Current Status (Vendor Specific Yaskawa Electric (Ye) Assy) - 131 (0X83) - YASKAWA SI-N3 Technical Manual

Hide thumbs Also See for SI-N3:
Table of Contents

Advertisement

Name
Alarm
Fault
Uv
LOCAL/REMOTE
1000-Series, GA500: Multi-Function Digital
Output
GA700, GA800, FP605: Multi-Function Digital
Output 1
1000-Series, GA500: Multi-Function Photocoupler
1
GA700, GA800, FP605: Multi-Function Digital
Output 2
1000-Series, GA500: Multi-Function Photocoupler
2
GA700, GA800, FP605: Multi-Function Digital
Output 3
*2
Multi-Function Digital Output 4
ZSV
Output Frequency
*1
Terminals are different for different drive models. Refer to
for more information.
*2
Multi-function digital output 4 is not available for 1000-Series, GA500, GA800, or FP605 drives.

Current Status (Vendor Specific Yaskawa Electric (YE) Assy) - 131 (0x83)

Input Instance
Byte
0
1
131
2
3
YASKAWA SIEP C730600 84F DeviceNet Technical Manual
Drive Alarm
0: No Alarm
1: Alarm
Drive Fault
0: No Fault
1: During Fault
Undervoltage
0: -
1: Undervoltage
Run command is from network
0: Run command is not from network
1: Run command is from network
1000-Series, GA700, GA800, FP605: Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
GA500: Terminal MA/MB
0: MA/MB OFF
1: MA/MB ON
1000-Series, GA500: Terminal P1
0: P1 OFF
1: P1 ON
GA700, GA800, FP605: Terminal M3/M4
0: M3/M4 OFF
1: M3/M4 ON
1000-Series, GA500: Terminal P2
0: P2 OFF
1: P2 ON
GA700, GA800: Terminal P1
0: P1 OFF
1: P1 ON
FP605
0: MD/MF OFF
1: MD/MF ON
*1
Terminal P2
0: P2 OFF
1: P2 ON
Zero-Servo Completed
0: -
1: Zero-Servo Completed
Actual Drive Speed
Monitors drive output frequency.
Units are determined by parameter o1-03 [Frequency Display Unit Selection].
Unit is not affected by Speed Scale SS.
Bit 7
Bit 6
Bit 5
Fault
Alarm
Ready
1000-Series,
GA500: Multi-
Function
Photocoupler 2
ZSV
-
GA700,
GA800, FP605:
Multi-Function
Digital Output 3
9 Input Assemblies (Drive Produces)
Description
*1
*1
*1
Terminals that Change depending on the Model of the Drive on page 55
Bit 4
Bit 3
Speed Agree
Reset
1000-Series,
1000-Series,
GA500: Multi-
GA500: Multi-
Function
Function
Photocoupler 1
Digital Output
GA700,
GA700,
GA800, FP605:
GA800, FP605:
Multi-Function
Multi-Function
Digital Output 2
Digital Output 1
Actual Current (Low Byte)
Actual Current (High Byte)
Bit 2
Bit 1
REV Running
ZSP
LOCAL/
Uv
REMOTE
Bit 0
Running
-
61