Emerson Rosemount 3051SF series Quick Start Manual
Emerson Rosemount 3051SF series Quick Start Manual

Emerson Rosemount 3051SF series Quick Start Manual

3051s series pressure transmitter; 3051sf series flowmeter
Hide thumbs Also See for Rosemount 3051SF series:

Advertisement

Rosemount
and Rosemount 3051SF Series Flowmeter
®
with HART
3051S Series Pressure Transmitter
Protocol
Quick Start Guide
00825-0100-4801, Rev MC
August 2016

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 3051SF series

  • Page 1 Quick Start Guide 00825-0100-4801, Rev MC August 2016 ™ Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter ® with HART Protocol...
  • Page 2: Table Of Contents

    August 2016 Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 3051S Series Pressure Transmitters. It also provides the basic electronic guidelines for the Rosemount 3051SFA Reference Manual, Rosemount 3051SFC Reference Manual, and Rosemount 3051SFP Reference Manual. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting.
  • Page 3: Mount The Transmitter

    Quick Start Guide August 2016 1.0 Mount the transmitter 1.1 Liquid flow applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the Flow drain/vent valves are oriented above the process.
  • Page 4 If the transmitter requires the use of a mounting bracket, use the images below ™ for instructions on how to properly mount the transmitter using the Emerson Process Management provided mounting brackets. Use only bolts provided with the transmitter or sold as Emerson spare parts.
  • Page 5 If the transmitter installation requires assembly of the process flanges, manifolds, or flange adaptors, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 1 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 6 August 2016 Quick Start Guide Figure 2. Proper Bolt Installation A. Bolt B. Sensor module Table 1. Torque Values for the Flange and Flange Adaptor Bolts Bolt material Head markings Initial torque Final torque Carbon Steel (CS) 300 in-lb 650 in-lb Stainless Steel (SST) 150 in-lb 300 in-lb...
  • Page 7: Consider Housing Rotation

    Quick Start Guide August 2016 1.7 In-line gage transmitter orientation The low side pressure port (atmospheric reference) on the in-line gage transmitter is located under the sensor module neck label. (See Figure 3 Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so any contaminants can drain away.
  • Page 8: Set Switches And Jumpers

    August 2016 Quick Start Guide 3.0 Set switches and jumpers If alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm “high” and the security “off”. 1. Do not remove the transmitter covers in explosive atmospheres when the circuit is live.
  • Page 9: Connect Wiring And Power Up

    Quick Start Guide August 2016 4.0 Connect wiring and power up Use the following steps to wire the transmitter: 1. Remove and discard orange conduit plugs. 2. Remove the housing cover labeled “Field Terminals.” 3. Connect the positive lead to the “+” terminal, and the negative lead to the “–” terminal.
  • Page 10 August 2016 Quick Start Guide 4.1 Signal wiring grounding Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the sensor module and inside the terminal compartment. These grounds are used when transient protection terminal blocks are installed or to fulfill local regulations.
  • Page 11 Quick Start Guide August 2016 A cable is required for wiring between the transmitter and remote mount LCD  display. The cable length is limited to 100 ft. 50 ft (option M8) or 100 ft (option M9) cable is provided for wiring between ...
  • Page 12 August 2016 Quick Start Guide Figure 8. Remote Mount Display Wiring Diagram (white) 24 AWG (blue) 24 AWG (black) 22 AWG (red) 22 AWG A. Remote mount display B. Junction box housing C. 4–20 mA Note Wire colors provided on page 12 are per Madison AWM Style 2549 cable.
  • Page 13 Quick Start Guide August 2016 4.3 Quick connect wiring (if applicable) As standard, the Rosemount 3051S Quick Connect arrives properly assembled to the sensor module and is ready for installation. Cordsets and field wireable connectors (in shaded area) are sold separately. Figure 9.
  • Page 14: Power Supply

    August 2016 Quick Start Guide Figure 10. Quick Connect Housing Pin-Out “+” “ ” A. Ground B. No connection Note For other wiring details, refer to pin-out drawing and the cordset manufacturer’s installation instructions. 4.4 Conduit electrical connector wiring (option GE or GM) For Rosemount 3051S with conduit electrical connectors GE or GM, refer to the cordset manufacturer’s installation instructions for wiring details.
  • Page 15: Verify Configuration

    Quick Start Guide August 2016 5.0 Verify configuration Use any HART-compliant master to communicate with and verify configuration of the Rosemount 3051S. 5.1 Field Communicator user interface Fast Key sequences vary with the device driver revision. The traditional interface Fast Key sequences apply to DD Rev. 8 or older and they can be found on page 16 The device dashboard Fast Key sequences apply to DD Rev.
  • Page 16 August 2016 Quick Start Guide  A check ( ) indicates the basic configuration parameters. At a minimum, these parameters should be verified as part of the configuration and startup procedure. Table 2. Traditional Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key Sequence Function Fast Key sequence...
  • Page 17 Quick Start Guide August 2016 Table 2. Traditional Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key Sequence Function Fast Key sequence Transmitter Security (Write Protect) 1, 3, 4, 5  Units (Process Variable) 1, 3, 2 Upper Sensor Trim 1, 2, 3, 3, 3 Zero Trim...
  • Page 18: Trim The Transmitter

    August 2016 Quick Start Guide 6.0 Trim the transmitter Transmitters are shipped fully calibrated per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit). 6.1 Zero trim A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects.
  • Page 19: Product Certifications

