Juniper EX2300 Series Hardware Manual page 146

Hide thumbs Also See for EX2300 Series:
Table of Contents

Advertisement

Table 37: Parts Required for Connecting an EX Series Switch to Earth Ground
Switch
Earthing
Terminal
Location
EX8208
Left side of
the chassis
EX8216
Two earthing
terminals:
Left side
of the
chassis
Rear
panel of
the
chassis
NOTE: You
must use
only one of
the two
protective
earthing
terminals.
Grounding
Grounding Lug
Cable
Specifications
Requirements
6 AWG
Panduit LCD2-14A-
(13.3 mm²),
Q or equivalent
minimum 90° C
—provided
wire, or as
permitted by
the local code
2 AWG
Panduit LCD2-14A-
(33.6 mm²),
Q or equivalent
minimum 90° C
—provided
wire, or as
permitted by
the local code
(Continued)
Screws and
Additional
Washers
Information
Two ¼ -20
x 0.5 in.
screws with
#¼" split-
washer
—provided
Two #¼" flat
washers—
provided
Two ¼ -20 x
0.5 in.
screws with
#¼" split-
washer
—provided
Two #¼" flat
washers—
provided
137