Smartgen HGM8110DC-2 User Manual page 51

Genset controller
Table of Contents

Advertisement

No.
21
Alarm Stop Inhibit
22
Instrument Mode
23
Reserved
24
Reset Maintenance Alarm
25
Reserved
High Temperature
26
Shutdown
Low Oil Pressure
27
Shutdown
28
Remote Start On Load
29
Remote Start Off Load
30
Manual Start Input
31
Reserved
32
Reserved
33
Simulate Stop Key
34
Simulate Manual Key
35
Reserved
36
Simulate Auto Key
37
Simulate Start Key
Simulate Generator Close
38
Key
Simulate Generator Open
39
Key
40
Reserved
41
Reserved
42
Reserved
43
Reserved
44
Reserved
45
Reserved
46
Reserved
47
Alt. Config. 1 Active
48
Alt. Config. 2 Active
49
Alt. Config. 3 Active
50-55
Reserved
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Type
All shutdown alarms are prohibited except emergence
stop.(Means battle mode or override mode)
All outputs are prohibited in this mode.
Controller will set maintenance time and date as default when
input is active.
Connected sensor digital input.
Connected sensor digital input.
In Auto mode, when input is active, genset can be started
automatically and take load after genset normal running;
when input is inactive, genset will stop automatically.
In Auto mode, when input is active, genset can be started
automatically and NOT take load after genset normal running;
when input is inactive, genset will stop automatically.
In Manual mode, when input active, genset will start
automatically; when input inactive, genset will stop
automatically.
An external button can be connected and pressed as
simulate panel.
An external button can be connected and pressed as
simulate panel.
When input port is active, users can set different parameters
to make it easy to select current configuration via input port.
2020-02-20
Description
Version 1.0
Page 51 of 69