Standard Di/Do Control (Vendor Specific Yaskawa Electric (Ye) Assy) - 107 (0X6B) - YASKAWA SI-N3 Technical Manual

Hide thumbs Also See for SI-N3:
Table of Contents

Advertisement

8 Output Assemblies (Drive Consumes)
Name
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
External Fault
Fault Reset
1000-Series, GA500: Multi-Function Digital
Output
GA700, GA800, FP605: Multi-Function Digital
Output 1
1000-Series, GA500: Multi-Function Photocoupler
1
GA700, GA800, FP605: Multi-Function Digital
Output 2
1000-Series, GA500: Multi-Function Photocoupler
2
GA700, GA800, FP605: Multi-Function Digital
Output 3
*2
Multi-Function Digital Output 4
Speed Reference
*1
Terminals are different for different drive models. Refer to
for more information.
*2
Multi-function digital output 4 is not available for 1000-Series, GA500, GA800, or FP605 drives.
Standard DI/DO Control (Vendor Specific Yaskawa Electric (YE) Assy) - 107
(0x6B)
Output Instance
Byte
107
0
44
Terminal S4 Function Input
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Terminal S5 Function Input
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Terminal S6 Function Input
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON
Terminal S7 Function Input
0: Terminal S7 Function [H1-07] OFF
1: Terminal S7 Function [H1-07] ON
Terminal S8 Function Input
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
0: -
1: Fault Reset
1000-Series, GA700, GA800, FP605: Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
GA500: Terminal MA/MB
0: MA/MB OFF
1: MA/MB ON
This function is enabled only when H2-01 = F.
1000-Series, GA500: Terminal P1
0: P1 OFF
1: P1 ON
GA700, GA800, FP605: Terminal M3/M4
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 = F.
1000-Series, GA500: Terminal P2
0: P2 OFF
1: P2 ON
GA700, GA800: Terminal P1
0: P1 OFF
1: P1 ON
FP605
0: MD/MF OFF
1: MD/MF ON
This function is enabled only when H2-03 = F.
*1
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-04 = F.
Speed Reference
Sets drive speed reference.
Units are determined by parameter o1-03 [Frequency Display Unit Selection].
Unit is not affected by Speed Scale SS.
Bit 7
Bit 6
Multi-Function
Multi-Function
Multi-Function
Input 8
Input 7
Description
*1
*1
*1
Terminals that Change depending on the Model of the Drive on page 55
Bit 5
Bit 4
Bit 3
Multi-Function
Multi-Function
Input 6
Input 5
Input 4
YASKAWA SIEP C730600 84F DeviceNet Technical Manual
Bit 2
Bit 1
Multi-Function
Run Rev
Input 3
Bit 0
Run Fwd