October 2016 Quick Start Guide NOTICE This guide provides basic guidelines for the Rosemount 3051S MultiVariable Transmitter (3051SMV). It also provides the basic Rosemount 3051SMV configuration guidelines for the Rosemount 3051SFA Reference Manual, Rosemount 3051SFC Reference Manual, and Rosemount 3051SFP Reference Manual.
Quick Start Guide October 2016 1.0 Mount the transmitter 1.1 Liquid flow applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Flow 1.2 Gas flow applications 1.
Page 4
Only use bolts supplied ™ with the transmitter or sold by Emerson Process Management as spare parts. Figure 1 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
Page 5
Quick Start Guide October 2016 Use the following bolt installation procedure: 1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt. 2.
October 2016 Quick Start Guide 1.6 O-rings with flange adaptors Failure to install proper flange adaptor O-rings may cause process leaks, which can result in death or serious injury. The two flange adaptors are distinguished by unique O-ring grooves. Only use the O-ring designed for its specific flange adaptor, as shown below: Rosemount 3051S/3051/2051/3095 Rosemount 1151...
Quick Start Guide October 2016 Note Do not rotate the housing more than 180° without first performing a disassembly procedure. See Section 4 of the Rosemount 3051SMV Reference Manual for more information. Over-rotation may sever the electrical connection between the sensor module and the feature board electronics.
Page 8
October 2016 Quick Start Guide NOTICE When the enclosed pipe plug is utilized in the conduit opening, it must be installed with a minimum engagement of five threads in order to comply with explosion-proof requirements. Refer to the Rosemount 3051SMV Reference Manual for more information.
Quick Start Guide October 2016 4.2 Power supply The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, intrinsic safety barriers, and related components.
October 2016 Quick Start Guide Figure 7. Rosemount 3051SMV RTD Wiring Connection A. Ground lug B. RTD cable assembly wires C. Pt 100 RTD sensor 5.0 Engineering Assistant installation 5.1 Engineering Assistant 6.1 or later The Rosemount 3051SMV Engineering Assistant 6.1 or later is PC-based software that performs configuration, maintenance, diagnostic functions, and serves as the primary communication interface to the Rosemount 3051SMV with the fully compensated mass and energy flow feature board.
Page 11
Quick Start Guide October 2016 256 MB RAM 100 MB free hard disk space RS232 serial port or USB port (for use with HART modem) CD-ROM Installing Rosemount 3051SMV Engineering Assistant 6.1 or later 1. Uninstall any existing versions of Engineering Assistant 6 currently installed on the PC.
October 2016 Quick Start Guide 1. Remove the cover from the field terminals side of the housing. 2. Power the device as outlined in “Connect wiring and power up”. 3. Connect the HART modem cable to the PC. 4. On the side of the transmitter marked “Field Terminals,” connect the modem mini-grabbers to the two terminals marked “PWR/COMM.”...
Page 13
Quick Start Guide October 2016 6.2 Basic navigation overview Figure 9. Engineering Assistant Basic Navigation Overview The Engineering Assistant software can be navigated in a variety of ways. The numbers below correspond to the numbers shown in Figure A. The navigation tabs contain the flow configuration information. In Offline mode, each tab will not become active until the required fields on the previous tab are completed.
Page 14
October 2016 Quick Start Guide 6.3 Launching Engineering Assistant 6.1 or later Flow configuration for the Rosemount 3051SMV is achieved by launching the Engineering Assistant software from the Start menu. 1. Select the Start menu > All Programs > Engineering Assistant. Engineering Assistant will open to the screen shown in Figure 2.
Page 15
Quick Start Guide October 2016 6.5 Fluid selection for database liquid/gas The Fluid Selection tab shown in Figure 12 allows the user to choose the process fluid. Figure 12. Fluid Selection Tab Note The following example will show a flow configuration for the database gas air used with a Rosemount 405C Conditioning Orifice Plate as the primary element.
Page 16
October 2016 Quick Start Guide 6.6 Fluid properties Note The Fluid Properties tab is an optional step and is not required to complete a flow configuration. The Fluid Properties tab for the database gas air is shown in Figure 13. The user may verify that the properties of the chosen fluid are acceptable.
Page 17
Quick Start Guide October 2016 6.7 Primary element selection The Primary Element Selection tab shown in Figure 14 allows the user to choose the primary element. Figure 14. Primary Element Selection Tab Continuing with the example configuration: 1. Expand the Conditioning Orifice Plate category. 2.
Page 18
October 2016 Quick Start Guide 6.8 Save/send configuration The Save/Send Configuration tab shown in Figure 15 allows the user to verify, save, and send the configuration information to the Rosemount 3051SMV with the fully compensated mass and energy flow feature board. 1.
