Table 37: Parts Required for Connecting an EX Series Switch to Earth Ground
Switch
Earthing
Terminal
Location
EX9204,
Rear panel of
EX9208,
the chassis
and
EX9214
EX9251
Rear panel of
the chassis
EX9253
Right side of
the chassis
Tools required for connecting an EX Series switch to earth ground:
• An electrostatic discharge grounding strap (provided)
• A Phillips (+) number 2 screwdriver to tighten the screws.
An AC–powered EX Series switch gains additional grounding when you plug the power supply in the
switch into a grounded AC power outlet by using an AC power cord appropriate for your geographical
location.
Grounding
Grounding Lug
Cable
Specifications
Requirements
One 6 AWG
Thomas& Betts
(13.3 mm²),
LCN6-14 or
minimum 90° C
equivalent—
wire, or one
provided
that complies
with the local
code
12 AWG
Panduit
(2.5 mm²),
LCD10-10A-L or
minimum 90° C
equivalent—
wire, or one
not provided
that complies
with the local
code—
not provided
14-10 AWG
Panduit
(2-5.3 mm²),
LCD10-14B-L or
minimum 90° C
equivalent—
wire, or one
provided
that complies
with the local
code—
not provided
(Continued)
Screws and
Additional
Washers
Information
See
Grounding
Two ¼ -20
Cable and Lug
x 0.5 in.
Specifications for
screws with
EX9200
#¼" split-
washer—
provided
Two #¼" flat
washers—
provided
Two 10-32
See
Grounding
screws—
Cable and Lug
provided
Specifications for
EX9200
Two M5 Pan
Head screws—
provided