No.
Items
Over Freq.
10
Shutdown
Under Freq.
11
Shutdown
12
Over Volt. Warn
Under Volt.
13
Warn
14
Over Freq. Warn
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Parameters
Defaults
(0-3600)s
3
0: Disable
1
1: Enable
(0~200)%
114
(0-3600)s
2
0: Disable
1
1: Enable
(0~200)%
80
(0-3600)s
3
0: Disable
1
1: Enable
(0~200)%
110
(0~200)%
108
(0-3600)s
5
0: Disable
1
1: Enable
(0~200)%
84
(0~200)%
86
(0-3600)s
5
0: Disable
1
1: Enable
(0~200)%
110
2020-02-20
Description
voltage; start alarm handle when it is below
this value.
Alarm starts when voltage reaches alarm
value and this delay time is expired.
Start to detect alarms when it is enabled;
not detect alarms when disabled;
Set value is percentage of AC Gen rated
freq. start alarm handle when it is above
this value.
Alarm starts when freq. reaches alarm
value and this delay time is expired.
Start to detect alarms when it is enabled;
not detect alarms when disabled;
Set value is percentage of AC Gen rated
freq. start alarm handle when it is below
this value.
Alarm starts when freq. reaches alarm
value and this delay time is expired.
Start to detect alarms when it is enabled;
not detect alarms when disabled;
Set value is percentage of AC Gen rated
voltage; start alarm handle when it is
above this value.
Set value is percentage of AC Gen rated
voltage; when alarm is active and voltage
is below return value, alarm can be cleared
automatically.
Alarm starts when voltage reaches alarm
value and this delay time is expired.
Start to detect alarms when it is enabled;
not detect alarms when disabled;
Set value is percentage of AC Gen rated
voltage; start alarm handle when it is below
this value.
Set value is percentage of AC Gen rated
voltage; when alarm is active and voltage
is above return value, alarm can be cleared
automatically.
Alarm starts when voltage reaches alarm
value and this delay time is expired.
Start to detect alarms when it is enabled;
not detect alarms when disabled;
Set value is percentage of AC Gen rated
freq. start alarm handle when it is above
Version 1.0