5 Installation Procedure

LED Name
MS
NS

Power-Up Diagnostics

An LED test is performed each time the drive is powered up. The initial boot sequence can take several seconds.
After the LEDs complete the diagnostic LED sequence, the option is successfully initialized. The LEDs then
assume operational conditions as shown in
Sequence
1
2
3
4
5
5
Installation Procedure

Section Safety

DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before
servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, measure for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
WARNING
Electrical Shock Hazard. Do not operate the drive when covers are missing. Replace covers and shields
before you operate the drive. Use the drive only as specified by the instructions. Some figures in this section include drives
without covers or safety shields to more clearly show the inside of the drive. If covers or safety shields are missing from the
drive, it can cause serious injury or death.
WARNING
Electrical Shock Hazard. Only let approved personnel install, wire, maintain, examine, replace parts, and
repair the drive. If personnel are not approved, it can cause serious injury or death.
12
Table 4.2 Option LED States
Indication
Operating State
Color
Display
OFF
Power supply OFF
Green
ON
Option operating
Green
Flashing
Option initializing
Red
ON
Fatal error occurred
Red
Flashing
Non-fatal error occurred
Red/Green
Flashing
Option self-test
OFF
Power supply OFF or Offline
Green
ON
Online communications established
Online communications not
Green
Flashing
established
Red
ON
Ring fault
Communications time-out (non-
Red
Flashing
fatal)
Red/Green
Flashing
Comm error
Table
Table 4.3 Power-Up Diagnostic LED Sequence
Module Status (MS)
Green
Red
Green
Green
Green
There is no power to the drive.
The option is operating normally.
There are defects or errors in the settings.
• There is an incorrect baud rate setting.
• MAC ID duplication
The option detected a fatal (unrecoverable) error.
If the unit does not recover after you cycle power, you may need to replace
the option.
The option detected a non-fatal (recoverable) error.
The option is in self-test mode.
The drive is not on-line.
• Duplicate MAC ID test has not been passed.
• There is no power to the drive.
The option is online and has established connections.
• The option has established connections to other nodes.
The option is online without an established connection.
• Duplicate MAC ID test was passed and is online but has no open
connections to other nodes.
The option detected a communications device error.
• An error occurred disabling DeviceNet communications. (MAC ID
duplication or Bus off detected)
A communications time-out occurred.
Specific communication faulted device.
• The device detected a network access error and is in the communications
faulted state.
• The device then received and accepted an Identify communication fault
request-long protocol message.
4.2.
Network Status (NS)
OFF
OFF
Green
Red
OFF
YASKAWA SIEP C730600 84F DeviceNet Technical Manual
Description
Time (ms)
250
250
250
250
-

Advertisement