Specifications and Reference Data
October 2016
Liquid Level Transmitter (Rosemount 3051SAL)
Overpressure limit is dependent on the flange rating or sensor
rating (whichever is lower). Use Instrument Toolkit to ensure the
seal system meets all pressure and temperature limits.
A.2.4 Static pressure limits
Coplanar Sensor Module (Single Variable)
Operates within specifications between static line pressures of:
Rosemount 3051S_CD
3051SMV_ _3 or 4
3051SF_3, 4, 7, or D
0
0.5 psia to 750 psig (0,03 to 51,71 bar)
1
0.5 psia to 2000 psig (0,03 to 137,9 bar)
2
0.5 psia to 3626 psig (0,03 to 150 bar)
3
0.5 psia to 3626 psig (0,03 to 150 bar)
4
0.5 psia to 3626 psig (0,03 to 150 bar)
5
0.5 psia to 3626 psig (0,03 to 150 bar)
1.
The static pressure limit of a DP Sensor with the P9 option is 4500 psig
(310,3 bar). The static pressure limit of a DP Sensor with the P0 option is
6092 psig (420 bar).
Coplanar Multivariable Sensor Module (Rosemount 3051SMV_
_1 or 2, Rosemount 3051SF_1, 2, 5, or 6)
Operates within specifications between static line pressures of 0.5
psia (0,03 bar) and the values in the table below:
Static
pressure
Range 1
Range 3
800 psi
GP/AP
(57,91 bar)
Range 4
2000 psi
GP/AP
(137,9 bar)
A.2.5 Burst pressure limits
Coplanar Sensor Module (Rosemount 3051S_C, Rosemount
3051SMV, Rosemount 3051SF)
10000 psig (689,5 bar)
In-Line Sensor Module (Rosemount 3051S_T)
Ranges 1-4: 11000 psi (758,4 bar)
Range 5: 26000 psi (1792,64 bar)
Specifications and Reference Data
(1)
DP Sensor
Differential pressure
Range 2
Range 3
800 psi
800 psi
(57,91 bar)
(57,91 bar)
3626 psi
3626 psi
(250 bar)
(250 bar)
A.2.6 Temperature Limits
Ambient
-40 to 185 °F (-40 to 85 °C)
(1)
With LCD display
: -40 to 175 °F (-40 to 80 °C)
With option code P0: -20 to 185 °F (-29 to 85 °C)
1.
LCD display may not be readable and LCD display updates will be slower at
temperatures below -4 °F (-20 °C).
Storage
-50 to 185 °F (-46 to 85 °C)
With LCD display: -40 to 185 °F (-40 to 85 °C)
With Wireless Output: -40 to 185 °F (-40 to 85 °C)
Process temperature limits
At atmospheric pressures and above:
Coplanar sensor module
Rosemount 3051S_C, Rosemount 3051SMV, Rosemount
(1)(2)
Silicone Fill Sensor
with Coplanar Flange
with Traditional Flange
with Level Flange
with Rosemount 305
Integral Manifold
(1)(5)
Inert Fill Sensor
In-Line sensor module
Rosemount 3051S_T
(1)
Silicone Fill Sensor
(1)
Inert Fill Sensor
Rosemount 3051SAL Level Transmitter
SYLTHERM
XLT
(8)
Silicone 704
Silicone 200
Inert (Halocarbon)
Glycerin and Water
®
Neobee M-20
Propylene Glycol and Water
1.
Process temperatures above 185 °F (85 °C) require derating the ambient
limits by a 1.5:1 ratio. For example, for process temperature of 195 °F (91
°C), new ambient temperature limit is equal to 170 °F (77 °C). This can be
determined as follows:
(195 °F - 185 °F) x 1.5 = 15 °F,
185 °F - 15 °F = 170 °F
2.
212 °F (100 °C) is the upper process temperature limit for DP Range 0.
3.
220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below
0.5 psia.
4.
-20 °F (-29 °C) is the lower process temperature limit with option code P0.
Reference Manual
00809-0200-4801, Rev DA
3051SF
-40 to 250 °F (-40 to 121 °C)
-40 to 300 °F (-40 to 149 °C)
-40 to 300 °F (-40 to 149 °C)
-40 to 300 °F (-40 to 149 °C)
-40 to 185 °F (-40 to 85 °C)
-40 to 250 °F (-40 to 121 °C)
-22 to 250 °F (-30 to 121 °C)
-102 to 293 °F (-75 to 145 °C)
32 to 401 °F (0 to 205 °C)
-49 to 401 °F (-45 to 205 °C)
-49 to 320 °F (-45 to 160 °C)
5 to 203 °F (-15 to 95 °C)
5 to 401 °F (-15 to 205 °C)
5 to 203 °F (-15 to 95 °C)
(3)
(3)(4)
(3)
(3)(4)
(6)(7)
(3)
(3)
111