7�3�7�5� Measurement system
Configuration
Address
variable
Measurement system
Option not available for the CVM-E3-MINI-FLEX and CVM-E3-MINI-FLEX-WiEth models.
(8)
7�3�7�6� Maximum demand
Configuration variable
Integration period
7�3�7�7� Display backlight
Configuration variable
Backlight
7�3�7�8� Activating the harmonics display screen
Configuration variable
Display of harmonics
7�3�7�9� CO
consumption and generation emissions�
2
Table 45: Modbus memory map: CO
Configuration variable
Tariff 1 consumption emissions ratio
Tariff 2 consumption emissions ratio
Tariff 1 generation emissions ratio
Tariff 2 generation emissions ratio
They have 1 decimal place.
(9)
Instruction Manual
Table 41: Modbus memory map: Measurement system
Measurement system
4-3Ph
0:
Three-phase network with 4 wires�
3-3Ph
1:
Three-phase network with 3 wires.
3-ArOM
2:
Three-phase network with 3 wires, Aron.
2B5C
3-2Ph
3:
Two-phase network with 3 wires.
2-2Ph
4:
Single-phase network with 2 wires, phase-to-phase.
2-1Ph
5:
Single-phase network with 2 wires, phase-to-neutral.
Table 42: Modbus memory map: Maximum demand
Maximum demand
Address
0: The maximum demand will not be calculated
274C
Table 43: Modbus memory map: Backlight
Backlight
Address
2B5E
Table 44: Modbus memory map: Display of harmonics
Display of harmonics
Address
2B62
CO
2
(9)
Valid data margin
Valid data margin
1 - 60 minutes
Valid data margin
1 - 999 seconds
Valid data margin
0: No
1: Yes
consumption and generation emissions�
2
emissions
Address
Valid data margin
2724
0 - 1�9999
0 - 1�9999
2725
2728
0 - 1�9999
2729
0 - 1�9999
Default
value
(8)
0
Default
value
0
Default value
300 s
Default value
1
Default
value
0
0
0
0