Hide thumbs Also See for Rosemount 3051S:

Advertisement

Quick Links

Manual Supplement
00809-0100-4851, Rev AA
2017
Rosemount™ 3051S Series of Instrumentation
High Pressure Solutions
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Operation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24
Safety Instrumented Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25
Advanced HART Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25
Specifications and Reference Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 52

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 3051S

  • Page 1: Table Of Contents

    Manual Supplement 00809-0100-4851, Rev AA 2017 Rosemount™ 3051S Series of Instrumentation High Pressure Solutions Introduction ............... . . page 2 Installation .
  • Page 2: Introduction

    Introduction Using this manual This manual is intended to be used as a supplement to the Rosemount 3051S Reference Manuals. Since the Rosemount 3051S High Static Differential Pressure Transmitter (Rosemount 3051SHP) and Rosemount 3051S utilize similar components, certain sections of this manual will be linked to the corresponding Rosemount 3051S Reference Manual section.
  • Page 3: Installation

    Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Section 2 Installation NOTICE This section provides basic guidelines for Rosemount 3051SHP. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. This manual is also available electronically on Emerson.com/Rosemount.
  • Page 4 Not all systems are capable of communicating with HART Revision 7 Protocol. This transmitter can be configured for either HART Revision 5 or 7. For instructions on how to change the HART revision of your transmitter, see the Rosemount 3051S ...
  • Page 5 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Table 1-1. Device Revisions and Files Review Identify device Find device driver instructions Review functionality May-07 00809-0100-4801 Update Statistical Process Monitoring Capability Sep-06 4, 5, 6 00809-0100-4801 NAMUR software revision is located on the hardware tag of the device. In accordance with NE53, revisions of the least significant level X (of 1.0.X) do not change functionality or operation of the device and will not be reflected in the review functionality column.
  • Page 6 Using a mounting bracket ™ The images below provide instructions on how to properly mount the transmitter using the Emerson provided mounting brackets. Use only bolts provided with the transmitter or sold as Emerson spare parts. Bolts should be tightened to a torque of 125 in-lb.
  • Page 7 2.2.6 Wireless considerations (if applicable) Power up sequence The power module should not be installed on any wireless device until the Emerson Smart Wireless Gateway (Gateway) has been installed and functioning properly. See “Power up transmitter” on page 11 for more details.
  • Page 8 If the supplied remote mount antenna kit is not installed per these instructions, Emerson is not responsible for wireless performance or non-compliance with spectrum regulations.
  • Page 9 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-2. Rosemount 3051SHP with High Gain, Remote Antenna A. Lightning arrestor B. Antenna C. Mounting mast D. Drip loop Note: Weather proofing is required! The remote mount antenna kit includes coaxial sealant for weather proofing the cable connections for the lightning arrestor, antenna, and the transmitter.
  • Page 10 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-4. Transmitter Housing Set Screw PlantWeb Junction box A. Housing rotation set screw ( -in.) Note Do not rotate the housing more than 180° without first performing a disassembly procedure. Over-rotation may sever the electrical connection between the sensor module and the feature board electronics.
  • Page 11 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Power up transmitter This section provides the steps needed to power up transmitters. These steps are unique based on the specific protocol used. Steps for HART transmitters begin on page ...
  • Page 12 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-6. Transmitter Wiring PlantWeb housing wiring Junction box housing wiring With optional process temperature connection A. RL ≥ 250 Ω B. Power supply Note Installation of the transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded.
  • Page 13 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-7. Wiring A. Insulate shield D. Trim shield and insulate B. Minimize distance E. Safety ground C. Connect shield back to the power supply ground 3. Replace the housing cover. It is recommended the cover be tightened until there is no gap between the cover and the housing.
  • Page 14 Alternate cable may be used as long as the transmitter with remote display and cable is configured according to the installation control drawing or certificate. Refer to appropriate approval certificate or control drawing in the Rosemount 3051S Reference Manual for remote cable IS requirements.
  • Page 15 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Quick connect wiring (if applicable) As standard, the quick connect arrives properly assembled to the sensor module and is ready for installation. Cordsets and field wireable connectors (in shaded area) are sold separately.
  • Page 16 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Power supply The DC power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces.
  • Page 17 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-12. Transmitter RTD Wiring Connection A. Pt 100 RTD sensor B. RTD cable assembly wires C. Ground lug 2.5.3 Connect wiring and power up F Fieldbus transmitter OUNDATION Cable connection The segment cable can enter the transmitter through either conduit connection on the housing.
  • Page 18 Wireless devices should also be powered up in order of proximity from the Gateway, beginning with the closest. This will result in a simpler and faster network installation. Enable active advertising on the Gateway to ensure new devices join the network faster. For more information, see the Emerson Wireless Gateway 1420 Reference Manual.
  • Page 19 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 1. Remove the housing cover on the field terminal side. 2. Connect the black power module. Verify configuration Use any compliant master to communicate with and verify configuration of the transmitter. Make sure to...
  • Page 20 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-14. Field Communicator Connections P/N 00753-9200-0010 COMM FIELDBUS WIRING A. WirelessHART terminal block B. HART and DA2 terminal block C. Multivariable terminal block D. F Fieldbus terminal block OUNDATION 2.6.2...
  • Page 21: Zero Trim

