[Pr. PA02_Regenerative option (**REG)]

Initial value
00000000h
[Pr. PA02.0-1_Regenerative option selection]
Initial value
00h
Select a regenerative option.
Incorrect setting may cause the regenerative option to burn.
If a selected regenerative option is not for use with the servo amplifier, [AL. 037 Parameter error] occurs.
Other regenerative options cannot be used together with the FR-XC-(H).
The setting value of this servo parameter is disabled for the MR-J5D_-_G_.
00: Regenerative option is not used.
• No regenerative resistors are used on servo amplifiers with a capacity of 100 W.
• Built-in regenerative resistors are used on servo amplifiers with a capacity of 0.2 kW to 7 kW.
01: FR-XC-(H)
02: MR-RB032
03: MR-RB12
05: MR-RB30
06: MR-RB50 (A cooling fan is required.)
08: MR-RB31
09: MR-RB51 (A cooling fan is required.)
0B: MR-RB3N
0C: MR-RB5N (A cooling fan is required.)
0D: MR-RB14
0E: MR-RB34
1C: MR-RB3Z
1D: MR-RB5Z (A cooling fan is required.)
80: MR-RB1H-4
81: MR-RB3M-4 (A cooling fan is required.)
82: MR-RB3G-4 (A cooling fan is required.)
83: MR-RB5G-4 (A cooling fan is required.)
93: MR-RB3Y-4 (A cooling fan is required.)
94: MR-RB5Y-4 (A cooling fan is required.)
"1C" and "1D" are available on servo amplifiers with firmware version B6 or later.
Setting range
Refer to the relevant detail No.
Setting range
Refer to the text
Setting method
Common
Ver.
A0
1 SERVO PARAMETER DETAILS
1.2 Basic setting servo parameters group ([Pr. PA_ _ ])