3-Wire Control 2 (Vendor Specific Yaskawa Electric (Ye) Assy) - 110 (0X6E) - YASKAWA SI-N3 Technical Manual

Hide thumbs Also See for SI-N3:
Table of Contents

Advertisement

8 Output Assemblies (Drive Consumes)
Output Instance
Byte
0
1
2
3
109
4
5
6
7
Name
Configurable Output 1
Configurable Output 2
Configurable Output 3
Configurable Output 4

3-Wire Control 2 (Vendor Specific Yaskawa Electric (YE) Assy) - 110 (0x6E)

Output Instance
Byte
0
1
110
2
3
Bits
0
0->1 Start Drive
1
0->1 Stop Drive
2
0->1 Start Jog
3
Fault Reset
Set drive direction.
00: No Change
4 -5
01: Forward
10: Reverse
11: No Change
Digital Output 2
6
If H2-02 is set to 0x0F.
Digital Output 3
7
If H2-03 is set to 0x0F.
When the reference is from the option card, this changes the Accel/Decel rate. When the function value is 7, this will set Digital Input 6 in the drive.
00: No command
8 - 9
01: Accel1/Decel1 (C1-01/C1-02)
10: Accel2/Decel2 (C1-03/C1-04)
11: No command
10 - 11
Reserved
48
Data to be written to the MEMOBUS/Modbus address defined in parameter F6-64 [Dynamic Out Assembly 109 Param1].
If F6-64 = 0, then MEMOBUS/Modbus address 0x0001 (Drive Command) is used.
Data to be written to the MEMOBUS/Modbus address defined in parameter F6-65 [Dynamic Out Assembly 109 Param2].
If F6-65 = 0, then MEMOBUS/Modbus address 0x0002 (Frequency Reference) is used.
Data to be written to the MEMOBUS/Modbus address defined in parameter F6-66 [Dynamic Out Assembly 109 Param3].
If F6-66 = 0, then MEMOBUS/Modbus address 0x0004 (Torque Reference) is used.
Data to be written to the MEMOBUS/Modbus address defined in parameter F6-67 [Dynamic Out Assembly 109 Param4].
If F6-67 = 0, then MEMOBUS/Modbus address 0x0009 (Digital Outputs) is used.
Speed Reference (0.1 Hz) (Low Byte)
Speed Reference (0.1 Hz) (High Byte)
Description
Description
Configurable Output 1 (Low Byte)
Configurable Output 1 (High Byte)
Configurable Output 2 (Low Byte)
Configurable Output 2 (High Byte)
Configurable Output 3 (Low Byte)
Configurable Output 3 (High Byte)
Configurable Output 4 (Low Byte)
Configurable Output 4 (High Byte)
Description
Description
Control Word (Low Byte)
Control Word (High Byte)
YASKAWA SIEP C730600 84F DeviceNet Technical Manual

Advertisement

Table of Contents
loading

Table of Contents