No.
Items
Timers
1
Start Delay
2
Stop Delay
3
Preheat Delay
4
Cranking Time
5
Crank Rest Time
6
Safety On Delay
7
Start Idle Time
Warming Up
8
Time
9
Cooling Time
10
Stop Idle Time
ETS Solenoid
11
Hold
12
Wait Stop Delay
13
After Stop Time
Engine
1
Engine Type
2
Flywheel Teeth
3
Rated Speed
4
Speed On Load
Loss of Speed
5
Signal
6
Action
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Parameters
Defaults
(0~3600)s
1
(0~3600)s
1
(0~3600)s
0
(3~60)s
8
(3~60)s
10
(0~3600)s
10
(0~3600)s
0
(0~3600)s
10
(0~3600)s
10
(0~3600)s
0
(0~3600)s
20
(0~3600)s
0
(0~3600)s
0
(0~39)
0
(10~300)
118
(0~6000)r/min
1500
(0~100)%
90
(0~3600)s
5
(0~1)
0
2020-02-20
Description
Time from mains abnormal or remote start
signal is active to start genset.
Time from mains normal or remote start
signal is deactivated to genset stop.
Time of pre-powering heat plug before
starter is powered up.
Time of starter power up
The waiting time before second power up
when engine start fail.
Alarms for low oil pressure, high
temperature, under speed, under
frequency /voltage, charge fail are inactive.
Idle running time of genset when starting.
Warming time between genset switch on
and normal running.
Radiating time before genset stop, after it
unloads.
Idle running time when genset stop.
The time of powering up the electromagnet
during stop procedure.
Time between ending of genset idle delay
and stopped when ―ETS time‖ is set as 0;
Time between ending of ETS hold delay
and stopped when ―ETS Hold output time‖
is not 0.
Time between genset stopped and standby
Default: Non ECU engine
When connected to J1939 engine, choose
the corresponding type.
Tooth number of the engine, for judging of
crank disconnect conditions and inspecting
of engine speed. See the installation
instructions.
Offer standard to judge over/under/loading
speed.
Setting value is percentage of rated speed.
Controller detects when it is ready to load.
It won't switch on when speed is under
loading speed.
Time from detecting speed is 0 to confirm
the action.
0: Warning;
1: Shutdown