6.13 PID control

 : PID control waiting time
 : PID control
6
 : Proportional gain
 : Integral gain
 : Differential gain
 : PID forward/reverse characteristics selection
• Function
[Parameter setting]






This function prevents the motor from running in the forward or reverse direction when it receives the
wrong operation signal.
Title
Function
Reverse-run prohibition
Using feedback signals (4 to 20mA, 0 to 5 V, 0 to 10V) from a detector, process control can be
exercised, for example, to keep the airflow, amount of flow or pressure constant.
Or, it is also possible to always set 0 for integral and differential at terminal input.
Title
Function
PID control waiting time
PID control
Proportional gain
Integral gain
Differential gain
PID forward/reverse characteristics
selection
Adjustment range
0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
Adjustment range
0-2400 [sec]
0: Disabled, 1: Enabled
0.01-100.0
0.01-100.0
0.00-2.55
0: Forward characteristic
1: Reverse characteristic
F-32
E6581595
Default setting
0
Default setting
0
0
0.30
0.20
0.00
0