[Pr. PC20_Function selection C-7 (*COP7)]

Initial value
00000000h
[Pr. PC20.2_Undervoltage alarm selection]
Initial value
0h
Select the alarm or warning that occurs when the bus voltage drops to the undervoltage alarm trigger level.
0: [AL. 010 Undervoltage] occurs regardless of servo motor speed
1: [AL. 0E9 Main circuit off warning] occurs when the servo motor speed is 50 r/min (50 mm/s) or less, and [AL. 010] occurs
when over 50 r/min (50 mm/s).
[Pr. PC20.4_Input open-phase detection selection]
Initial value
0h
Enable or disable the detection of input open-phase detection function.
0: Automatic
1: Warning enabled
2: Alarm enabled
3: Disabled
The following table shows the input open-phase detection function for when "0" (automatic) is set.
Servo amplifier
1-axis
Multi axis
1 SERVO PARAMETER DETAILS
70
1.4 Extension setting servo parameters group ([Pr. PC_ _ ])
Setting range
Refer to the relevant detail No.
Setting range
Refer to the text
Setting range
Refer to the text
Servo amplifier main circuit
input voltage
3-phase AC
1-phase AC
Main circuit DC
3-phase AC
Main circuit DC
3-phase AC
Setting method
Common
Ver.
A0
Ver.
A0
Amplifier capacity
2 [kW] or less
2 [kW] or less
3.5 [kW] or more
3.5 [kW] or more
All capacity
Ver.
Refer to the relevant detail No.
Input open-phase detection
function
Disabled
Disabled
Warning occurrence
Disabled
Disabled