No.
Function
9
Charger(D+)
10
Aux. Input 1
11
Aux. Input 2
12
Aux. Input 3
13
Aux. Input 4
14
Aux. Input 5
15
Aux. Input 6
16
Magnetic Pickup
17
MP 2
18
MP 1
19
Aux. Input 7
20
21
Aux. Output 4
22
ECU CAN Internal
23
Resistance
24
ECU CAN H
25
ECU CAN L
CAN2 Internal
26
Resistance
27
CAN2 H
28
CAN2 L
CAN3 Internal
29
Resistance
30
CAN3 H
31
CAN3 L
RS485 Internal
32
Resistance
33
RS485A(+)
34
RS485B(-)
35
36
Aux. Output 5
37
38
Aux. Output 6
39
40
DC Current +
41
DC Current -
42
DC Voltage +
43
DC Voltage -
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Cable Size
Connected with charger starter's D+ (WL) terminals.
2
1.0mm
Being hang up If there is no this terminal.
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
Connected with Speed sensor, shielding line is
2
0.5mm
recommended. (B-) has already connected with speed
sensor 2 inside the controller.
2
1.0mm
Ground connected is active (B-)
Normally close output, rated 7A
2
1.5mm
Public points of relay
Normally open output, rated 7A
Impedance-120Ω shielding wire is recommended, its
/
single-end earthed. (120Ω resistor is connected inside
2
0.5mm
for Terminal 23 and Terminal 25; short connect Terminal
2
23 and Terminal 24 at using.)
0.5mm
Impedance-120Ω shielding wire is recommended, its
/
single-end earthed. (120Ω resistor is connected inside
2
0.5mm
for Terminal 26 and Terminal 28; short connect Terminal
2
26 and Terminal 27 at using.)
0.5mm
Impedance-120Ω shielding wire is recommended, its
/
single-end earthed. (120Ω resistor is connected inside
2
0.5mm
for Terminal 29 and Terminal 31; short connect Terminal
2
29 and Terminal 30 at using.)
0.5mm
Impedance-120Ω shielding wire is recommended, its
/
single-end earthed. (120Ω resistor is connected inside
2
0.5mm
for Terminal 32 and Terminal 34; short connect Terminal
2
32 and Terminal 33 at using.)
0.5mm
2
2.5mm
Normally close output, rated 8A
2
2.5mm
Normally open output, rated 8A
2
2.5mm
Relay common port
2
2.5mm
Normally open output, rated 8A
2
2.5mm
Relay common port
2
1.0mm
External connected to DC positive of current transformer
External connected to DC negative of current
2
1.0mm
transformer
2
1.0mm
External connected to DC positive of PT
2
1.0mm
External connected to DC negative of PT
2020-02-20
Remarks
Details see Table
15
Details see Table
15
Details see Table
14
Details see Table
14.
Version 1.0
Page 28 of 69