6 Related Drive Parameters

EDS Files

For easy network implementation of drives equipped with the option, an EDS file can be obtained from:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: Check the back cover of these manuals.
For questions, contact Yaskawa or a Yaskawa representative.
Note:
Download the EDS file for SI-N3 option. The SI-N3 will not function as a slave in the network without the appropriate EDS file.
6
Related Drive Parameters
These parameters set the drive for operation with the option. Make sure that the parameter settings in this table are
correct before you start network communications.
Note:
Hex.: MEMOBUS addresses that you can use to change parameters over network communication are represented in hexadecimal
numbers.
No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
b1-02
Run Command Selection 1
(0181)
F6-01
Communication Error
Selection
(03A2)
F6-02
Comm External Fault (EF0)
Detect
(03A3)
F6-03
Comm External Fault (EF0)
Select
(03A4)
30
Selects the input method for frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Note:
• To start and stop the drive with the DeviceNet master device using serial communications,
set b1-02 = 3 [Run Command Selection 1 = Option PCB] or set the Net Control bit in the
assemblies or Control Supervisor Object. To control the frequency reference of the drive via
the master device, set b1-01 = 3 or set the Net Reference bit in the assemblies or AC/DC
object.
• The default setting is different for different drives. Refer to the instruction manual of your
specific drive for more information.
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
Note:
To start and stop the drive with the DeviceNet master device using serial communications, set
b1-02 = 3 or set the Net Control bit in the assemblies or Control Supervisor Object. To
control the frequency reference of the drive via the master device, set b1-01 = 3 [Frequency
Reference Selection 1 = Option PCB] or set the Net Reference bit in the assemblies or AC/
DC object.
Selects drive response when the drive detects a bUS [Option Communication Error] error during
communications with the option.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
Note:
• When you set this parameter to 3 or 4, the drive will continue operation after it detects a
fault. Separately prepare safety protection equipment and systems, for example fast-stop
switches.
• Refer to the drive manual to know if settings 4 and 5 are available. Settings 4 and 5 are
available in A1000 software versions PRG: 1021 and later.
• The setting range for 1000-Series drives is different for different software versions. Refer to
the Peripheral Devices & Options section of the drive instruction manual for more
information.
Selects the conditions at which EF0 [Option Card External Fault] is detected.
0 : Always Detected
1 : Detected during RUN Only
Sets the method to stop the motor or let the motor continue operating when the drive detects an
EF0 [Option Card External Fault].
0 : Ramp to Stop
1 : Coast to Stop
Description
YASKAWA SIEP C730600 84F DeviceNet Technical Manual
Default
(Range)
1
(0 - 4)
1
(0 - 3)
1
(0 - 5)
0
(0, 1)
1
(0 - 3)