Diagnostics and Troubleshooting

9
Diagnostics and Troubleshooting
Please note the following safety guidelines when errors occur:
9.1

Error Management

The PSENvip continuously carries out self-tests and output tests during operation. If an er-
ror is discovered, the following sequence is triggered:
}
An error identifier is shown on the display of the PSENvip receiver (see "Error messages"
in this chapter)
}
The error plus some additional diagnostic data is entered in a special data area on the
PSENvip (see "DIAGNOSTICS menu" in this chapter)
}
Execution of the error reaction.
The PSENvip's reaction to an error depends on the severity of that error.
9.1.1

Minor errors

Possible causes
}
Feasibility error
}
Internal error
Reaction of the PSENvip
}
The PSENvip switches to a HOLD state.
}
Outputs OSSD1/OSSD2 on the receiver are switched off.
}
In this state it is possible to make adjustments during initial commissioning and after a
tool change.
Remedy
}
Note the error message (see section entitled "Error messages").
}
Rectify the error.
}
Press the <ESC> key and return the PSENvip to the NORMAL OPERATION state.
Operating Manual PSENvip RL D P Set
1001641-EN-09
WARNING!
The press brake must be shut down immediately if the test reveals a
fault!
Failure to comply could result in a hazardous situation, which could lead
to serious injury and death.
In this case, have the safety equipment checked by qualified staff.