Figure 43: Clearance Requirements for Airflow and Hardware Maintenance for EX2300-48MP
Switches
The power cord retainer clips in EX2300 switches except the EX2300-24MP and EX2300-48MP
switches extend out of the rear of the chassis by 3 in. (7.6 cm).
• Allow at least 6 in. (15.2 cm) of clearance on the side between devices that have fans installed. Allow
2.8 in. (7 cm) between the side of the chassis and any non-heat-producing surface such as a wall. For
the cooling system to function properly, the airflow around the chassis must be unrestricted.
Figure 44 on page 72
except the EX2300-24MP switch.
Figure 46 on page 73
shows the airflow in EX2300 switches with 24 ports with PoE capability,
Figure 45 on page 73
shows the airflow in EX2300 switches with 48 ports with PoE capability,
shows the airflow in EX2300-24MP switch.
71