electronic remote calculates the mean and standard deviation of the process seals, hydrostatic tank gauging, ratio control and others. variable 22 times per second and makes them available to the user.
  • Page 121: Static Pressure Limits

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Liquid Level Transmitter (Rosemount 3051SAL) A.2.6 Temperature Limits Overpressure limit is dependent on the flange rating or sensor Ambient rating (whichever is lower). Use Instrument Toolkit to ensure the -40 to 185 °F (-40 to 85 °C) seal system meets all pressure and temperature limits.
  • Page 122: Humidity Limits

    Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA A DIN 16288 Male (available in SST for sensor 32 °F (0 °C) is the lower process temperature limit for DP Range 0. G11 Code ranges 1-4 only) For Rosemount 3051S_C, 160 ° F (71 °C) limit in vacuum service. For Rosemount 3051SMV_ _ 1, 2, 140 °...
  • Page 123: Shipping Weights

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Bolts A.3.5 Shipping weights Plated carbon steel per ASTM A449, Type 1 Sensor module weights Austenitic 316 SST per ASTM F593 Coplanar ASTM A453, Class D, Grade 660 SST ASTM A193, Grade B7M alloy steel 3.1 lb (1,4 kg) ASTM A193, Class 2, Grade B8M SST...
  • Page 124 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Transmitter option weights Option code Option Add lb (kg) E12, E22 SST coplanar flange with SST drain vents 1.9 (0,9) F14, F24 Cast Alloy 400 traditional flange with Alloy 400/K-500 drain vents 3.6 (1,6) F15, F25 SST traditional flange with Alloy C-276 drain vents...
  • Page 125: Dimensional Drawings

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA A.4 Dimensional drawings Figure A-1. Transmitter with Coplanar Sensor Module and Flange PlantWeb housing Junction Box housing Wireless housing Front view Front view Front view 4.20 4.20 (107) (107) 90°...
  • Page 126 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Figure A-2. Transmitter with Coplanar Sensor Module and Traditional Flange PlantWeb housing Junction Box housing Wireless housing Front view Front view Front view 90° 6.93 (176) 10.91 (277) 9.26 9.26 (235) (235)
  • Page 127 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Figure A-3. Transmitter with In-Line Sensor Module PlantWeb housing Junction Box housing Wireless housing Front view Front view Front view 4.20 4.20 (107) (107) 90° 6.93 (176) 10.91 3.46 (277) (87.8) 4.20...
  • Page 128 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Figure A-4. Coplanar Mounting Configurations (B4 Bracket) Pipe mount Panel mount Front view Front view Front view 4.55 2.58 (116) (66) 6.15 (156) 2.81 (71) 3.54 4.72 6.25 (90) (120) (159) Dimensions are in inches (millimeters).
  • Page 129 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Figure A-6. In-Line Mounting Configurations (B4 Bracket) Pipe mount Panel mount Front view Side view 2.58 4.55 (116) (66) 6.15 2.81 (156) 6.15 (71) 6.25 3.08 (159) (78) 4.72 (120) 6.90 (175) Dimensions are in inches (millimeters).
  • Page 130 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Figure A-8. Rosemount 3051SFA Annubar Flowmeter Front view Side view Top view Dimensions are in inches (millimeters). The Pak-Lok Annubar model is available up to ANSI Class 600 (1440 psig at 100 °F [99 bar at 38 °C]). Specifications and Reference Data...
  • Page 131 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Table A-1. Rosemount 3051CFA Annubar Flowmeter Dimensional Data Sensor size A (Max) B (Max) C (Max) D (Max) 7.50 (190.5) 16.03 (407.2) 9.00 (228.6) 6.90 (175.3) 9.25 (235.0) 17.78 (451.6) 9.00 (228.6) 6.90 (175.3) 12.00 (304.8)
  • Page 132 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Figure A-10. Rosemount 3051SFP Integral Orifice Flowmeter Front view Bottom view Side view 11.9 8.8 (223.46) (302.3) 7.7 (195.6) Flow (134.14) B.D. Downstream J Upstream Dimensions are in inches (millimeters). Line size -in.
  • Page 133: Accessories

