Enable Definition Of Programmable Output Ports; Enable Definition Of Programmable Output Ports Form - Smartgen HGM8110DC-2 User Manual

Genset controller
Table of Contents

Advertisement

No.
Items
Relay Output Port 5
1
Contents Setting
2
Active Type
Relay Output Port 6
1
Contents Setting
2
Active Type

8.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS

8.2.1 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS FORM

Table 14 – Definition Content of Programmable Output Ports
No.
0
Not Used
1
Custom Period 1
2
Custom Period 2
3
Custom Period 3
4
Custom Period 4
5
Custom Period 5
6
Custom Period 6
7
Custom Combined 1
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13
Oil Pre-heat Output
14
Reserved
15
Reserved
16
Reserved
17
Air Flap Control
18
Audible Alarm
19
Louver Control
20
Fuel Pump Control
21
Heater Control
22
Cooler Control
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Parameters
Defaults
(0~299)
38
(0~1)
0
(0~299)
48
(0~1)
0
Type
For function description details please see the
following.
Act at over speed shutdown and emergency stop;
Engine air inletting can be closed.
Act at warning, shutdown, electric trip; Annunciator can
be connected externally; When flexible input "Alarm
Mute" is active, it can be prohibited to output.
Act at generator start, disconnect after genset
complete stop.
It is controlled by level sensor fuel pump controlling the
upper and lower limits.
It is controlled by temp sensor heating and controlling
the upper and lower limits.
It is controlled by temp sensor cooling and controlling
2020-02-20
Description
1: Output(N/C)
Energise to Stop. See Table 14
0: Output(N/O)
1: Output(N/C)
Common Alarm. See Table 14
0: Output(N/O)
1: Output(N/C)
Description
Version 1.0