Change Of State Response (Vendor Specific Yaskawa Electric (Ye) Assy); (0Xc7) - YASKAWA SI-N3 Technical Manual

Hide thumbs Also See for SI-N3:
Table of Contents

Advertisement

9 Input Assemblies (Drive Produces)
Bits
11
Reserved
12
Digital Input 1 Status
13
Digital Input 2 Status
14
Digital Input 3 Status
15
Digital Input 4 Status

Change of State Response (Vendor Specific Yaskawa Electric (YE) Assy) - 199

(0xC7)

Note:
The drive is compatible with option software versions 1107 and later.
Input Instance
Byte
0
1
2
3
199
4
5
6
7
Name
Run Fwd
Run Rev
External Fault
Fault Reset
NetRef
NetCtrl
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
80
Fields (# bits)
Bit 7
Bit 6
Multi-Function
Multi-Function
Input 4
Input 3
-
-
Fault
Alarm
NetCtrl (Status) NetRef (Status)
Forward Run command from Network
0: Forward Run command is not from network
1: Forward Run command is from network
Reverse Run command from Network
0: Reverse Run command is not from network
1: Reverse Run command is from network
External Fault command from Network
0: External Fault command is not from network
1: External Fault command is from network
Fault Reset command from Network
0: Fault Reset command is not from network
1: Fault Reset command is from network
Reference command from Network
0: Reference command is not from network
1: Reference command is from network
Run command from Network
0: Run command is not from network
1: Run command is from network
Terminal S3 command by Network
0: Terminal S3 Function [H1-03] OFF
1: Terminal S3 Function [H1-03] ON
Terminal S4 command by Network
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Terminal S5 command by Network
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Terminal S6 command by Network
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON
Terminal S7 command by Network
0: Terminal S7 Function [H1-07] OFF
1: Terminal S7 Function [H1-07] ON
Reserved
Digital Input 1 Status
Digital Input 2 Status
Digital Input 3 Status
Digital Input 4 Status
Bit 5
Bit 4
Bit 3
NetCtrl
NetRef
Fault Reset
Multi-Function
-
-
Input 8
Ready
Speed Agree
Reset
-
-
Output Frequency (Low Byte)
Output Frequency (High Byte)
Torque Actual (Low Byte)
Torque Actual (High Byte)
Description
YASKAWA SIEP C730600 84F DeviceNet Technical Manual
Description
Bit 2
Bit 1
External Fault
Run Rev
Multi-Function
Multi-Function
Input 7
Input 6
REV Running
ZSP
-
2nd Motor
Uv
Bit 0
Run Fwd
Multi-Function
Input 5
Running
oPE

Advertisement

Table of Contents
loading

Table of Contents