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Figure A-11. Rosemount 3051SAL Liquid Level Transmitter Side view Front view Flush flanged configuration Extended flanged configuration 4.20 (107) 4.20 (107) 5.21 (132) 4.55 (116) 7.09 9.65 (180) (245) 8.53 (217) Extension 2, 4, or 6 (51, 102, or 152)
  • Page 134: Ordering Information

    Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA A.6 Ordering Information ™ ™ Table A-3. Rosemount 3051S Scalable Coplanar Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 135 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA ™ ™ Table A-3. Rosemount 3051S Scalable Coplanar Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 136 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA ™ ™ Table A-3. Rosemount 3051S Scalable Coplanar Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 137 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA ™ ™ Table A-3. Rosemount 3051S Scalable Coplanar Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 138 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA ™ ™ Table A-3. Rosemount 3051S Scalable Coplanar Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 139 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA ™ ™ Table A-3. Rosemount 3051S Scalable Coplanar Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 140 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA ™ ™ Table A-3. Rosemount 3051S Scalable Coplanar Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 141 “Assemble to” items are specified separately and require a completed model number. Process connection option codes B12, C11, D11, EA2, EA3, and EA5 are only available on differential Measurement Type, code D. ™ Consult an Emerson Process Management representative for performance specifications. Not available with Performance Class code 3.
  • Page 142 Not available with housing style codes 00, 2E, 2F, 2G, 2M, 5A, 5J, or 7J. Not available with process connection option code A11. Requires PlantWeb housing and Hardware Adjustments option code D1. Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative for additional information.
  • Page 143 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Table A-4. Rosemount 3051S Scalable In-line Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 144 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Table A-4. Rosemount 3051S Scalable In-line Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 145 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Table A-4. Rosemount 3051S Scalable In-line Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 146 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Table A-4. Rosemount 3051S Scalable In-line Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 147 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Table A-4. Rosemount 3051S Scalable In-line Pressure Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
  • Page 148 Not available with housing style codes 00, 01, 2E, 2F, 2G, 2M, 5A, 5J, or 7J. Requires PlantWeb housing and Hardware Adjustments option code D1. Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative for additional information.
  • Page 149 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Not available with Housing code 00, 5A, 5J, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe; Nonincendive (option code I5) or FM FISCO Intrinsically Safe (option code IE), install in accordance with Rosemount drawing 03151-1009. Suitable for use with all IS approvals (I1, I2, I3, I5, I6, I7, IA, IB, IE, IF, IG, IP, IM, KG).
  • Page 150 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Model Transmitter type 3051SAL...
  • Page 151 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Junction Box housing Aluminum –14 NPT...
  • Page 152 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. High side connection type [select based on seal system type chosen] Single seal system Dual seal system...
  • Page 153 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. 0.075-in.
  • Page 154 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. 26.2 ft (8,0 m) 29.5 ft (9,0 m) 32.8 ft (10,0 m)
  • Page 155 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Seal style See the Rosemount 1199 Product Data Sheet...
  • Page 156 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Alarm limit (19)(22) NAMUR alarm and saturation levels, high alarm...
  • Page 157 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. IECEx Flameproof, Dust Ignition-proof IECEx Intrinsic Safety IECEx FISCO Intrinsic Safety (F...
  • Page 158 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Table A-5. Rosemount 3051SAL Scalable Level Transmitter Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Alloy K-500 bolts (30) ASTM A453, Class D, Grade 660 bolts...
  • Page 159 Valid when SuperModule Platform and housing have equivalent approvals. Not available with M20 or G ½ conduit entry size. Requires PlantWeb housing and Hardware Adjustments option code D1. Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative for additional information.
  • Page 160 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Table A-6. Rosemount 300S Series Housing Kit Model 300S Housing kit for Rosemount 3051S Coplanar, In-Line, and Liquid Level Transmitters Code Housing style Material Conduit entry PlantWeb housing Aluminum –14 NPT PlantWeb housing Aluminum...
  • Page 161 Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output Note: See the Rosemount 3051S Reference Manual for cable requirements. Contact an Emerson representative for additional information. (8)(9) Remote mount LCD display and interface, 50 ft. (15 m) cable; SST bracket, requires 4-20 mA / HART output (8)(9) Remote mount LCD display and interface, 100 ft.
  • Page 162 Material specified is cast as follows: CF-3M is the cast version of 316L SST. For housing, material is aluminum with polyurethane paint. Available with output code A only. Not available with approvals. Contact an Emerson representative for additional information. Requires PlantWeb housing.
  • Page 163: Exploded View Diagram

    Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA A.7 Exploded view diagram The following drawing shows the name and location for commonly ordered spare parts. A. Cover H. Coplanar flange B. Cover O-ring I. Process flange O-ring C.
  • Page 164: Spare Parts

    Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA A.8 Spare parts See Rosemount 3051S_C, 3051S_T & 3051SAL ordering tables in Appendix A: Specifications and Reference Data (Table A-1, Table A-2, Table A-3 respectively) for ordering spare sensor modules. - Typical Model Number 3051S1CD2A2000A00 Electronics board assembly hardware (PlantWeb housing) Part number...
  • Page 165 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Remote meter terminal blocks PlantWeb housing 7-position remote communications terminal block assembly 03151-9006-0101 Junction Box remote communications standard terminal block assembly 03151-9000-1010 Junction Box remote communications transient terminal block assembly 03151-9000-1011 Part number Covers...
  • Page 166 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA CS bolts, graphite PTFE O-rings SST adapters 03031-1300-0102 Alloy C-276 adapters 03031-1300-0103 Alloy 400 adapters 03031-1300-0104 Ni plated CS adapters 03031-1300-0105 SST bolts, graphite PTFE O-rings SST adapters 03031-1300-0112 Alloy C-276 adapters 03031-1300-0113 Alloy 400 adapters...
  • Page 167 Specifications and Reference Data Reference Manual October 2016 00809-0200-4801, Rev DA Traditional flange bracket kits B1 bracket, 2-in. pipe mount, CS bolts 03151-9272-0001 B2 bracket, panel mount, CS bolts 03151-9272-0002 B3 flat bracket for 2-in. pipe mount, CS bolts 03151-9272-0003 B7 (B1 style bracket with SST bolts) 03151-9272-0007 B8 (B2 style bracket with SST bolts)
  • Page 168 Reference Manual Specifications and Reference Data October 2016 00809-0200-4801, Rev DA Part number Meters Indicating meter for PlantWeb aluminum housing Meter kit: LCD display assembly, 4-pin interconnection header and aluminum meter cover assembly 03151-9193-0001 Meter only: LCD display assembly, 4-pin interconnection header 03151-9193-0002 Cover assembly kit: aluminum meter cover assembly 03151-9193-0003...
  • Page 169: European Directive Information

    Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA Appendix B Product Certifications Rev. 1.9 European Directive Information ........... . page 159 Ordinary Location Certification .
  • Page 170: Canada

    Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA FM FISCO Markings: FISCO Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1, Zone 0, IIC, T3C; Certificate: 3012350 when connected per Rosemount drawing Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM 03151-1016 [3051S] 03151-1313 [ERS];...
  • Page 171: International

    Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA Special Conditions for Safe Use (X): 4. The SuperModule(s) must be securely screwed in place to maintain the ingress protection of the enclosure(s). 1. The Rosemount 3051S Transmitters fitted with transient N1 ATEX Type n protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012.
  • Page 172 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA 2. Unused cable entries must be filled with suitable blanking Model plugs which maintain the ingress protection of the enclosure 3051SAL…M7, M8, or M9 93 H to at least IP66. 30 V 300 mA 1.0 W 12 nF...
  • Page 173: Brazil

    Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA IECEx Intrinsic Safety – Group I - Mining (IG with Special Special Conditions for Safe Use (X): A0259) 1. The device contains a thin wall diaphragm. Installation, Certificate: IECEx TSA 14.0019X maintenance and use shall take into account the Standards: IEC 60079-0:2011, IEC 60079-11:2011 environmental conditions to which the diaphragm will be...
  • Page 174 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA Markings: 3051S: Ex d IIC T6…T4; Ex tD A20 T 105 °C T 12. When installation, use and maintenance of transmitter, 95 °C; IP66 observe following standards: 3051SFx: Ex d IIC T5/T6 Ga/Gb; DIP A20 T 105 °C;...
  • Page 175: Eac - Belarus, Kazakhstan, Russia

    Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA 3. Intrinsically safe parameters: 3. Cable glands, conduit or blanking plugs, certified by NEPSI with Ex e or Ex n protection type and IP66 degree of protection provided by enclosure, should be used on external Maximum Maximum Maximum...
  • Page 176: Combinations

    Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA B.13 Combinations B.14 Additional certifications K1 Combination of E1, I1, N1, and ND SBS American Bureau of Shipping (ABS) Type Approval K2 Combination of E2 and I2 Certificate: 00-HS145383-6-PDA K5 Combination of E5 and I5 Intended Use: Measure gauge or absolute pressure of liquid, gas or vapor applications on ABS classed K6 Combination of E6 and I6...
  • Page 177: Installation Drawings

    Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA B.15 Installation drawings B.15.1 Factory Mutual (FM) – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 178 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 179 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 180 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 181 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 182 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 183 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 184 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 185 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 186 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 187 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 188 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 189 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 190 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA Product Certifications...
  • Page 191 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA Product Certifications...
  • Page 192 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA Product Certifications...
  • Page 193: Canadian Standards Association (Csa)

    Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA B.15.2 Canadian Standards Association (CSA) – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 194 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 195 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 196 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 197 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 198 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 199 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 200 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 201 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 202 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 203 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 204 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 205 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 206: Kema

    Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA B.15.3 KEMA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 207 Product Certifications Reference Manual October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 208 Reference Manual Product Certifications October 2016 00809-0200-4801, Rev DA – PRINTED COPIES ARE UNCONTROLLED – Electronic Master Rosemount Proprietary Product Certifications...
  • Page 209: Resource Block

    Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA ™ Appendix C Fieldbus Block OUNDATION Information Resource Block ..............page 199 Sensor Transducer Block .
  • Page 210 Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Table C-1. Resource Block Parameters Parameter Index Valid range Initial value Units Other Description DEV_REV Read Manufacturer revision number associated with the resource - used by an interface device to locate the DD Only file for the resource.
  • Page 211 Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Table C-1. Resource Block Parameters Parameter Index Valid range Initial value Units Other Description FAULT_STATE 1: Clear Read Condition set by loss of communication to an output block, fault promoted to an output block or a physical 2: Active Only contact.
  • Page 212 Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Table C-1. Resource Block Parameters Parameter Index Valid range Initial value Units Other Description MISC_OPTION Read Indicates which miscellaneous licensing options are enabled. Only RB_SFTWR_ set by build Read Major revision of software that the resource block was REV_MAJOR created with.
  • Page 213 Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Table C-1. Resource Block Parameters Parameter Index Valid range Initial value Units Other Description SAVE_CONFIG Read Number of EEPROM blocks that have been modified _BLOCKS since last burn. This value will count down to zero when Only the configuration is saved.
  • Page 214: Sensor Transducer Block

    Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Table C-1. Resource Block Parameters Parameter Index Valid range Initial value Units Other Description ADVISE_ Read Enabled ADVISE_ALM alarm conditions. Corresponds bit ENABLE for bit to the ADVISE_ACTIVE. A bit on means that the Only corresponding alarm condition is enabled and will be detected.
  • Page 215 Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Parameter Index Valid range Initial value Units Other Description ALERT_KEY 1-255 The identification number of the plant unit. MODE_BLK The actual, target, permitted, and normal modes of the block. BLOCK_ERR Read This parameter reflects the error status associated with...
  • Page 216 Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Parameter Index Valid range Initial value Units Other Description SENSOR_CAL The date of the last sensor calibration. This is intended _DATE to reflect the calibration of that part of the sensor that is usually wetted by the process.
  • Page 217: Analog Input (Ai) Function Block

    Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Analog Input (AI) Function Block The Analog Input (AI) function block processes field device measurements and makes them available to other function blocks. The output value from the AI block is in engineering units and contains a status indicating the quality of the measurement.
  • Page 218 Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Table C-3. Definitions of AI Block System Parameters Available Read/ Parameter Index values Units Default write Description ALERT_KEY 1 – 255 None Read The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
  • Page 219 Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Table C-3. Definitions of AI Block System Parameters Available Read/ Parameter Index values Units Default write Description L_TYPE Direct None Direct Read Linearization type. Determines whether the field value is used directly (Direct), is converted Indirect linearly (Indirect), or is converted with the Indirect Square...
  • Page 220 AP/3051T all torr AI2 deg C deg C deg F ™ The host system may write over default values pre-configured by Emerson Assume that when L_Type = Direct, the user configures Out_Scale which is equal to XD_Scale Fieldbus Block Information OUNDATION...
  • Page 221: Lcd Display Transducer Block

    Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA LCD Display Transducer Block Table C-4. LCD Display Transducer Block Parameters Parameter Index Valid range Initial value Units Other Description ST_REV 0-255 The revision level of the static data associated with the function block.
  • Page 222 Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Table C-4. LCD Display Transducer Block Parameters Parameter Index Valid range Initial value Units Other Description PARAM_INDEX The relative index of DP2 within its block. See Table 34 CUSTOM_TAG spaces The block description that is displayed for DP2.
  • Page 223: Advanced Diagnostics Transducer Block (Adb)

    Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Advanced Diagnostics Transducer Block (ADB) Table C-5. ADB Parameters Parameter Index Valid range Initial value Units Other Description ST_REV 0-255 Read The revision level of the static data associated with the function block. Only TAG_DESC spaces...
  • Page 224: Oundation

    Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Table C-5. ADB Parameters Parameter Index Valid range Initial value Units Other Description SPM_ 1 to 1440 min. Time Period for Mean and Stdev MONITORING calculations during Learning and _CYCLE Monitoring SPM_BYPASS_...
  • Page 225 Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Table C-5. ADB Parameters Parameter Index Valid range Initial value Units Other Description SPM2_BLOCK_ All Function Blocks in the device The function block type for the SPM2 TYPE variable SPM2_BLOCK_ All Function Blocks in the device NULL...
  • Page 226 Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Table C-5. ADB Parameters Parameter Index Valid range Initial value Units Other Description SPM3_PARAM All DS-65 parameters for the OD Parameter index for the SPM3 Block _INDEX Tag that is entered. block type of the entered block tag.
  • Page 227 Fieldbus Block Information Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Table C-5. ADB Parameters Parameter Index Valid range Initial value Units Other Description SPM4_PARAM All DS-65 parameters for the OD Parameter index for the SPM4 Block _INDEX Tag that is entered. block type of the entered block tag.
  • Page 228 Reference Manual Fieldbus Block Information OUNDATION October 2016 00809-0200-4801, Rev DA Table C-5. ADB Parameters Parameter Index Valid range Initial value Units Other Description PLINE_ON 0 = FALSE FALSE Turns algorithm On/Off 0xff = TRUE PLINE_ 1. Run Resets the algorithm and reinitiates RELEARN learning 2.
  • Page 229: New Function Blocks

    Fieldbus Revision 23 Release Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA ™ Appendix D Fieldbus Revision 23 OUNDATION Release New function blocks ............. . page 219 New functionality .
  • Page 230: New Functionality

    Fieldbus Revision 23 Release Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA New functionality PID with auto tuner This block has now been improved to include an auto-tune function. Advanced Diagnostic Block The Statistical Process Monitoring (SPM) with continuous update of mean and standard deviation at sensor update rate –...
  • Page 231 Fieldbus Revision 23 Release Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Sensor status remains uncertain when reading is beyond sensor limits (increased robustness) Prior to this release when a pressure went beyond the sensor limits, the pressure status would go to BAD. For example;...
  • Page 232 Fieldbus Revision 23 Release Reference Manual OUNDATION October 2016 00809-0200-4801, Rev DA Fieldbus Revision 23 Release OUNDATION...
  • Page 234 Standard Terms and Conditions of Sale can be found at: http://www.Emerson.com/en-us/Terms-of-Use Asia Pacific Regional Office The Emerson logo is a trademark and service mark of Emerson Electric Co. Annubar, SuperModule, PlantWeb, DeltaV, Scalable, AMS, Instrument Toolkit, Emerson Automation Solutions Asia Pacific Pte Ltd...

Table of Contents