1MRS757256 F
9.2.1.2
9.2.1.3
PML630/Compact Load-Shedding Solution
Technical Manual
User-programmable inverse-time characteristics
The user can define curves by entering parameters into the following standard
formula.
GUID-775FD6DE-7F45-4112-A154-79F599BBA74F V1 EN
t[s] Operate time (in seconds)
A
set
Curve parameter A
Curve parameter B
B
set
Curve parameter C
C
set
E
set
Curve parameter E
I
Measured current
Start value
I>
set
k
set
Time multiplier
RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is an
earth-fault specific characteristic.
The RI-type is calculated using the formula
k
=
t s
[ ]
>
I
−
×
0 339 0 236
.
.
I
GUID-93D85F4E-FBFC-4B6D-BEF8-CBB1E8DCDB0D V1 EN
The RD-type is calculated using the formula
I
=
−
×
[ ]
5 8 1 35 In
.
.
t s
× >
k I
GUID-0624AC12-4B2A-43E7-8357-9D8EA9B38689 V1 EN
t[s]
Operate time (in seconds)
Time multiplier
k
set
I
Measured current
Start value
I>
set
General function block features
Section 9
(Equation 22)
(Equation 23)
(Equation 24)
341