Reference Manual
00809-0200-4801, Rev DA
Table C-3. Definitions of AI Block System Parameters
Parameter
Index
ST_REV
01
STATUS_
14
Propagate fault
OPTS
Bad if Limited
STDDEV
39
STRATEGY
03
TAG_DESC
02
UPDATE_EVT
20
XD_SCALE
10
1.
The host system may write over default values pre-configured by Emerson
2.
Assume that when L_Type = Direct, the user configures Out_Scale which is equal to XD_Scale
210
Available
values
Units
N/A
None
forward
Uncertain if
Limited
Uncertain if
Man Mode
0 – 100
Percent
0 – 65535
None
32 text
None
characters
N/A
None
Any sensor
inH
O (68 °F)
2
range
inHg (0 °C)
ftH
O (68 °F)
2
mmH
O (68 °F)
2
mmHg (0 °C)
psi
bar
mbar
2
g/cm
2
kg/cm
Pa
kPa
torr
atm
deg C
deg F
F
OUNDATION
Read/
Default
write
Description
0
Read
The revision level of the static data associated
with the function block. The revision value will
only
be incremented each time a static parameter
value in the block is changed.
0
Read
and
Write
0
Read
The average absolute error between the PV
and its previous mean value over that
and
evaluation time defined by VAR_SCAN.
Write
0
Read
The strategy field can be used to identify
grouping of blocks. This data is not checked or
and
processed by the block.
Write
none
Read
The user description of the intended
application of the block.
and
Write
N/A
Read
This alert is generated by any change to the
static data.
only
(1)
AI1
:
In all Rosemount devices the units of the
transducer block is forced to match the unit
Customer
code.
specification
or
inH
O (68 °F)
2
for DP/GP rng
1, 2, 3)
or
psi for DP/GP
rng 4, 5
AP/3051T all
rng
AI2 deg C
.
Fieldbus Block Information
October 2016
F
Fieldbus Block Information
OUNDATION