4 SPECIFICATION OPERATION

Items
Operating Voltage
Power Consumption
Alternator Input Range
3Phase 4Wire
3Phase 3Wire
Single Phase 2Wire
2Phase 3Wire
Alternator Frequency
DC Generator Voltage Input
Load DC Current Input
Speed sensor voltage
Speed sensor Frequency
Start Relay Output
Fuel Relay Output
Programmable Relay Output (1)
Programmable Relay Output (2)
Programmable Relay Output (3)
Programmable Relay Output (4)
Programmable Relay Output (5)
Programmable Relay Output (6)
RS485 Port
Internet Access
Vibration Test
Shock Test
Bump Test
Safety Rule Requirements
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Table 4 - Technical Parameters
DC8.0V to DC35.0V, Continuous Power Supply.
<8W (standby ≤3W)
AC15V-AC 360V (ph-N)
AC30V - AC620V (ph-ph)
AC15V - AC360V (ph-N)
AC15V - AC360V (ph-N)
50 /60Hz
DC 0V-10V (Converter post voltage, ratio can be set)
DC 4mA-20mA (Converter post current, ratio can be set)
1.0V to 24.0V (RMS)
10,000 Hz (max.)
16 A DC28V at supply output
16 A DC28V at supply output
7A DC28V supply output
7A DC28V supply output
7A DC28V supply output
7A AC250V voltage free output
8A AC250V voltage free output
8A AC250V voltage free output
Isolated, half-duplex, 9600 baud rate, longest communication
distance 1000m;
10Mbit
5 - 8 Hz: ± 7.5 mm
8 - 500 Hz: 2 g
IEC 60068-2-6
50g, 11ms, half-sine, complete shock test from three directions;
For each test, 18 shocks totally
IEC 60068-2-27
25g, 16ms, half-sine;
IEC 60255-21-2
Based on EN 61010-1 mounting category (over voltage) III, 300V,
2020-02-20
Contents
Version 1.0
Page 10 of 69