Page 19
Quick Start Guide October 2016 Figure 16. Engineering Assistant Device Connection Screen 5. Select the Search button located in the lower right hand corner of the screen. Engineering Assistant will begin to search for connected devices. 6. When the search is completed, select the device to communicate with and select Send Configuration button.
October 2016 Quick Start Guide 7.0 Verify device configuration Use Rosemount 3051SMV Engineering Assistant or any HART-compliant master to communicate with and verify configuration of the Rosemount 3051SMV. Table 2 shows the 375 Field Communicator fast keys for the fully compensated mass and energy flow.
Page 21
Quick Start Guide October 2016 Table 2. Fast Keys for Fully Compensated Mass and Energy Flow Function Fast Key sequence Flow Reading and Status 1, 4, 2, 1, 1 Gage Pressure Reading and Status 1, 4, 2, 1, 6 Gage Pressure Sensor Limits 1, 4, 1, 5, 9 Gage Pressure Units 1, 3, 3, 6...
Page 22
October 2016 Quick Start Guide Table 3. Fast Keys for Direct Process Variable Output Function Fast Key sequence Burst Mode Setup 1, 4, 3, 3, 3 Burst Mode Options 1, 4, 3, 3, 4 Callendar-van Dusen Sensor Matching 1, 2, 4, 5, 4 Damping 1, 3, 7 Diaphragm Seals Information...
Quick Start Guide October 2016 8.0 Trim the transmitter Transmitters are shipped fully calibrated per request or by the factory default of full scale. 8.1 Zero trim A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects on static and differential pressure sensors. When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct level.
October 2016 Quick Start Guide 9.0 Product Certifications Rev 1.18 9.1 European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at EmersonProcess.com/Rosemount.
Page 26
October 2016 Quick Start Guide 2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted. I1 ATEX Intrinsic Safety Certificate: Baseefa08ATEX0064X Standards: EN 60079-0:2012, EN 60079-11:2012 II 1 G Ex ia IIC T4 Ga, T4(-60 °C ≤ T ≤...
Page 27
Quick Start Guide October 2016 N1 ATEX Type n Certificate: Baseefa08ATEX0065X Standards: EN 60079-0: 2012, EN 60079-15: 2010 II 3 G Ex nA IIC T4 Gc, (-40 °C ≤ T ≤ +70 °C), V Markings: = 45 V Special Condition for Safe Use (X): 1.
Page 28
October 2016 Quick Start Guide RTD (for 3051SFx) SuperModule OUNDATION Parameters HART Fieldbus only HART Fieldbus Power P 1.3 W 887 mW 17.32 mW 137 mW Capacitance C 14.8 nF 0.11 uF 0.8 nF Inductance L 1.33 mH Special Conditions for Safe Use (X): 1.
Page 29
Quick Start Guide October 2016 I2 INMETRO Intrinsic Safety Certificate: UL-BR 15.0357X Standards: ABNT NBR IEC 60079-0:2008 + Addendum 1:2011, ABNT NBR IEC 60079-11:2009 Markings: Ex ia IIC T4 Ga, T4(-60 °C ≤ T ≤ +70 °C) Special Conditions for Safe Use (X): 1.
Page 30
October 2016 Quick Start Guide 7. During installation in a hazardous location, cable glands and blanking plugs certified by state appointed inspection bodies with Ex d IIC Gb or Ex d IIC Gb DIP A20 [Flowmeters] IP66 type of protection should be used. Redundant cable entries should be blocked with blanking plugs.
Page 31
Quick Start Guide October 2016 8. During installation in hazardous location, cable glands, conduit, and blanking plugs certified by state-appointed inspection bodies with DIP A20 IP66 type of protection should be used. Redundant cable entries should be blocked with blanking plugs. 9.
Page 32
October 2016 Quick Start Guide 9.14 Additional Certifications SBS American Bureau of Shipping (ABS) Type Approval Certificate: 00-HS145383 Intended Use: Measure gauge or absolute pressure of liquid, gas or vapor applications on ABS classed vessels, marine, and offshore installations. [HART Only] SBV Bureau Veritas (BV) Type Approval Certificate: 31910 BV...
Page 33
Quick Start Guide October 2016 Figure 17. Rosemount 3051SMV Declaration of Conformity...
Page 38
October 2016 Quick Start Guide Rosemount 3051SMV China RoHS List of Rosemount 3051SMV Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6) (PBB) (PBDE) Electronics...
Page 40
Standard Terms and Conditions of Sale can be found at Asia Pacific Regional Office www.Emerson.com/en-us/pages/Terms-of-Use Emerson Process Management Asia Pacific Pte Ltd The Emerson logo is a trademark and service mark of Emerson 1 Pandan Crescent Electric Co. Singapore 128461...
Need help?
Do you have a question about the rosemount 3051S series and is the answer not in the manual?
Questions and answers