No.
23
Fuel Pre-supply
24
Generator Excite
25
Pre-lubricate
26
Remote Control
27
Reserved
28
Reserved
29
Close Generator
30
Open Breaker
31
Reserved
32
Reserved
33
Start Relay
34
Fuel Relay
35
Idle Control
36
Speed Raise Relay
37
Speed Drop Relay
38
Energise to Stop
39
Speed Drop Pulse
40
ECU Stop
41
ECU Power Supply
42
Speed Raise Pulse
43
Crank Success
44
Generator OK
45
Generator Available
46
Reserved
47
Reserved
48
Common Alarm
49
Common Trip and Stop
50
Common Shutdown
51
Common Trip
52
Common Warning
53
Reserved
54
Battery Over Voltage
55
Battery Under Voltage
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Type
the upper and lower limits.
Act in the period from crank to safety on time.
Output in the crank process; output for 2s again if Gen
frequency is lost in high speed period.
Act in the period from pre-heating to safety on time.
This port is controlled by communication (PC).
Control generator breaker to take load.
Control generator breaker to take off load.
Act at generator start, disconnect at waiting to stop.
Used for gensets with idle speed control; Pull in before
crank, disconnect at entering warming up period; Pull
in at stop idle process, and disconnect at genset
complete stop.
Act in the period of warming up.
Act in the period of stop idle and wait to stop running time.
Used for engines with ETS electromagnet. Close when
stop idle is over and open when pre-set ―ETS delay‖ is
over.
Act for 0.1s when controller enters into stop idle, used
to control part of ECU dropping to idle speed.
Used for ECU engine and control its stop.
Used for ECU engine and control its power.
Act for 0.1s when controller enters into warming up
delay; used to control part of ECU raising to normal
speed.
Close when a successful start signal is detected.
Act when generating is normal.
Act in period of generator ok to hi-speed cooling.
Act at genset common warning, common shutdown,
common trips alarm.
Act when common trip and stop alarm occurs.
Act when common shutdown alarm occurs.
Act when common trips alarm occurs.
Act when common warning alarm occurs.
Act when battery's over voltage warning alarm occurs.
Act when battery's low voltage warning alarm occurs.
2020-02-20
Description
Version 1.0
Page 44 of 69