    Quick Start Guide August 2016 8.0 Product Certifications Rev 1.9 8.1 European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at EmersonProcess.com/Rosemount.
  • Page 20 August 2016 Quick Start Guide FM FISCO Certificate: 3012350 Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 2005, NEMA 250 – 2003 ≤ ≤ Markings: IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C +60 °C);...
  • Page 21 Quick Start Guide August 2016 8.6 Europe ATEX Flameproof Certificate: KEMA 00ATEX2143X Standards: EN 60079-0:2012, EN 60079-1:2007, EN 60079-26:2007 (3051SFx models with RTD are certified to EN60079-0:2006) ≤ ≤ Markings: II 1/2 G Ex d IIC T6…T4 Ga/Gb, T6(–60 °C +70 °C), ≤...
  • Page 22 August 2016 Quick Start Guide ATEX FISCO Certificate: BAS01ATEX1303X Standards: EN 60079-0:2012, EN 60079-11:2012 ≤ ≤ Markings: II 1 G Ex ia IIC T4 Ga, T4(–60 °C +70 °C) Parameter FISCO Voltage U 17.5 V Current I 380 mA Power P 5.32 W Capacitance C Inductance L...
  • Page 23 Quick Start Guide August 2016 Note RTD Assembly is not included with the Rosemount 3051SFx Type n Approval. 8.7 International IECEx Flameproof and Dust Certificate: IECEx KEM 08.0010X (Flameproof) Standards: IEC 60079-0:2011, IEC 60079-1:2007, IEC 60079-26:2006 (3051SFx models with RTD are certified to IEC 60079-0:2004) ≤...
  • Page 24 August 2016 Quick Start Guide Model 3051S …A…M7, M8, or M9; 60 μH 3051SF …A…M7, M8, or M9; 30 V 300 mA 1.0 W 12 nF 3051SAL…C… M7, M8, or M9 33 μH 3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 3051SAL…M7, M8, or M9...
  • Page 25 Quick Start Guide August 2016 IECEx FISCO Certificate: IECEx BAS 04.0017X Standards: IEC 60079-0:2011, IEC 60079-11:2011 ≤ ≤ Markings: Ex ia IIC T4 Ga, T4(–60 °C +70 °C) Parameter FISCO Voltage U 17.5 V Current I 380 mA Power P 5.32 W Capacitance C Inductance L...
  • Page 26 August 2016 Quick Start Guide IECEx Type n Certificate: IECEx BAS 04.0018X Standards: IEC 60079-0:2011, IEC 60079-15:2010 ≤ ≤ Markings: Ex nA IIC T5 Gc, (–40 °C +85 °C) Special Condition for Safe Use (X): 1. The equipment is not capable of withstanding the 500 V insulation test required by clause 6.5 of EN 60079-15:2010.
  • Page 27 Quick Start Guide August 2016 8.9 China China Flameproof and Dust Ignition-proof Certificate: 3051S: GYJ16.1249X 3051SFx: GYJ11.1711X 3051S-ERS: GJY15.1406X Standards: 3051S: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2013, GB12476.5-2013 3051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2000 3051S-ERS: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010 Markings: 3051S: Ex d IIC T6…T4; Ex tD A20 T 105 °C T 95 °C;...
  • Page 28 August 2016 Quick Start Guide 10. Maintenance should be done in non-hazardous location. 11. End users are not permitted to change any components inside. 12. When installation, use and maintenance of transmitter, observe following standards: GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”...
  • Page 29 Quick Start Guide August 2016 4. The product should be used with Ex-certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus. 5.
  • Page 30 August 2016 Quick Start Guide GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”. 8.10 EAC – Belarus, Kazakhstan, Russia EM Technical Regulation Customs Union (EAC) Flameproof Certificate: RU C-US.AA87.B.00094 Markings: Ga/Gb Ex d IIC T6…T4 X Technical Regulation Customs Union (EAC) Intrinsic Safety Certificate: RU C-US.AA87.B.00094...
  • Page 31 Quick Start Guide August 2016 8.14 Additional Certifications SBS American Bureau of Shipping (ABS) Type Approval Certificate: 00-HS145383-6-PDA Intended Use: Measure gauge or absolute pressure of liquid, gas or vapor applications on ABS classed vessels, marine, and offshore installations. SBV Bureau Veritas (BV) Type Approval Certificate: 31910/A0 BV Requirements: Bureau Veritas Rules for the Classification of Steel Ships...
  • Page 32 August 2016 Quick Start Guide Figure 15. Rosemount 3051S Declaration of Conformity...
  • Page 33 Quick Start Guide August 2016...
  • Page 34 August 2016 Quick Start Guide...
  • Page 35 Quick Start Guide August 2016...
  • Page 36 August 2016 Quick Start Guide...
  • Page 37 Quick Start Guide August 2016 Rosemount 3051S China RoHS List of Rosemount 3051S Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6) (PBB) (PBDE) Electronics...
  • Page 38 +65 6777 8211 Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/pages/Terms-of-Use.aspx +65 6777 0947 The Emerson logo is a trademark and service mark of Emerson Enquiries@AP.EmersonProcess.com Electric Co. PlantWeb, SuperModule, Rosemount, and Rosemount logotype Middle East and Africa Regional Office are trademarks of Emerson Process Management.