    If zero offset is greater than 3% of true zero, follow the Using the transmitter zero adjustment button  instructions below to rerange. If hardware adjustments are not available, see the Rosemount 3051S Reference Manual to perform a  rerange using the Field Communicator.
  • Page 22 Push and hold the Zero adjustment button for at least two seconds but no longer than ten seconds. Figure 1-15. Transmitter Adjustment Buttons PlantWeb Junction box A. Zero B. Span Safety instrumented systems installation For safety certified installations, refer to the Rosemount 3051S Reference Manual for installation procedure and system requirements. Rosemount 3051S High Pressure...
  • Page 23: Configuration

    For configuration details using wireless, reference the Rosemount 3051S Wireless Reference Manual.  Section 4 Operation and Maintenance For operation and maintenance details using HART, reference the Rosemount 3051S HART  Reference Manual. For operation and maintenance details using Fieldbus, reference the Rosemount 3051S F ...
  • Page 24: Troubleshooting

     Manual. Service support ™ To expedite the return process outside of the United States, contact the nearest Emerson representa- tive. Within the United States, call the Emerson Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
  • Page 25: Safety Instrumented Systems

    For system details using HART , reference the Rosemount 3051S HART Reference Manual.  ™ For system details using Fieldbus, reference the Rosemount 3051S F Fieldbus Reference  OUNDATION Manual. For system details using wireless, reference the Rosemount 3051S Wireless Reference Manual.
  • Page 26: Specifications And Reference Data

    Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Section 8 Specifications and Reference Data Performance specifications ™ 8.1.1 Rosemount 3051SHP For zero-based spans, reference conditions, silicone oil fill, C-276 isolating diaphragm, coned and threaded process connections, digital trim values set to equal range points.
  • Page 27 Goods are warranted for 12 months from the date of initial installation of 18 months from the date of shipment by seller, whichever period expires first. Three-year and five-year warranty apply to date of shipment by seller. Rosemount Ultra transmitters have a limited warranty of 15 years from date of shipment. All other provisions of Emerson standard limited warranty remain the same. 8.1.8...
  • Page 28 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 8.1.11 Line pressure effect (DP measurement only) Differential pressure range Zero error Span error Range 6 ±0.1% URL per 1000 psi ±0.3% of reading per 1000 psi Range 7 ±0.1% URL per 1000 psi ±0.2% of reading per 1000 psi...
  • Page 29: Functional Specifications

    Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Functional specifications 8.2.1 Range and sensor limits Differential pressure range Range 6 –250 inH O (-623 mbar) 250 inH O (623 mbar) Range 7 –700 inH O (–1,74 bar) 700 inH...
  • Page 30 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Power supply External power supply required. Rosemount 3051SHP: 10.5 to 42.4 Vdc with no load  Rosemount 3051SHP with Advanced HART Diagnostics Suite:  12 to 42.4 Vdc with no load...
  • Page 31 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 The device dashboard presents the diagnostics in a graphical, task-based interface that provides single click access to critical process/device information and descriptive graphical troubleshooting. Suite includes: SPM, power advisory, status log, variable log, advanced process alerts, service alerts, and time stamp capability.
  • Page 32 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Software upgrade in the field Software for the Rosemount 3051SHP with F Fieldbus is easy to upgrade in the field using the OUNDATION Fieldbus “Common Device Software Download” procedure. OUNDATION ™...
  • Page 33: Update Rate

    Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Block Execution time Integrator 20 milliseconds Output Splitter 20 milliseconds Control Selector 20 milliseconds Fully compensated mass flow block (option code H01) Calculates fully compensated mass flow based on differential pressure with external process pressure and temperature measurements over the Fieldbus segment.
  • Page 34: Temperature Limits

    Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 8.2.12 Power module Field replaceable, keyed connection eliminates the risk of incorrect installation, Intrinsically Safe Lith- ium-thionyl chloride Power Module with polybutadine terephthalate (PBT) enclosure. Ten-year life at one minute update rate.
  • Page 35 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Storage –50 to 185 °F (–46 to 85 °C) With LCD display: –40 to 185 °F (–40 to 85 °C) With wireless output: –40 to 185 °F (–40 to 85 °C)
  • Page 36: Physical Specifications

    Emerson is not in a position to evaluate or guarantee the compatibility of the process fluid or other process parameters with the product, options, configuration or materials of construction selected.
  • Page 37: Electrical Connections

    Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 8.3.2 Electrical connections –14 NPT, G , and M20 x 1 conduit. HART interface connections fixed to terminal block for output code A and X. 8.3.3 Process connections Autoclave connection or seals 8.3.4...
  • Page 38 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Remote antenna (WN) Fiberglass omni-directional antenna 8.3.10 Power module Field replaceable, keyed connection eliminates the risk of incorrect installation, Intrinsically Safe Lith- ium-thionyl chloride power module with PBT enclosure 8.3.11...
  • Page 39 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Item Weight in lb (kg) Wireless extended cover 0.7 (0,3) LCD display 0.1 (0,04) Junction box terminal block 0.2 (0,1) PlantWeb terminal block 0.2 (0,1) Power module 0.5 (0,2) Display only.
  • Page 40: Dimensional Drawings

    Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Dimensional drawings Figure 1-18. PlantWeb Housing Side view Front view 5.17 4.20 (131,3) (106,7) 7.70 (195,5) 8.25 (209,4) 6.71 (170,4) 90.0° 3.53 6.88 (89,7) (174,8) 11.16 (283,5) 4.20 (106,7) A. Digital display cover D.
  • Page 41 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-19. Other Housings Quick connect Junction box 1.50 3.45 (38,1) (87,6) 5.88 (149,2) 6.43 (163,2) Dimensions are in inches (millimeters). Figure 1-20. Remote Meter Option 5.17 (131,3) 5.20 (132,0)
  • Page 42 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-21. High Gain, Remote Mount Antenna (WN Option) 20.2 (513) A. Antenna B. Mounting bracket C. Lightning arrester D. 25 ft (7,6 m) cable E. Min drip loop Ø12-in. (0.3 m) Dimensions are in inches (millimeters).
  • Page 43 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Figure 1-22. Traditional Mounting Configurations Pipe mount Panel mount 6.400 (162,56) 2.810 (71,37) 6.43 (163,2) 4.94 (125,4) Dimensions are in inches (millimeters). Figure 1-23. Remote Display Mounting Configurations (B4 Bracket)
  • Page 44: Transmitter Options

    Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 8.4.1 Options Transmitter options Standard configuration Unless otherwise specified, transmitter is shipped as follows: Engineering units Rosemount 3051SHP O (Range 6 and 7) psi (Range 8) 0 (engineering units above)
  • Page 45 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 8.4.3 Tagging (three options available) Standard SST hardware tag is wired to the transmitter. Tag character height is 0.125-in. (3,18 mm),  56 characters maximum. Tag may be permanently stamped on transmitter nameplate upon request, 56 characters ...
  • Page 46: Ordering Information

    316 stainless steel construction with stainless steel bolts  Other publications For additional information, go to Emerson.com. Ordering information Table 1-4. Rosemount 3051SHP Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
  • Page 47 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Table 1-4. Rosemount 3051SHP Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
  • Page 48 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Table 1-4. Rosemount 3051SHP Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
  • Page 49 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Table 1-4. Rosemount 3051SHP Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
  • Page 50 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Table 1-4. Rosemount 3051SHP Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
  • Page 51 18. Not available with Housing code 7J. 19. See the Rosemount 3051S Reference Manual for cable requirements. Contact an Emerson representative for additional information. 20. NACE compliant wetted materials are identified by Footnote 21. Not available with output code F or X. Not available with housing code 7J.
  • Page 52: Product Certifications

    European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Installing Equipment in North America ®...
  • Page 53 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 Canada Canada Explosion-proof, Dust Ignition-proof, Division 2 Certificate: 1143113 Standards: CAN/CSA C22.2 No. 0-10, CSA C22.2 No. 25-1966 (R2014), CSA C22.2 No. 30-M1986 (R2012), CSA C22.2 No. 94.2-07, CSA C22.2 No. 213-M1987 (R2013), CAN/CSA-C22.2 No.
  • Page 54 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
  • Page 55 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
  • Page 56 7. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7 J impact test. 8. The Rosemount 3051S SuperModule must be securely screwed in place to maintain the ingress protection of the enclosure.
  • Page 57 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
  • Page 58 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
  • Page 59 Manual Supplement Rosemount 3051S High Pressure 00809-0100-4851, Rev AA 2017 EAC – Belarus, Kazakhstan, Russia Technical Regulation Customs Union (EAC) Flameproof and Dust Certificate: RU C-US.AA87.B.00378 Markings: Ga/Gb Ex d IIC T6…T4 X Ex tb IIIC T105°C T 95°C Db X Ex ta IIIC T105°C T...
  • Page 60 Terms and Enquiries@AP.Emerson.com Conditions of Sale page. The Emerson logo is a trademark and service mark of Emerson Electric Co. SmartPower, SuperModule, Saturn, PlantWeb, Rosemount, and Middle East and Africa Regional Office Rosemount logotype are trademarks of Emerson. Emerson Automation Solutions HART and WirelessHART are registered trademarks of the FieldComm Group.

Table of Contents