Cummins Qsm11 (Import); Cummins Qsx15-Cm570 - Smartgen HGM8110DC-2 User Manual

Genset controller
Table of Contents

Advertisement

14.3 CUMMINS QSM11 (import)

It is suitable for CM570 engine control module. Engine type is QSM11 G1, QSM11 G2.
Terminals of controller
Fuel relay output
Start relay output
Terminals of controller
CAN GND
CAN(H)
CAN(L)
Engine type: Cummins ISB

14.4 CUMMINS QSX15-CM570

It is suitable for CM570 engine control module. Engine type is QSX15 etc.
Terminals of controller
Fuel relay output
Start relay output
Terminals of controller
CAN GND
CAN(H)
CAN(L)
Engine type: Cummins QSX15-CM570
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Table 23 - C1 Pin Connector
C1 connector
5&8
-
Table 24 – 3-Pin Data Link Connector
3 pins data link connector
C
A
B
Table 25 – 50-Pin Connector
50 pins connector
38
-
Table 26 – 9-Pin Connector
9 pins connector
SAE J1939 shield-E
SAE J1939 signal-C
SAE J1939 return-D
2020-02-20
Remark
Externally extend relay, when fuel is
outputting, connect Terminal 5 and Terminal
8 of C1 connector.
Connect to starter coil directly.
Remark
CAN communication shielding line
(connect with ECU terminal only).
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Remark
Oil spout switch
Connect to starter coil directly.
Remark
CAN communication shielding line
(connect with ECU terminal only).
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.