Enter ―After Stop Time‖ (if configured) as soon as generator stops. Otherwise, controller enters stop
6)
failure and sends ―Fail to Stop‖ warning alarm at the same time. (If gen-set stops successfully after
warning of ―Failed to Stop‖, it will enter ―After Stop Time‖ and removes alarm automatically.)
Enter ―Generator at Rest‖ as soon as ―After Stop Time‖ is over.
7)

5.5 MANUAL START/STOP OPERATION

1)
MANUAL START: Press
to start generator, it can automatically detect crank disconnect, and generator accelerates to
high-speed running automatically. If high water temperature, low oil pressure, over speed and abnormal
voltage during generator running, controller can protect genset to stop quickly. Press
open or close the switch. (Please refer to No.3~8 of Auto start operation for detail procedures, where the
only difference is the way of switch open and close).
2)
MANUAL STOP: Press
stop operation for detail procedures).
NOTE: In ―manual mode‖, the procedures of ATS please refer to ATS procedure of generator in this manual.
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
, controller enters into manual mode and its indicator is light on. Press
and it can stop the running generators. (Please refer to No.2~7 of Auto
2020-02-20
Version 1.0
Page 17 of 69